Daikin · Heat pump · Other

3-D airflow auto-swing order

FTXM-W/V

What happens, in order

  1. Vertical louvers move from right to left.
  2. Horizontal flaps move downward.
  3. Vertical louvers move from left to right.
  4. Horizontal flaps move upward.
  5. Repeat the vertical and horizontal swings while both are set to automatic.

Applies to: Indoor unit with horizontal and vertical swing set to automatic

Models

FTXM-W/V

More Daikin heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 38. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.