Daikin · technician tips

Daikin service menus, test modes and resets

442 tips for air conditioner, air handler, furnace, general, heat pump: access codes, button combinations, test modes and the resets you need at the appliance.

Jump to: Access & passwords (9) · Button combinations (14) · Service & test modes (49) · Reset & cancel (39) · Settings shortcuts (55) · Commissioning (87) · Other (189)

Access & passwords

Installer and service menu codes, and how to get into them.

Dealer access levels

Air conditioner · ONE+, One Touch

The dealer access menu offers three levels: no access, view only, and adjust settings. Entry to commissioning screens is controlled from the dealer menu.

  1. Open the dealer/support menu.
  2. Select the access level needed for the job.
  3. Enter the 4-digit PIN if asked.

Applies to: Daikin Dealer access on ONE+ / One Touch thermostat

Source: daikin-one-touch-unitary-homeowner-settings.pdf, p. 3. Written in our own words; check the manual for your exact model.

Unlock a locked thermostat

Air conditioner · ONE+, One Touch

When the lock PIN is set, the thermostat asks for the 4-digit code before changes can be made.

  1. Touch the lock/unlock prompt.
  2. Enter the 4-digit code.
  3. Touch done to unlock.

Applies to: Locked ONE+ / One Touch thermostat

Source: daikin-one-touch-unitary-homeowner-settings.pdf, p. 3. Written in our own words; check the manual for your exact model.

Open dealer edit to reach installer set-up

Furnace · Daikin One+

Dealer edit under the dealer navigation menu opens the installer set-up screens, where advanced adjustments are made. Access is through the learn more icon after acknowledging the prompt. That icon shows the installer code.

  1. Go to dealer navigation and select dealer edit.
  2. Acknowledge the prompt.
  3. Tap the learn more icon.
  4. Read the installer code shown and use it to enter the installer set-up screens.

Applies to: Daikin One+ thermostat, installer set-up

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 43-44. Written in our own words; check the manual for your exact model.

Get to the installer code and set-up screens

General · Daikin One+

Acknowledging the prompt lets you tap the learn more icon. That icon shows the installer code, which gives access to the installer set-up screens.

  1. Acknowledge the prompt.
  2. Tap the learn more icon.
  3. Read the installer code shown on screen.
  4. Use the code to open the installer set-up screens.

Applies to: Daikin One+ installer access

Source: Daikin One+ Installation & Commissioning (S21), p. 38. Written in our own words; check the manual for your exact model.

Open dealer edit to revisit installer setup

General · Daikin One+

Dealer edit gives access to the installer set-up screens so advanced adjustments can be made or reviewed.

  1. Go to Dealer Navigation.
  2. Select Dealer edit.
  3. Make or review advanced adjustments on the installer set-up screens.

Applies to: Daikin One+ installer setup

Source: Daikin One+ Installation & Commissioning (S21), p. 37. Written in our own words; check the manual for your exact model.

Opening dealer edit with the installer code

Heat pump · Daikin One Touch

Dealer edit is where the installer makes advanced adjustments. Reach it by acknowledging the continue prompt. Then open the info icon in the top right corner to show the installer code, and close that screen with the X. Enter the code on the dealer edit screen and press the unlock thermostat button.

  1. Acknowledge the continue prompt to reach the dealer edit screen.
  2. Press the information icon in the top right corner to display the installer code.
  3. Note the code, then close the screen with the X.
  4. Enter the installer code on the dealer edit screen.
  5. Press the unlock thermostat button.

Applies to: Daikin One Touch smart thermostat, dealer navigation

Source: Daikin One Touch smart thermostat training module TRC-10, p. 56-57. Written in our own words; check the manual for your exact model.

Dealer and support access levels

Mini-split · Daikin ONE+

Dealer and support access is set to one of three levels: no access, view only, or adjust settings.

  1. Open the dealer or support screen.
  2. Select no access, view only, or adjust settings.
  3. To unlock, enter the 4-digit code and select unlock thermostat.

Applies to: Daikin ONE+ dealer and support access

Source: Daikin ONE+ and ONE Touch homeowner settings menu outline, p. 3. Written in our own words; check the manual for your exact model.

Lock the thermostat with a PIN

Mini-split · Daikin ONE+

The lock menu uses a 4-digit PIN to protect the thermostat from changes.

  1. Open the lock menu.
  2. Enter a 4-digit PIN.

Applies to: Daikin ONE+ thermostat lock

Source: Daikin ONE+ and ONE Touch homeowner settings menu outline, p. 1. Written in our own words; check the manual for your exact model.

Open remote controller service settings menu

Water heater · Mega-Q

Opens the service menu so Field Settings can be reached.

  1. Press and hold the Cancel button for 4 seconds or more.
  2. Select Field Settings in the Service Settings menu and press Menu/OK.

Applies to: Remote controller

Source: Mega-Q installation manual, p. 42. Written in our own words; check the manual for your exact model.

Button combinations

Key presses that open menus, show readouts or switch modes.

Run the unit without the remote controller

Air conditioner · FTXM

The indoor unit ON/OFF switch starts and stops operation when the remote controller is missing or has no batteries. It uses the AUTO setting at 77°F (25.0°C) with AUTO airflow.

  1. Press the indoor unit ON/OFF switch once to start.
  2. Press it again to stop.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin FTXM operation manual, p. 5. Written in our own words; check the manual for your exact model.

Start the wireless LAN connection from the remote

Air conditioner · FTXM

Holding the wireless LAN button on the remote controller for 5 seconds starts the wireless LAN connection. The adapter is inside the outdoor unit front panel.

  1. Hold the wireless LAN button on the remote controller for 5 seconds.
  2. Use the SSID and KEY printed on the outdoor unit for the connection.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin FTXM operation manual, p. 7-8. Written in our own words; check the manual for your exact model.

Switch display between Fahrenheit and Celsius

Air conditioner · FTXM WVJU9

Hold the remote's TEMP-related pair (the key labelled with the arrow and the TIMER button) together for about 5 seconds. The switch only works while a temperature is on the display. The unit confirms the change with a beep.

  1. Make sure a temperature is currently shown on the remote display.
  2. Press the arrow button and the TIMER button together and hold for about 5 seconds.
  3. Check the display now shows the other unit (F to C or C to F).

Applies to: Remote controller, all FTXM09/12/18/24WVJU9 models

Source: Daikin Room Air Conditioner operation manual, p. 11. Written in our own words; check the manual for your exact model.

Lock or unlock the operating panel

General · Humidifying Air Purifier

Holding the LOCK button for about 2 seconds turns the lock on or off. While locked, button presses trigger 3 short beeps. Unplugging the unit cancels the lock.

  1. Hold the LOCK button for about 2 seconds to set or cancel the lock.

Applies to: Operating panel

Source: Daikin MCKB70YSAU installation & operation manual, p. 11. Written in our own words; check the manual for your exact model.

Start the ventilator and enter Energy Savings mode

General · Daikin One Powered Ventilator

First power-up uses the ON button, which runs continuous airflow at the factory default of 30 CFM.

  1. With power on, the screen first shows OFF.
  2. Press ON to show temperature and humidity and start 30 CFM continuous airflow.
  3. To enter Energy Savings mode, press ON/OFF/ENERGY SAVINGS until Energy Savings shows on the left side of the display.

Applies to: DQ-P-16-100

Source: IO-DPV installation manual, p. 6-8. Written in our own words; check the manual for your exact model.

Using the dial as a home button

General · Daikin One+

The thermostat has a physical dial on the right for manual setpoint changes. In normal mode, pressing the centre of the dial returns to the primary screen from anywhere. The touch screen on the left is used for navigation by tapping icons.

  1. Turn the right-side dial to change manual setpoints.
  2. Press the centre of the dial at any time in normal mode to return to the primary screen.
  3. Tap icons on the left touch screen to open each screen.

Applies to: Daikin One+ S21 thermostat

Source: Daikin One+ Smart Thermostat Installation & Commissioning (S21) manual, p. 6. Written in our own words; check the manual for your exact model.

Enter Setting Mode 1 on the outdoor unit display

Heat pump · DX6VS, DZ6VS

Setting Mode 1 is entered from the display screens with a button hold. Use it to adjust the system settings listed in the Screen 3 table.

  1. Hold RECALL to enter setting mode.
  2. Press LEARN to move between screens.
  3. Press RECALL to step to the next setting number.
  4. Press TEST to change the selected setting.
  5. Press TEST again to save the change and return to setting mode.
  6. Some outdoor unit builds show setting numbers up to 3.12. Check the screen 3 table for the items your unit supports.

Applies to: Outdoor unit 7-segment display

Source: SiUS612209EA service instructions, p. 40. Written in our own words; check the manual for your exact model.

Enter Setting Mode 2 on the outdoor unit display

Heat pump · DX6VS, DZ6VS

Setting Mode 2 holds the installer and service parameters, including defrost, charge mode and RPS limits.

