Daikin · Heat pump · Other

Compressor frequency control priority

FTXM-W/V

What happens, in order

  1. Determine the command frequency defrost time limit first, then forced cooling, then the indoor unit frequency command.
  2. Set the upper limit as the lowest of the limits from compressor protection, input current, discharge pipe temperature, heating peak-cut, freeze-up protection and defrost.
  3. Set the lower limit as the highest of the limits from four-way valve operation compensation, draft prevention and pressure difference upkeep.
  4. Avoid the prohibited frequencies, such as the power supply frequency.
  5. On compressor start, set the initial frequency from the D value of the indoor unit.

Applies to: FTXM-W/V wall mounted heat pump

More Daikin heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin FTXM-W/V service manual, p. 73-74. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.