NTI · Boiler · Ignition

Failed ignition and lockout

TRX150

What happens, in order

  1. Burner fails to light.
  2. Control runs ignition trials. Trials after the first are not immediate.
  3. Blower runs after each failed trial to purge the system.
  4. If the burner lights on any trial, normal operation resumes.
  5. If the burner does not light after the fifth trial, the control locks out.
  6. Lockout indicates a problem with the boiler, controls or gas supply. Call a service technician.
  7. If RESET is not pressed, the boiler resets automatically after one hour (codes 501 and 503).

Timings and thresholds

ItemValue
Blower purge after a failed ignition trialabout 5 seconds
Ignition trials before lockoutfive in total (four more after the first)
Automatic reset after lockout if RESET is not pressedone hour

Codes you may see during this

501 503

Applies to: TRX150

More NTI boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: NTI TRX150 manual, p. 97. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.