  1. From setting mode 1, press LEARN to change the setting display.
  2. Hold RECALL and TEST together to enter Setting Mode 2 (Screen 4).
  3. Press RECALL to step through the setting numbers.
  4. Press TEST to change the selected setting.
  5. Press TEST to save and return to setting mode.

Applies to: Outdoor unit 7-segment display

Source: SiUS612209EA service instructions, p. 41. Written in our own words; check the manual for your exact model.

POWERFUL and Wireless LAN buttons together (ARC466A70 / ARC466A71)

Heat pump · FTXM-W, FTXM-V

Holding the POWERFUL button and the Wireless LAN button together for 5 seconds starts POWERFUL operation on the remote, and it also starts the wireless LAN connection.

  1. Hold the POWERFUL button and the Wireless LAN button together for 5 seconds.

Applies to: FTXM-W/V wall mounted units with ARC466A70 or ARC466A71 remote

Source: SiUS042113EA service manual, p. 85. Written in our own words; check the manual for your exact model.

Reach screens 1 to 4 on the mode display

Heat pump · DX6VS / DZ6VS

Each screen is reached by holding a button from the screen before it. Screen 4 uses two buttons together.

  1. From screen 0, hold RECALL for 5 seconds to reach screen 1 (error history).
  2. From screen 1, hold RECALL for 5 seconds to reach screen 2 (monitoring).
  3. From screen 2, hold RECALL for 5 seconds to reach screen 3 (setting mode 1).
  4. From screen 0, hold RECALL and TEST together for 5 seconds to reach screen 4 (setting mode 2).

Applies to: DX6VS / DZ6VS outdoor unit control board

Source: Daikin SiUS612209EB service instructions, p. 37. Written in our own words; check the manual for your exact model.

Reach the mode display screens with the RECALL and TEST buttons

Heat pump · DX6VS / DZ6VS outdoor unit mode display

The 3-digit mode display on the outdoor board has five screens. The first digit shows the screen number.

  1. Screen 0 is the default screen and shows the most recent fault.
  2. Hold RECALL for 5 seconds from screen 0 to reach screen 1 (error history).
  3. Hold RECALL for 5 seconds from screen 1 to reach screen 2 (monitoring).
  4. Hold RECALL for 5 seconds from screen 2 to reach screen 3 (setting mode 1).
  5. Hold RECALL and TEST together for 5 seconds to reach screen 4 (setting mode 2).
  6. Press LEARN to return to screen 0.

Applies to: Outdoor unit control board mode display

Source: Daikin SiUS612209EA service instructions, p. 37. Written in our own words; check the manual for your exact model.

COMFORT AIRFLOW operation

Mini-split · FTXM-W/V

Comfort button turns on a flap pattern aimed to avoid direct airflow on occupants. Flaps go up in cool/dry and down in heat, and fan speed is not user-selectable in this mode. The flaps return to their previous memory position when it is stopped.

  1. Press the Comfort button to start COMFORT AIRFLOW; the icon shows on the display.
  2. Press Comfort again to stop; the icon clears and flaps return to the saved position.
  3. Airflow rate is forced to AUTO while this mode is active.
  4. Do not run with POWERFUL; the last function pressed takes priority.
  5. Setting a manual up/down flap direction cancels COMFORT AIRFLOW.
  6. In heating, an obstruction under the unit can stop warm air reaching the room centre, making the room slow to warm.

Applies to: FTXM-W/V wall mounted indoor units

Source: SiUS042113EA service manual, p. 40. Written in our own words; check the manual for your exact model.

ECONO operation (Econo/Quiet button)

Mini-split · FTXM-W/V

ECONO cuts maximum running current and power use, which also lowers maximum capacity. It can be used in cooling, heating, dry and auto, but only while the unit is running. It cannot be combined with POWERFUL, and the latest command takes priority.

  1. Press the Econo/Quiet button on the wireless remote and choose the wanted option; each press changes the LCD option.
  2. To cancel, press Econo/Quiet until no icon shows.
  3. Pressing ON/OFF also cancels it and clears the ECONO icon.
  4. Expect less heating or cooling effect at the lower power level.
  5. If power consumption is already low, ECONO will not reduce it further.

Applies to: FTXM-W/V wireless remote

Source: SiUS042113EA service manual, pp. 42-43. Written in our own words; check the manual for your exact model.

Service & test modes

Forced fan, low and high fire, test and diagnostic modes, error history and live data.

Charge mode: how it works and when to use it

Air conditioner · DX6VS, DZ6VS

Use charge mode only when the required charge cannot be added without running the system, or when adjusting subcooling. It runs the system at full capacity for about two hours, then returns to normal thermostat control.

  1. Turn off the electric heater or gas furnace.
  2. Finish the system start-up test first.
  3. Set the thermostat to OFF before selecting CHARGE MODE.
  4. Use dedicated PVE oil gauges and hoses.

Applies to: Charging

Source: Daikin DX6VS/DZ6VS outdoor unit installation & service reference, p. 29. Written in our own words; check the manual for your exact model.

Charge verification test status messages

Air conditioner · One+ and Touch

Charge verification test reports a numbered status. Use it to decide whether to adjust charge with gauges or wait for the system to settle.

  1. Start the Charge Mode run test only on inverter AC or heat pump systems.
  2. Status 0 means system test required; status 1 means initial test successful.
  3. Status 1 (R410A and R32 lists differ): outdoor temperature out of range, adjust charge with gauges.
  4. Status 2: system stabilizing; wait.
  5. Status 3: outdoor fan speed not in range.
  6. Status 4: compressor speed not in range.
  7. Status 5: indoor superheat not in range.
  8. Status 6: subcool in range, shows subcool value.
  9. Status 7: subcool in range, confirming continuous operation.

Applies to: R410A and R32 inverter AC and heat pumps

Source: Daikin One+ and Touch Thermostat Commissioning Menu Outline, p. 4. Written in our own words; check the manual for your exact model.

Confirm the wireless LAN connection

Air conditioner · Atmosphera

Checks that the wireless adapter is talking to the network, using the indoor unit LED.

  1. With operation stopped, press and hold the button for 5 seconds.
  2. Press to confirm the selected setting. The LCD shows the wireless symbol and the indicator blinks.
  3. Check the wireless adapter lamp on the indoor unit against the status table.

Applies to: Wireless LAN connection adapter

Source: Daikin Atmosphera operation manual, p. 41. Written in our own words; check the manual for your exact model.

Optional run tests

Air conditioner · One+ and Touch

Run tests in the optional tests menu energize one piece of equipment at a time for checkout. Each runs until stopped or until setup steps finish.

  1. Select Cooling, Fan, Heat Pump Heat, Gas Heat, Electric Heat or Pump Down from the optional tests menu.
  2. Press Run test to start and Stop to end it.
  3. Cooling and heat options appear only if the system has those capabilities.
  4. Pump Down is for all-climate HP, enhanced 5-ton and some older inverter models.
  5. Refrigerant leak test is for R32 EEV air handlers only.

Applies to: Unitary systems

Source: Daikin One+ and Touch Thermostat Commissioning Menu Outline, p. 4. Written in our own words; check the manual for your exact model.

Run an equipment test from System Test

Air conditioner · Daikin One+, Touch thermostat

System Test has run options for each mode. Each test runs until you stop it or the setup steps are finished. Some tests only show for certain equipment.

  1. Open System Optimization, then System Test.
  2. Pick the test: Cooling, Fan, Heat Pump Heat, Gas Heat, Electric Heat, or Pump Down.
  3. Select Run test and watch the equipment.
  4. Select Stop when finished.

Applies to: Cooling only if system has cooling. Pump Down only on all-climate HP, enhanced 5-ton and some older inverter models.

Source: Daikin One+ commissioning menu outline v3.9, p. 4. Written in our own words; check the manual for your exact model.

Read the last six faults (fault recall)

Air handler · DV**FEC / DFVE**, CAPE(A)* / CHPE*

The control board has a push button that shows the last six faults on the 2-digit display. The control must be in standby (no thermostat inputs) first.

  1. Make sure the control is in standby with no thermostat inputs.
  2. Press and hold FAULT RECALL for 2 to 5 seconds. The display shows solid "--".
  3. Release the button. The display shows the most recent fault.
  4. Press FAULT RECALL again to step back through older faults.
  5. After the last fault the display shows "--" and the control returns to standby.
  6. Repeated identical faults show at most three times.
  7. If the button is left alone for more than 3 minutes, the control returns to standby.
  8. Holding the button longer than 15 seconds also returns the control to standby.

Applies to: EEV indoor units with 2-digit display and FAULT RECALL button

Source: SiUS612209EA service instructions, p. 25. Written in our own words; check the manual for your exact model.

Recall the last 6 faults on EEV indoor units

Air handler · DV**FEC, DFVE**, CAPE(A)*, CHPE*

The indoor unit control keeps a fault history that can be read from the fault recall button.

