NTI · Boiler · Domestic hot water

Indirect tank (DHW) call

Trinity Tft

What happens, in order

  1. Tank aquastat (dry contact) closes SENSOR COM and DHW (terminals 6 and 9)
  2. Control turns on the DHW circulator output PUMP A
  3. In the single system circulator piping the CH circulator output PUMP C is turned off for the DHW call and PUMP B (boiler pump) stays on; with separate zone circulators PUMP A and PUMP C do the flowing and PUMP B is not used
  4. Control runs the ignition sequence
  5. Burner modulates to hold the DHW setpoint
  6. When the aquastat opens the burner shuts off, the blower post-purges and PUMP A drops out

Timings and thresholds

ItemValue
DHW call inputContact closure between terminals 6 and 9

Codes you may see during this

Hold / Lockout 79

Applies to: Trinity Tft60, Tft85, Tft110, Tft155, Tft175, Tft200, Tft250, Tft300, Tft399

Models

Tft60Tft85Tft110Tft155Tft175Tft200Tft250Tft300Tft399

More NTI boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: NTI Tft60-399 Installation and Operation Instructions (rev. 2012-04-09), Sec. 8.0 Lighting, Sec. 10.0 Piping, Sec. 15.0 Troubleshooting. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.