Compressor frequency control priority
What happens, in order
- Determine the command frequency defrost time limit first, then forced cooling, then the indoor unit frequency command.
- Set the upper limit as the lowest of the limits from compressor protection, input current, discharge pipe temperature, heating peak-cut, freeze-up protection and defrost.
- Set the lower limit as the highest of the limits from four-way valve operation compensation, draft prevention and pressure difference upkeep.
- Avoid the prohibited frequencies, such as the power supply frequency.
- On compressor start, set the initial frequency from the D value of the indoor unit.
Applies to: FTXM-W/V wall mounted heat pump
More Daikin heat pump sequences
- 3-minute standby before restart · Startup
- Commissioning and test run · Startup
- Five-step commissioning set-up · Startup
- Preheating control before inverter start (open phase) · Startup
- System start-up procedure with evacuation and checks · Startup
- Triple evacuation method (recommended) · Pump/purge
- 3-D airflow auto-swing order · Other
- Commissioning sequence in the app · Other
Related
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Daikin FTXM-W/V service manual, p. 73-74. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.