  1. Make sure the system is in standby with no thermostat inputs.
  2. Press and hold the fault recall button for more than 2 seconds.
  3. Read the recalled faults in order, from most recent to least recent.

Applies to: EEV indoor units

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 80. Written in our own words; check the manual for your exact model.

Recall the last 6 faults on the EEV air handler

Air handler · DV**FEC, DFVE**

The fault recall history is kept on the indoor integrated control.

  1. Make sure the unit is in standby with no thermostat inputs.
  2. Press and hold the FAULT RECALL button for more than 2 seconds.
  3. Read the faults back; they show from most recent to least recent, up to 6.

Applies to: EEV air handler wiring/integrated control

Source: Daikin SiUS612209EA service instructions, p. 75-80 (wiring diagram notes). Written in our own words; check the manual for your exact model.

Recall the last six faults on an EEV indoor unit

Air handler · DFVE EEV air handler, DV**FEC EEV air handler, CAPE / CHPE EEV cased coil

The control keeps a fault history. The last six faults can be read back, most recent first.

  1. Make sure the unit is in standby with no thermostat inputs.
  2. Press and hold the FAULT RECALL button for more than 2 seconds.
  3. Read the stored faults from the most recent to the oldest.

Applies to: EEV indoor units with integrated control (DFVE / DV**FEC / CAPE / CHPE)

Source: Daikin SiUS612209EB service instructions, p. 80. Written in our own words; check the manual for your exact model.

Recall the last six faults on the EEV indoor unit

Air handler · DV**FEC, DFVE**, CAPE(A)*, CHPE*

Use the FAULT RECALL button on the control board to step through the six most recent faults. The unit must be in standby (no thermostat inputs). Repeated identical faults show a maximum of three times. The recall times out after 3 minutes idle.

  1. Confirm the control is in standby with no thermostat inputs.
  2. Press FAULT RECALL for 2 to 5 seconds until the display shows solid "--".
  3. Release the button. The display shows the most recent fault.
  4. Press FAULT RECALL again to step to older faults.
  5. At the end of the list the display shows "--" and returns to standby.
  6. Holding the button longer than 15 seconds returns the control to standby.

Applies to: EEV indoor units (control board 7-segment display). Active codes of the gas furnace or blower are on their own boards.

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 25. Written in our own words; check the manual for your exact model.

Run refrigerant leak test on R32 EEV air handlers

Air handler · Daikin One+, Touch thermostat

The refrigerant leak test is only shown for R32 air handlers with EEV control.

  1. Open System Optimization, then Optional Tests.
  2. Select Refrigerant Leak Test.
  3. Select Run test and then Stop when the test is complete.

Applies to: R32 EEV air handlers only

Source: Daikin One+ commissioning menu outline v3.9, p. 4. Written in our own words; check the manual for your exact model.

Error history log

Furnace · Daikin One+

The thermostat logs alerts with an error code. Entries are shown in white when not critical and yellow when critical.

  1. Open System Optimization and select Error history.
  2. Check each logged code; yellow entries are critical, white entries are not critical.

Applies to: Daikin One+ thermostat

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 33. Written in our own words; check the manual for your exact model.

Optional tests

Furnace · Daikin One+

Each optional test has a short description. The thermostat only shows tests the system can perform.

  1. Open Optional Tests from System Optimization and read the test description.
  2. Press the stop test button to end a running optional test.

Applies to: Daikin One+ thermostat

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 36. Written in our own words; check the manual for your exact model.

Run the R-32 leak function test (A2u)

Furnace · Daikin DR96TN/DD96TN

Simulates an R-32 leak so you can check the furnace response; it only works when no alarm or fault is active.

  1. Press the left or right switch until A2u shows
  2. Press the center switch, choose yes with the left or right switch
  3. Press the center switch to confirm and start the test
  4. Select no in the same menu to stop it early

Applies to: Daikin DR96TN/DD96TN two-stage furnaces

Source: Daikin DR96TN-DD96TN service RSD6612304 (05-2024), R-32 Information - A2L Verification p.10. Written in our own words; check the manual for your exact model.

Status menu

Furnace · Daikin One+

The status menu shows data for the selected equipment as a scrollable list.

  1. Return to the installer set-up screen to open the status list at any time.
  2. Select the equipment and scroll through its data.

Applies to: Daikin One+ thermostat

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 37. Written in our own words; check the manual for your exact model.

Charge verification mode

Heat pump · Daikin One Touch

Charge verification mode keeps the system running steadily for about 1 to 2 hours so refrigerant can be charged through the suction charge port. It stops when the stop test button is pressed or when the test completes. Follow the equipment installation manual for proper charging.

  1. Select Charge Verification Mode in System Optimization.
  2. Charge through the suction charge port while the system runs steadily.
  3. Press stop test or wait for completion to end the mode.
  4. Refer to the equipment installation manual for the charging procedure.

Applies to: Inverter heat pump or air conditioner

Source: Daikin One Touch smart thermostat training module TRC-10, p. 48. Written in our own words; check the manual for your exact model.

Charging mode requires indoor heat off

Heat pump · DX6VS, DZ6VS

Charge mode (Setting Mode 2 item 9) and the system verification test will not start if the thermostat has indoor heat on.

  1. Set the thermostat to off before entering charge mode.
  2. Turn off any furnace or secondary heater before starting the system verification test.

Applies to: Daikin communicating system with outdoor unit

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 47. Written in our own words; check the manual for your exact model.

Control modes: normal, forced and power transistor test

Heat pump · FTXM-W/V

The control runs in normal operation mode, forced operation mode, or power transistor test mode. Forced operation includes forced cooling for pump-down. A dry command is treated as cooling unless the manual states otherwise.

Applies to: FTXM-W/V wall mounted heat pump

Source: Daikin FTXM-W/V service manual, p. 73. Written in our own words; check the manual for your exact model.

D-Checker: connect cable and verify COM port

Heat pump · DX6VS, DZ6VS

The cable plugs into X41A on the outdoor PCB. Small chassis (1.5 to 3.0 ton) and large chassis (3.5 to 4.0 ton) both use X41A on their boards.

  1. Plug the D-Checker USB end into the laptop.
  2. Plug the terminal end into X41A on the outdoor unit PCB.
  3. Open Device Manager and go to the hardware list.
  4. Expand COM Ports and note the port the USB cable uses.
  5. Select that port in D-Checker options.

Applies to: DX6VS / DZ6VS small and large chassis outdoor units

Source: Daikin SiUS612209EA service instructions, p. 129. Written in our own words; check the manual for your exact model.

D-Checker: install software and set options

Heat pump · DX6VS, DZ6VS

D-Checker is a PC tool that logs inverter sensor data and actuator status from the outdoor unit through a dedicated cable. Supported data varies by model. It does not support monitoring or recording several outdoor units at once.

  1. Copy the latest D-Checker version to any folder on the laptop and run it.
  2. Confirm you have the latest version. Ask Daikin tech support if unsure.
  3. Open Options (F6).
  4. Select the COM port, the unit of measurement and the sampling rate (manual recommends 5 seconds).
  5. Enter the service office (your name or department) and the responsible person.
  6. Press OK to save.

Applies to: DX6VS / DZ6VS inverter outdoor units

Source: Daikin SiUS612209EA service instructions, p. 128. Written in our own words; check the manual for your exact model.

D-Checker: system detection and recording

Heat pump · DX6VS, DZ6VS

D-Checker cannot talk to a system that is in sleep or hibernate mode. A wrong COM port or a sleeping system causes detection to fail. Each detected piece of equipment shows as its own icon.

  1. Create a new customer record with at least a customer ID (Recording, Add new, F3).
  2. Select the customer (F2) and click Auto select (F2) to detect the system.
  3. If detection fails, check the COM port or wake the system from sleep, then try again.
  4. When the system name appears, click OK (F1).
  5. To record, click Start Rec. (F6). Use Graph View (F2) to choose data points from Op. Selected Data (F4) or Op. All Data (F3).

Applies to: DX6VS / DZ6VS outdoor units with D-Checker

Source: Daikin SiUS612209EA service instructions, pp. 130-132. Written in our own words; check the manual for your exact model.

Enter cascade unit address setting mode

Heat pump · Mega-Q

Use an insulating rod on the push buttons through the inspection port. Touching live parts can cause electric shock. Close the electrical box cover before power-up.

  1. Turn on power to the heat source unit, cascade unit and tank control board.
  2. Open the cascade unit upper front panel and the service cover of the electrical components box.
  3. In normal mode, press BS1 (page break) for more than 5 seconds to enter setting mode.
  4. Press BS2 (operation) 13 times until the display shows 2 1 3.
  5. Press BS3 (confirm). The current value shows, initial value is 0.
  6. Use BS2 to select the address (OFF OFF 1 to 8).
  7. Press BS3 to lock the address. The blinking display changes to steady.
  8. Press BS3 again. The display shows 2 0 0.
  9. Press BS1 to finish. The display shows OFF OFF OFF.
  10. If confused, press BS1 to return to normal mode and start again from step 1.
  11. Close the service cover, then repeat for each cascade unit.

