Daikin · Heat pump · Other
INTELLIGENT EYE energy saving operation
What happens, in order
- If nobody is detected for 20 minutes, the unit enters energy saving operation and the INTELLIGENT EYE lamp goes off.
- The set temperature is shifted for energy saving.
- In FAN mode only, the airflow rate is reduced slightly.
- When motion is detected again, the lamp lights and energy saving ends.
- In 2-area operation, if people are in both zones the airflow goes left. If nobody is in either zone, the airflow stays where it was.
Timings and thresholds
| Item | Value |
|---|---|
| No presence before energy saving starts | 20 minutes |
| Shift in HEAT | -2.0°C (-3.6°F) |
| Shift in COOL | +2.0°C (+3.6°F) |
| Shift in DRY | +2.0°C (+3.6°F) |
| Extra COOL/DRY shift when room exceeds 30.0°C (86°F) | +1.0°C (+1.8°F) |
Applies to: INTELLIGENT EYE models
Models
FTXM09/12WVJU9FTXM09/12VVJUFTXM18/24WVJU9FTXM18/24VVJU
More Daikin heat pump sequences
- 3-minute standby before restart · Startup
- Commissioning and test run · Startup
- Five-step commissioning set-up · Startup
- Preheating control before inverter start (open phase) · Startup
- System start-up procedure with evacuation and checks · Startup
- Triple evacuation method (recommended) · Pump/purge
- 3-D airflow auto-swing order · Other
- Commissioning sequence in the app · Other
Related
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS042113EA service manual, p. 45. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.