Applies to: Mega-Q cascade unit A1P board

Source: Mega-Q installation manual, p. 35-36. Written in our own words; check the manual for your exact model.

Enter Setting Mode 1 and change a setting

Heat pump · DX6VS, DZ6VS

Setting Mode 1 holds the installer-adjustable airflow and mode settings. Parameter values blink at 0.4 s on / 0.4 s off while you are in the setting.

  1. Hold RECALL to enter the setting mode.
  2. Press RECALL to step through the setting screens until the item you need is shown.
  3. Press TEST to change the highlighted setting.
  4. Press RECALL to increase the value shown.
  5. Press TEST again to save the change and return to setting mode.
  6. Press LEARN to return from one setting screen to the other as needed.

Applies to: Outdoor unit control board 7-segment display

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 40. Written in our own words; check the manual for your exact model.

Enter Setting Mode 2 (Screen 4)

Heat pump · DX6VS, DZ6VS

Setting Mode 2 holds the system-level settings such as defrost interval, compressor speed limits and boost modes.

  1. From Setting Mode 1, press LEARN.
  2. Hold RECALL and TEST together to open SETTINGS MODE 2 (Screen 4).
  3. Press RECALL to move to the setting you need.
  4. Press TEST to change the setting.
  5. Press RECALL to increase the number.
  6. Press TEST to save and return to setting mode.

Applies to: Outdoor unit control board 7-segment display

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 41. Written in our own words; check the manual for your exact model.

Force a defrost from the thermostat

Heat pump · DX6VS, DZ6VS

A technician can start a defrost cycle on a heat pump from the thermostat for testing. Use it only when the outdoor coil needs to be checked for frost.

  1. In heating mode, select the force defrost option on the thermostat.
  2. Watch the outdoor unit go into defrost.
  3. Defrost ends when the coil reaches about 54 °F and the defrost sensor reading meets the control's criteria.

Applies to: Heat pump outdoor units with inverter control board

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 7. Written in our own words; check the manual for your exact model.

Optional tests

Heat pump · Daikin One Touch

Optional tests show a stop test button while they run. The thermostat only lists tests the connected equipment can perform.

  1. Open the optional tests list in full set-up.
  2. Pick a test and use stop test to end it early if needed.

Applies to: Daikin One Touch thermostat, full set-up

Source: Daikin One Touch installation guide, p. 49. Written in our own words; check the manual for your exact model.

Outdoor coil cleaning (qualified servicer only)

Heat pump · DX6VS, DZ6VS

Cleaning the outdoor coil is a qualified-servicer task. Restricted airflow from dirt, leaves or debris causes poor operation and damage. Damaged coil tubing leaks refrigerant, so an inexperienced person should not clean it.

  1. Disconnect all power before servicing. Multiple power sources may be present.
  2. Hire a qualified servicer to clean the outdoor coil.
  3. Do not let untrained people clean the coil, as puncturing the tubing causes refrigerant loss.

Applies to: Outdoor coil

Source: Daikin DX6VS/DZ6VS installation & service reference, p. 57. Written in our own words; check the manual for your exact model.

Outdoor unit 3-digit mode display overview

Heat pump · DX6VS, DZ6VS

The 3-digit display on the PCB is a backup to the thermostat for reading faults, fault history, monitoring and setting. It has five modes: fault code (screen 0, default), fault history (screen 1, 6 recent faults), monitoring (screen 2), setting mode 1 (screen 3) and setting mode 2 (screen 4). Use the TEST, RECALL, LEARN and MODES buttons to navigate. The display blinks at 0.4 seconds on and 0.4 seconds off. The button sequences and tables are not fully on these pages.

Applies to: DX6VS/DZ6VS outdoor unit control board

Source: Daikin DX6VS/DZ6VS outdoor unit installation manual, p. 48. Written in our own words; check the manual for your exact model.

Reach each display screen

Heat pump · FIT

Screens are reached by holding buttons for about 5 seconds, one screen at a time.

  1. From Screen 0, hold RECALL for 5 seconds to reach Screen 1.
  2. From Screen 1, hold RECALL for 5 seconds to reach Screen 2.
  3. From Screen 2, hold RECALL for 5 seconds to reach Screen 3.
  4. From any screen, hold RECALL and TEST together for 5 seconds to reach Screen 4.
  5. To go back to Screen 0 at any time, press LEARN.

Applies to: FIT outdoor units

Source: Daikin FIT outdoor unit installation & service reference, p. 49. Written in our own words; check the manual for your exact model.

Read the outdoor unit error code history

Heat pump · DX6VS, DZ6VS

Screen 0 shows the present error code. Screen 1 shows the six most recent codes, with latest first.

  1. Go to Screen 0 to read the present error code.
  2. Go to Screen 1 to read the error history, from latest to 6th.
  3. Check history when a code is not shown on the thermostat, for example E57.

Applies to: Outdoor unit 7-segment display

Source: SiUS612209EA service instructions, p. 42. Written in our own words; check the manual for your exact model.

Run inverter charge verification

Heat pump · Daikin One+, Touch thermostat

Charge Verification runs a test on inverter AC or heat pump systems. R410A and R32 units use different charge verification menus, and the status number shows progress.

  1. Open System Optimization, then Charge Verification.
  2. Confirm the refrigerant type shown matches the unit.
  3. Select Run test and monitor the test status number.
  4. Use the status message to decide next steps. Status 1 for out-of-range outdoor temperature means adjust charge with gauges.
  5. Select Stop when done.

Applies to: Inverter AC and heat pumps. R410A and R32 versions differ.

Source: Daikin One+ commissioning menu outline v3.9, p. 4. Written in our own words; check the manual for your exact model.

Run system verification (start-up) test

Heat pump · DX6VS, DZ6VS

The start-up test is needed when the thermostat shows E11. It is run from the thermostat menu or from Setting Mode 2 item 4. The code clears when testing is complete.

  1. Make sure the indoor heat source is off at the thermostat, because heat on blocks the test.
  2. Run the SYSTEM START-UP TEST from the thermostat menu.
  3. Confirm E11 clears when the test completes.

Applies to: Daikin communicating system with outdoor unit

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 48. Written in our own words; check the manual for your exact model.

Service diagnosis method 1 (remote controller ARC466A70/A71)

Heat pump · FTXM-W/V

Scrolls through error codes on the remote controller temperature display. A short beep or two consecutive beeps means the code does not match. Not all codes are shown, so use method 2 if the code is not found.

  1. Hold the Timer Cancel button for 5 seconds. 00 is shown on the temperature display.
  2. Press Timer Cancel repeatedly until a long beep sounds. The displayed code is the error code.
  3. To return to normal mode, hold Timer Cancel for 5 seconds, or leave the remote untouched for 60 seconds.

Applies to: ARC466A70 and ARC466A71 remote controllers

Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 93. Written in our own words; check the manual for your exact model.

Service diagnosis method 1 code list

Heat pump · FTXM-W/V

Method 1 scrolls through the following codes in order: 00, A5, E7, F3, F6, L3, L4, L5, U4, E6, H6, U0, H0, A6, C7, A3, H8, H9, C9, CC, C4, C5, CH, J3, J6, J8, E5, A1, E1, UA, U3, UF, UH, P4, H7, U2, EA, AH, FA, E8, E3, H3, F8, A0.

  1. Use this list to match what the remote controller scrolls through.
  2. Codes not described in the troubleshooting section are noted in the code table.

Applies to: ARC466A70 and ARC466A71 remote controllers

Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 92. Written in our own words; check the manual for your exact model.

Service diagnosis method 2 (service check mode)

Heat pump · FTXM-W/V

Uses the left and right numbers of the code. Beeps tell you which number matches the error code.

  1. Press the centre of the Temp button and the Mode button together. 5C appears on the LCD.
  2. Select 5C (service check) with the Temp up or down button.
  3. Press Mode to enter service check. The left-side number blinks.
  4. Change the left number with Temp up or down until you hear two consecutive beeps or a long beep.
  5. Listen: a single beep means the left number does not match. Two consecutive beeps mean the left number matches but the right does not. A long beep means both match.
  6. Press Mode. The right-side number blinks. Change it with Temp up or down until you hear the long beep.
  7. The numbers at the long beep form the error code. Look it up in the code table (p. 96).
  8. Hold Mode for 5 seconds to exit service check. The controller also returns to normal after 60 seconds untouched.

Applies to: FTXM-W/V wall mounted units with remote controller

Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 94-95. Written in our own words; check the manual for your exact model.

Service monitor PCB (A2P) switches and LEDs

Heat pump · FTXM-W/V

The service monitor PCB has a green LED (LEDA) and several switches. SW1 to SW4 and LED1 to LED5 do not work on this board. SW5-2 sets warmer airflow, SW5-3 sets the facility setting, and SW6-1 controls the drain pan heater.

  1. Use SW5-2 only for the warmer airflow setting; see page 161 for the options.
  2. Use SW5-3 only for the facility setting; see page 160 for the options.
  3. Use SW6-1 for the drain pan heater; see page 163 for the options.
  4. Do not expect SW1 to SW4 or LED1 to LED5 to respond.

Applies to: Outdoor unit service monitor PCB (A2P), FTXM-W/V series

Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 34. Written in our own words; check the manual for your exact model.

Start power transistor test from the indoor unit

Heat pump · FTXM-W/V

Used with the inverter analyzer to drive the inverter output for a test.

  1. Turn the power on.
  2. Select FAN operation with the Mode button on the remote controller.
  3. Press the centre of the Temp button and the Mode button together.
  4. Select T with the Temp up or Temp down button.
  5. Press Mode to start the power transistor test.

Applies to: Indoor unit remote controller test mode with inverter analyzer

Source: Daikin Inverter Pair FTXM-W/V service manual SiUS042113EA, p. 151. Written in our own words; check the manual for your exact model.

Status menu

Heat pump · Daikin One Touch

The status menu shows data for the selected equipment in a scrollable list. You can get back to it at any time from the installer set-up screen.

  1. Return to the installer set-up screen.
  2. Open the status menu and scroll to the equipment data you need.

Applies to: Daikin One Touch thermostat, installer set-up

Source: Daikin One Touch installation guide, p. 50. Written in our own words; check the manual for your exact model.

System optimization menu

Heat pump · Daikin One Touch

System Optimization includes System Test (inverter units only), Charge Verification Mode (inverter units only), Optional Test, Error History, thermostat calibration for temperature and humidity, and Status. Error History logs alerts with an error code: white is not critical, yellow is critical. Status shows current system run data.

  1. Open Step 4 System Optimization.
  2. Run System Test and Charge Verification Mode as needed for inverter units.
  3. Review Error History. Yellow entries are critical.
  4. Use Status to check current system run data.

Applies to: Daikin One Touch full setup

Source: Daikin One Touch smart thermostat training module TRC-10, p. 46. Written in our own words; check the manual for your exact model.

System test for inverter units

Heat pump · Daikin One Touch

The system test must be run on inverter units before setup can be completed. Setup only proceeds when the system test finishes with no errors. A run test screen appears when the tests are complete.

  1. Run the system test on the inverter unit.
  2. Confirm the test completes with no errors.
  3. Wait for the run test screen before continuing setup.

Applies to: Inverter heat pump or air conditioner

Source: Daikin One Touch smart thermostat training module TRC-10, p. 47. Written in our own words; check the manual for your exact model.

Use monitoring mode (Screen 2)

Heat pump · FIT

Screen 2 shows an item number and its value. The item list is in the monitoring table in this section. Blink timing is 1 second for this screen.

  1. Enter Screen 2 by holding RECALL from Screen 1.
  2. Press RECALL to move between monitored items.
  3. Press TEST to confirm the status shown.
  4. Press LEARN to return to Screen 0.

Applies to: FIT outdoor units

Source: Daikin FIT outdoor unit installation & service reference, p. 51. Written in our own words; check the manual for your exact model.

Use the thermostat status menu to check the system

Heat pump · DX6VS, DZ6VS

The status menu shows the current operating status of the system. Use it to confirm that equipment is working correctly and to help with troubleshooting.

  1. Open the Status menu on the communicating thermostat.
  2. Compare the displayed status with the expected operation for the mode and conditions.

Applies to: Communicating Daikin thermostat with this outdoor unit

Source: Installation instructions outdoor unit DX6VS/DZ6VS, p. 32. Written in our own words; check the manual for your exact model.

View error code display and error history

Heat pump · DX6VS, DZ6VS

Screen 0 shows the present error code. Screen 1 shows the last six error codes, with the latest first.

  1. Use the recall buttons to go to Screen 0 to read the present error code.
  2. Go to Screen 1 to read the error history: latest, 2nd through 6th.
  3. Check the history when the thermostat does not show the code, as the thermostat may not display every outdoor fault.

Applies to: Outdoor unit control board 7-segment display

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 42. Written in our own words; check the manual for your exact model.

Wireless remote controller service mode hierarchy

Heat pump · FTXM-W/V

The remote controller has a normal user mode and a service mode. Service mode contains a simplified diagnosis view, service check mode, address setting mode and trial operation mode. The code display changes each time the TIMER CANCEL button is pressed in simplified diagnosis.

  1. Hold the remote controller button combination for 5 seconds to enter service mode (the center of the temperature adjustment button does the same as pressing both buttons together).
  2. In simplified diagnosis, press TIMER CANCEL to step through the code display.
  3. In service check mode, read the left-side and right-side numbers separately.
  4. Use address setting mode to set the address that matches the jumper position.
  5. Use trial operation mode to run the unit for a test.

Applies to: FTXM-W/V wireless remote controller (ARC466 series)

Source: Daikin SiUS042113EA service manual, p. 169. Written in our own words; check the manual for your exact model.

Fault diagnosis with the remote controller

Mini-split · FTXM WVJU9

Reads the stored error code from the remote controller.

  1. Hold the remote controller button for about 5 seconds until the temperature display blinks.
  2. Point the remote controller at the indoor unit and press the button repeatedly.
  3. A short beep means a non-matching code. A long beep means a matching code.
  4. On the long beep, read the error code and follow the table.

Applies to: Remote controller and indoor unit

Source: Daikin room air conditioner operation manual, p. 50. Written in our own words; check the manual for your exact model.

Forced cooling operation

Mini-split · FTXM-W/V

Only allowed when the outdoor unit has no fault, is not in the 3-minute standby delay, and is not already running. Protection functions override everything during forced cooling. Start from the indoor unit ON/OFF switch or from the remote controller.

  1. Indoor ON/OFF switch: press and hold for at least 5 seconds. The unit starts. It stops by itself after about 15 minutes; press the switch again to stop it sooner.
  2. Remote controller: press the Temp and Mode buttons together, then press the Temp buttons to select "T" and press Mode to confirm.
  3. Remote controller: press Mode to select cooling.
  4. Remote controller: press On/Off to start. It stops by itself after about 30 minutes; press On/Off to stop sooner.

Applies to: FTXM-W/V indoor units with ON/OFF switch or wireless remote ARC466

Source: SiUS042113EA Inverter Pair service manual, p. 161. Written in our own words; check the manual for your exact model.

Pump down before relocating or disposing of the unit

Mini-split · FTXM-W/V

Pump down must be done when moving or scrapping the unit so refrigerant is kept out of the environment. Forced cooling is used to pull refrigerant into the outdoor unit.

  1. Remove the valve caps from the liquid stop valve and the gas stop valve.
  2. Start forced cooling operation.
  3. After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
  4. After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation.

Applies to: FTXM-W/V wall mounted units, relocation or disposal

Source: SiUS042113EA Inverter Pair service manual, p. 160. Written in our own words; check the manual for your exact model.

Enter setting mode on cascade unit display

Water heater · Mega-Q

Hold the page break button for over 5 seconds in normal mode to get into setting mode. BS1 changes mode, BS2 changes values, BS3 confirms.

  1. Press and hold BS1 for more than 5 seconds from normal mode.
  2. Use BS2 to change values and BS3 to confirm.
  3. Press BS1 once to leave setting mode and return to normal mode.

Applies to: Cascade unit push-button display

Source: Mega-Q installation manual, p. 40. Written in our own words; check the manual for your exact model.

Reset & cancel

Clearing lockouts, service reminders and fault history; skipping purge or de-air programs.

Cancel 24 hour OFF TIMER

Air conditioner · FTXM

Removes the OFF timer. The TIMER lamp goes off once it is cleared.

  1. Press the OFF TIMER button.
  2. Check the timer time clears and the TIMER lamp is off.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin room air conditioner operation manual, p. 27. Written in our own words; check the manual for your exact model.

Cancel 24 hour ON TIMER

Air conditioner · FTXM

Removes the ON timer. The day of the week and clock display return to the LCD and the TIMER lamp goes off.

  1. Press the ON TIMER button.
  2. Check the timer time clears and the TIMER lamp is off.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin room air conditioner operation manual, p. 26. Written in our own words; check the manual for your exact model.

Cancel COMFORT AIRFLOW operation

Air conditioner · FTXM

The flaps go back to the position they were in before COMFORT AIRFLOW was started.

  1. Press the COMFORT AIRFLOW button again.
  2. Check that the icon disappears from the LCD.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin room air conditioner operation manual, p. 24. Written in our own words; check the manual for your exact model.

Cancel POWERFUL operation

Air conditioner · FTXM

Pressing the button again ends POWERFUL early. Pressing a settings button also cancels it.

  1. Press the POWERFUL button again.
  2. Check that the POWERFUL icon disappears from the LCD.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin room air conditioner operation manual, p. 25. Written in our own words; check the manual for your exact model.

Clear the error history

Air conditioner · Daikin One+, Touch thermostat

Error history lists each logged error with its date, time, code, equipment and description. Clearing it removes the whole log.

  1. Go to System Optimization, then Error History.
  2. Review the logged entries, including date, time, code and equipment.
  3. Select Clear error history and confirm with Continue, or cancel to keep the log.

Applies to: Daikin One+ and Touch thermostats with error history

Source: Daikin One+ commissioning menu outline v3.9, p. 4. Written in our own words; check the manual for your exact model.

Delete all reservations for one day

Air conditioner · FTXM

Clears every reservation on the selected day. Works while confirming or setting reservations.

  1. Press the weekly timer key to show the day and reservation number.
  2. Select the day to clear.
  3. Hold the set key for about 5 seconds. Listen for the receiving tone and check the OPERATION lamp blinks twice.
  4. Press the exit key. If other reservations remain, WEEKLY TIMER stays active.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin FTXM WVJU9 operation manual, p. 35. Written in our own words; check the manual for your exact model.

Delete all WEEKLY TIMER reservations

Air conditioner · FTXM

Clears the whole weekly schedule. This does not work while the WEEKLY TIMER setting screen is open.

  1. From the normal display, hold the timer key for about 5 seconds.
  2. Listen for the receiving tone and check the OPERATION lamp blinks twice.
  3. Confirm that the WEEKLY TIMER icon is gone and the TIMER lamp is off.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin FTXM WVJU9 operation manual, p. 35. Written in our own words; check the manual for your exact model.

Delete one WEEKLY TIMER reservation

Air conditioner · FTXM

Removes a single reservation entry. Other saved reservations stay active.

  1. Press the weekly timer key to show the day and reservation number.
  2. Select the day and reservation number to delete.
  3. Press the set key. The timer-type icon blinks.
  4. Press the mode key until no icon is shown. Selecting a blank entry cancels that reservation.
  5. Press the set key. Listen for the receiving tone and check the OPERATION lamp blinks twice.
  6. Press the exit key. If other reservations remain, WEEKLY TIMER stays active.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin FTXM WVJU9 operation manual, p. 35. Written in our own words; check the manual for your exact model.

Factory reset and error history

Air conditioner · One+ and Touch

Factory reset is in the setup options. Error history can be cleared from its own screen.

  1. Use factory reset from setup options only when the thermostat must return to defaults.
  2. Open the error history screen to review code, equipment, date and description.
  3. Choose Clear error history, then Continue to confirm, or Cancel to keep the history.

Applies to: Thermostat

Source: Daikin One+ and Touch Thermostat Commissioning Menu Outline, p. 1 and p. 4. Written in our own words; check the manual for your exact model.

Factory reset from setup options

Air conditioner · Daikin One+, Touch thermostat

The setup options menu in the commissioning flow includes a factory reset choice. Use it only when the thermostat must return to defaults.

  1. Open setup options in the commissioning menu.
  2. Select factory reset.

Applies to: Daikin One+ and Touch thermostats, unitary commissioning

Source: Daikin One+ commissioning menu outline v3.9, p. 1. Written in our own words; check the manual for your exact model.

Reset cloud registration

Air conditioner · ONE+, One Touch

Reset registration is offered in the account menu only when the app is connected to the thermostat.

  1. Open the account menu.
  2. Select reset registration.
  3. Confirm with continue or cancel.

Applies to: Cloud registration reset

Source: daikin-one-touch-unitary-homeowner-settings.pdf, p. 2. Written in our own words; check the manual for your exact model.

Reset wireless adapter to factory default

Air conditioner · Atmosphera

Erases network settings and power consumption history. Do this before discarding the unit or handing it to another user.

  1. With operation stopped, press and hold the button for 5 seconds.
  2. Press or to select the reset menu.
  3. Press and hold the button for 2 seconds to confirm. The adapter lamp blinks for 1 second.
  4. Press to return to the default screen.

Applies to: Wireless LAN connection adapter

Source: Daikin Atmosphera operation manual, p. 41. Written in our own words; check the manual for your exact model.

Timer and clock reset after power loss

Air conditioner · FTXM

After a circuit breaker trip, power failure, or battery change in the remote, the indoor clock becomes inaccurate and timers must be set again.

  1. Reset the clock on the remote controller.
  2. Set the ON or OFF timer again.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin room air conditioner operation manual, p. 27. Written in our own words; check the manual for your exact model.

Turn off the wireless connection

Air conditioner · Atmosphera

Turns off wireless communication without affecting remote controller use.

  1. With operation stopped, press and hold the button for 5 seconds.
  2. Press or to select the wireless menu, then confirm.
  3. Press and hold the button for 2 seconds to confirm. The adapter lamp goes off and communication is OFF.
  4. Press to return to the default screen.

Applies to: Wireless LAN connection adapter

Source: Daikin Atmosphera operation manual, p. 41. Written in our own words; check the manual for your exact model.

Turn WEEKLY TIMER off and back on

Air conditioner · FTXM

Deactivates the saved weekly schedule without deleting it. If a deactivated schedule is turned back on, the last reservation mode is used.

  1. While the WEEKLY TIMER icon is on the LCD, press the WEEKLY TIMER key. The icon goes off and the TIMER lamp goes out.
  2. To reactivate, press the WEEKLY TIMER key again.
  3. If not all reservations seem to apply, deactivate once, then reactivate.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin FTXM WVJU9 operation manual, p. 34. Written in our own words; check the manual for your exact model.

Wait before cutting power after stopping

Air conditioner · FTXM

After the unit stops, keep the power on for at least 5 minutes. Cutting power right away can cause water leakage.

  1. Stop the unit.
  2. Wait at least 5 minutes before switching off the power.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin FTXM operation manual, p. 4. Written in our own words; check the manual for your exact model.

Clear the EEV indoor unit error code history

Air handler · DV**FEC, DFVE**, CAPE(A)*, CHPE*

Erasing the history uses the FAULT RECALL button. The display confirms the clear with "88".

  1. Press and hold FAULT RECALL until the 7-segment display blinks "--".
  2. Release the button. The display shows "88" and the fault history is cleared.
  3. Do not hold the button longer than 15 seconds, or the control returns to standby without clearing.

Applies to: EEV indoor units

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 25. Written in our own words; check the manual for your exact model.

Clear the error code history

Air handler · DV**FEC / DFVE**, CAPE(A)* / CHPE*

Erases the stored fault history from the indoor control board. Gas furnace and modular blower faults are kept on their own boards and must be checked there.

  1. Press and hold FAULT RECALL until the display blinks "--".
  2. Release the button. The display shows "88" and clears the faults.
  3. Keep the button pressed for no longer than 15 seconds or the control returns to standby without clearing.

Applies to: EEV indoor units with 2-digit display

Source: SiUS612209EA service instructions, p. 25. Written in our own words; check the manual for your exact model.

Read network LEDs and reset the network

Air handler · DFVE EEV air handler, DV**FEC EEV air handler, CAPE / CHPE EEV cased coil

The red STATUS LED shows network status and the green RX LED flashes with network traffic. The network is reset with the LEARN button.

  1. Check the red STATUS LED for network status.
  2. Check that the green RX LED shows traffic.
  3. Press the LEARN button to reset the network.

Applies to: EEV indoor units on the transmission/data-share network

Source: Daikin SiUS612209EB service instructions, p. 80. Written in our own words; check the manual for your exact model.

Reset the indoor network with the LEARN button

Air handler · DV**FEC, DFVE**

The red STATUS LED shows network status and the green RX LED shows network traffic.

  1. Check the red STATUS LED for network status and the green RX LED for traffic.
  2. Press the LEARN button to reset the network.

Applies to: EEV air handler and EEV cased coil control boards

Source: Daikin SiUS612209EA service instructions, p. 79-80. Written in our own words; check the manual for your exact model.

Reset the furnace control to factory defaults (rFd)

Furnace · Daikin DR96TN/DD96TN

The rFd menu item returns the control menu settings to factory defaults.

  1. Press the left or right switch until rFd shows
  2. Press the center switch, pick yes or no with the left or right switch
  3. Press the center switch to confirm

Applies to: Daikin DR96TN/DD96TN two-stage furnaces

Source: Daikin DR96TN-DD96TN service RSD6612304 (05-2024), LED Display Menu p.26 and troubleshooting chart p.28. Written in our own words; check the manual for your exact model.

View and clear the stored faults (L6F / F10)

Furnace · Daikin DR96TN/DD96TN

The stored fault list is labelled L6F in the troubleshooting chart and F10 (last 10 faults) in the menu table; the center switch steps through it and clears it.

  1. Press the left or right switch until L6F shows
  2. Press the center switch and read the stored faults
  3. To erase them, keep the center switch pressed for 5 to 30 seconds; the display blinks three dashes three times, then shows L6F again

Applies to: Daikin DR96TN/DD96TN two-stage furnaces

Source: Daikin DR96TN-DD96TN service RSD6612304 (05-2024), LED Display Menu p.26 and troubleshooting chart p.28. Written in our own words; check the manual for your exact model.

Clear filter replacement lamp after replacing dust collection filter

General · Daikin Air Purifier

After a new dust collection filter is fitted, the filter replacement lamp stays on until the filter is reset with a two-button press. The button names are not legible in the extracted text, so confirm which two buttons on the panel are meant.

  1. Fit the new dust collection filter.
  2. Press and hold the two buttons specified in the manual together for about 2 seconds.

Applies to: MCB50YSAU

Source: Daikin Air Purifier installation & operation manual, p. 24. Written in our own words; check the manual for your exact model.

Factory reset of the controller

General · Daikin One Powered Ventilator

Restores the controller to factory defaults. Only works with the unit in the OFF state.

  1. Make sure the unit is in the OFF setting.
  2. Press and hold both UP and DOWN for about 5 seconds.
  3. Release when OFF flashes once on the display, which confirms the reset.

Applies to: DQ-P-16-100

Source: IO-DPV installation manual, p. 7. Written in our own words; check the manual for your exact model.

Finish an advanced setting change with a power cycle

General · Humidifying Air Purifier

After changing certain advanced settings the unit will not return to normal mode until it is power cycled.

  1. Wait until the lamp is blinking after the setting change.
  2. Unplug the power supply plug while the lamp is still blinking.
  3. Wait at least 5 seconds.
  4. Plug the unit back in.
  5. If the lamps do not change, unplug the unit, wait at least 5 seconds, re-plug it and repeat the whole procedure from the start.
  6. Settings are kept after unplugging. Notification tone is the exception: it returns to ON after the plug is removed, so set it again if needed.

Applies to: Advanced settings procedure

Source: Daikin MCKB70YSAU installation & operation manual, p. 24. Written in our own words; check the manual for your exact model.

Recover from lightning or power glitch

General · Humidifying Air Purifier

If the indicator lamps light abnormally after a lightning strike or similar event and the unit stops working, do this reset.

  1. Unplug the power supply plug.
  2. Wait at least 5 seconds.
  3. Reinsert the plug and start operation again.

Applies to: Whole unit

Source: Daikin MCKB70YSAU operation manual, p. 36. Written in our own words; check the manual for your exact model.

Reset filter replacement alert

General · Humidifying Air Purifier

The filter alert does not clear by itself after a filter change. It needs a long press on the filter control.

  1. Install the new dust collection filter.
  2. Press and hold the filter control for about 2 seconds.
  3. Listen for two short beeps; the filter replacement lamp then turns off.

Applies to: Filter replacement alert

Source: Daikin MCKB70YSAU operation manual, p. 31. Written in our own words; check the manual for your exact model.

Reset the filter replacement alert

General · Air Purifier

Clears the filter replacement lamp after the dust collection filter is replaced.

  1. Replace the dust collection filter.
  2. Press and hold the two reset buttons together for about 2 seconds.
  3. Wait for two short beeps; the filter replacement lamp turns off.

Applies to: MCB50YSAU

Source: Daikin MCB50YSAU installation & operation manual, p. 18. Written in our own words; check the manual for your exact model.

Factory reset from set-up options

Heat pump · Daikin One Touch

The welcome screen set-up options include a factory reset of the thermostat. Use this only when the thermostat must return to default settings before commissioning.

  1. On the welcome screen, open the set-up options.
  2. Select the factory reset option.

Applies to: Daikin One Touch smart thermostat

Source: Daikin One Touch installation training TRC-10, p. 35. Written in our own words; check the manual for your exact model.

High pressure switch needs main power reset

Heat pump · DX6VS / DZ6VS

The high pressure switch is not automatically reset. After it trips and the cause is corrected, turn the main power OFF to reset it.

  1. Correct the high-pressure cause first.
  2. Turn main power OFF to reset the high pressure switch.

Applies to: DX6VS / DZ6VS outdoor unit

Source: Daikin DX6VS / DZ6VS service instructions SiUS612209EA, p. 16. Written in our own words; check the manual for your exact model.

Reset the communication network with the LEARN button

Heat pump · DX6VS / DZ6VS, DV**FEC / DFVE**, CAPE(A)* / CHPE*

The integrated control module's LEARN button resets the network. The same button is used for the communication troubleshooting checks.

  1. Press the LEARN button on the control board for approximately 5 seconds to reset the network.
  2. After resetting, check whether the communication error code has cleared.

Applies to: Indoor unit integrated control module

Source: Daikin SiUS612209EA service instructions, p. 71. Written in our own words; check the manual for your exact model.

Cancel the code display

Mini-split · FTXM WVJU9

Stops the fault code from showing on the remote controller.

  1. Hold the remote controller button for about 5 seconds.
  2. The code display also clears if no button is pressed for a while.

Applies to: Remote controller

Source: Daikin room air conditioner operation manual, p. 50. Written in our own words; check the manual for your exact model.

Delete WEEKLY TIMER reservations

Mini-split · FTXM-W/V

Reservations can be removed one at a time, all for one day, or all at once. The all-delete hold does not work while the WEEKLY TIMER setting screen is open.

  1. Individual reservation: open the reservation screen, select the day and number, confirm, then cycle the mode to blank until no icon shows. Confirm and check for two OPERATION lamp blinks.
  2. Whole day: select the day on the normal screen and hold the button for about 5 seconds until two OPERATION lamp blinks confirm the deletion.
  3. All reservations: hold the button for about 5 seconds on the normal display. The WEEKLY TIMER icon and TIMER lamp go off and all reservations are removed.

Applies to: WEEKLY TIMER reservations

Source: Daikin FTXM-W/V service manual, pp. 56. Written in our own words; check the manual for your exact model.

Reset cloud registration

Mini-split · Daikin ONE+

The reset registration option appears under the account menu only when the app is connected.

  1. Open the account menu.
  2. Select reset registration if the app is connected.

Applies to: Daikin ONE+ cloud account

Source: Daikin ONE+ and ONE Touch homeowner settings menu outline, p. 2. Written in our own words; check the manual for your exact model.

Reset wireless LAN adapter to factory default

Mini-split · FTXM-W/V

Erases network settings and power consumption history in the adapter. Do this before discarding the unit or handing it to another user.

  1. With operation stopped, press and hold the menu button for 5 seconds.
  2. Press up or down and select the reset menu number.
  3. Press and hold the select button for 2 seconds. The adapter lamp blinks for 1 second.
  4. Press return to go to the default screen.

Applies to: Wireless LAN connection adapter, FTXM-W/V

Source: Daikin FTXM-W/V service manual, p. 69. Written in our own words; check the manual for your exact model.

Turn off wireless LAN connection

Mini-split · FTXM-W/V

Turns off wireless communication from the remote controller menu without resetting the stored settings.

  1. With operation stopped, press and hold the menu button for 5 seconds.
  2. Press up or down and select the wireless menu number. The display shows the menu and communication blinks.
  3. Press and hold the select button for 2 seconds. The adapter lamp turns off.
  4. Press return to go to the default screen.

Applies to: Wireless LAN connection adapter, FTXM-W/V

Source: Daikin FTXM-W/V service manual, p. 69. Written in our own words; check the manual for your exact model.

Turn WEEKLY TIMER off and on

Mini-split · FTXM-W/V

WEEKLY TIMER can be deactivated without deleting reservations. The saved reservations come back when it is reactivated, using the last reservation mode.

  1. With the WEEKLY TIMER icon showing on the LCD, press the WEEKLY TIMER button to deactivate it. The icon disappears and the TIMER lamp goes off.
  2. To reactivate, press the same button again.

Applies to: WEEKLY TIMER

Source: Daikin FTXM-W/V service manual, p. 55. Written in our own words; check the manual for your exact model.

Wait before restarting after power-off

Mini-split · FTXM-W/V

After repairs that involve turning the power off, wait at least 30 seconds before turning it back on.

  1. Turn the power off.
  2. Wait at least 30 seconds.
  3. Turn the power back on and restart the system.

Applies to: Outdoor unit, E6 recovery

Source: SiUS042113EA service manual, p. 121. Written in our own words; check the manual for your exact model.

Wait before cutting power after shutdown

Water heater · Mega-Q

Turning the power off right after the unit stops can cause water leakage.

  1. After the unit stops operating, wait at least 5 minutes before turning off the power.

Applies to: Mega-Q system

Source: Daikin Mega-Q installation manual, p. 3. Written in our own words; check the manual for your exact model.

Settings shortcuts

Where the useful parameters live and what they are set to from the factory.

Adjust indoor unit display brightness

Air conditioner · FTXM WVJU9

Brightness of the indoor unit display can be set to High (default), Low or Off. The display goes back to the default screen by itself after 60 seconds.

  1. Press and hold the MENU button for 2 seconds.
  2. Use the NEXT or BACK buttons to select the brightness menu number.
  3. Press SELECT to confirm.
  4. Use the NEXT or BACK buttons to pick High, Low or Off.
  5. Press SELECT again to set the value.
  6. Press BACK to return to the default screen (press BACK twice to return sooner).

Applies to: Remote controller menu, all FTXM WVJU9 models

Source: Daikin Room Air Conditioner operation manual, p. 12. Written in our own words; check the manual for your exact model.

Confirm WEEKLY TIMER reservations

Air conditioner · FTXM

Lets you view the saved reservations for each day without changing them. You can switch into setting mode from here if a change is needed.

  1. In normal display, press the confirm key. The current day and reservation number appear.
  2. Select the day and reservation number to check. Press the set key to view its details.
  3. To change a reservation, select its number and press the set key. This opens setting mode.
  4. Press the exit key to leave confirmation mode. The WEEKLY TIMER icon shows if the timer is active.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin FTXM WVJU9 operation manual, p. 34. Written in our own words; check the manual for your exact model.

Copy a WEEKLY TIMER day to other days

Air conditioner · FTXM

Copies the whole reservation set of one day to other days of the week. Changes to an individual day after copying are made in setting mode.

  1. Enter copy mode from the weekly timer screen.
  2. Select the source day of the week and press the set key.
  3. Select the destination day and press the set key. Listen for the receiving tone and check that the OPERATION lamp blinks twice.
  4. Repeat for each additional destination day.
  5. Press the confirm key to finish. The WEEKLY TIMER is activated.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin FTXM WVJU9 operation manual, p. 33. Written in our own words; check the manual for your exact model.

Program a WEEKLY TIMER reservation

Air conditioner · FTXM

Each reservation has an ON or OFF time. ON entries also take a set temperature. Times step by 10 minutes from 0:00 to 23:50. Temperature can be set from 50°F (10.0°C) to 90°F (32.0°C).

  1. Press the WEEKLY TIMER button to enter setting mode.
  2. Select the day and reservation number (1 to 4).
  3. Press the set button, then select ON TIMER, OFF TIMER, or blank to delete.
  4. Press the set button and choose the time.
  5. For ON TIMER, press the set button and choose the temperature.
  6. Press the set button to save; listen for the receiving tone and check that the OPERATION lamp blinks twice.
  7. Press the confirm button to finish.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin room air conditioner operation manual, p. 30. Written in our own words; check the manual for your exact model.

Set 24 hour OFF TIMER

Air conditioner · FTXM

Stops the unit at a set clock time. Same method as ON TIMER, using the OFF TIMER button. Time steps are 10 minutes.

  1. Check the clock is correct (see p. 11).
  2. Press the OFF TIMER button; OFF and the blinking time appear.
  3. Press the up or down button until the wanted time shows.
  4. Press the OFF TIMER button again to confirm; the TIMER lamp lights orange.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin room air conditioner operation manual, p. 27. Written in our own words; check the manual for your exact model.

Set 24 hour ON TIMER

Air conditioner · FTXM

Starts the unit at a set clock time. The clock must be correct first. Time steps are 10 minutes; holding the button scrolls fast. The TIMER lamp lights orange when set. Operation starts with the previously used mode, temperature, airflow rate and direction.

  1. Check the clock is correct and set it if not (see clock setting, p. 11).
  2. Press the ON TIMER button; ON and the blinking time appear.
  3. Press the up or down button until the wanted time shows.
  4. Press the ON TIMER button again to confirm; the TIMER lamp lights orange.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin room air conditioner operation manual, p. 26. Written in our own words; check the manual for your exact model.

Set a WEEKLY TIMER reservation (final steps)

Air conditioner · FTXM

Finish each reservation by confirming the time and temperature. ON TIMER needs both time and temperature; OFF TIMER needs only the time. Set the remote controller clock first, because a breaker trip or power failure makes the indoor clock drift.

  1. Set the time with the arrow keys. Times run from 0:00 to 23:50 in 10-minute steps.
  2. Press the set key. The time is stored and the temperature starts to blink.
  3. For ON TIMER, choose the temperature. Range is 50°F (10.0°C) to 90°F (32.0°C).
  4. In COOL or AUTO, the unit runs at 64°F (18.0°C) even if set between 50°F and 63°F.
  5. In HEAT or AUTO, the unit runs at 86°F (30.0°C) even if set between 87°F and 90°F.
  6. Press the set key again. Listen for the receiving tone and check that the OPERATION lamp blinks twice and the TIMER lamp lights orange.
  7. To add another reservation, repeat from the reservation-select step.
  8. Press the confirm key to finish. The WEEKLY TIMER icon shows on the LCD and the timer is active.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin FTXM WVJU9 operation manual, p. 32. Written in our own words; check the manual for your exact model.

Set countdown (hours remaining) ON/OFF TIMER

Air conditioner · FTXM

Counts down in 1 hour steps from 1 to 12 hours instead of using clock time. The display drops by 1 hour each hour until it blank (off).

  1. Press and hold the ON or OFF TIMER button for about 5 seconds until the signal indicator blinks, then release.
  2. Press the up or down button to set 1 to 12 hours.
  3. Press the ON or OFF TIMER button again to confirm; the TIMER lamp lights orange.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin room air conditioner operation manual, p. 28. Written in our own words; check the manual for your exact model.

Set ECONO or QUIET OUTDOOR UNIT operation

Air conditioner · FTXM

Each press of the button cycles through the options: ECONO, QUIET OUTDOOR UNIT, both combined, and off (no icon). ECONO limits maximum power draw, useful when sharing a circuit with other appliances. QUIET OUTDOOR UNIT lowers outdoor noise by changing compressor frequency and fan speed.

  1. Press the ECONO / QUIET OUTDOOR UNIT button and select the wanted mode.
  2. Keep pressing until no icon is displayed to cancel.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin room air conditioner operation manual, p. 26. Written in our own words; check the manual for your exact model.

Start COMFORT AIRFLOW operation

Air conditioner · FTXM

Turns on the COMFORT AIRFLOW function, which sends air upward in COOL and DRY and downward in HEAT so it does not blow directly on people. Airflow rate is forced to AUTO. Not available in FAN mode.

  1. Press the COMFORT AIRFLOW button.
  2. Confirm the COMFORT AIRFLOW icon appears on the LCD.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin room air conditioner operation manual, p. 24. Written in our own words; check the manual for your exact model.

Start POWERFUL operation

Air conditioner · FTXM

Runs the unit at maximum capacity in any mode for 20 minutes, then returns to the settings used before POWERFUL was started.

  1. Press the POWERFUL button during operation.
  2. Confirm the POWERFUL indicator shows on the LCD.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin room air conditioner operation manual, p. 25. Written in our own words; check the manual for your exact model.

Away mode setup

Furnace · Daikin One+

The away screen shows whether away mode is on or off and the away cooling and heating setpoints. On/off is chosen from the drop-down menu. Setpoints can be changed by dragging the numbers or the comfort range. With the mobile app, geo-fencing switches to away mode automatically when the user is outside the set radius. Away settings must be configured in the mobile app.

  1. Open the away screen.
  2. Select on or off from the drop-down menu.
  3. Drag the away cooling and heating setpoints or the comfort range to change them.
  4. In the mobile app, enable geo-fencing and set the radius if automatic away mode is wanted.
  5. Make away settings in the mobile app.

Applies to: Daikin One+ away mode

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 49. Written in our own words; check the manual for your exact model.

Service reminders

Furnace · Daikin One+

Service reminders can be set to help maintain the system. Preset reminder options are media filter, humidifier pad and general service reminders.

Applies to: Daikin One+ Smart Thermostat

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 7. Written in our own words; check the manual for your exact model.

Settings menu contents

Furnace · Daikin One+

The Settings menu has these groups: Display (visual features), Comfort (target humidity), and Configuration (app account setup, dealer information, date and time, message and alert settings, system components, and home Wi-Fi).

  1. Open Settings.
  2. Use Display to adjust and turn on visual features.
  3. Use Comfort to set the target humidity.
  4. Use Configuration for app account, dealer information, date and time, alerts, system components and Wi-Fi.

Applies to: Daikin One+ settings menu

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 51. Written in our own words; check the manual for your exact model.

System mode options

Furnace · Daikin One+

Tapping the system mode icon lets you choose Auto (cool and heat), Cool, Heat, Off, or Emergency heat. Emergency heat is only available on heat pump systems.

  1. Tap the system mode icon.
  2. Select Auto, Cool, Heat, Off, or Emergency heat (heat pump only).

Applies to: Daikin One+ thermostat, heat pump and conventional systems

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 47. Written in our own words; check the manual for your exact model.

Turn off R-32 monitoring when no R-32 system is fitted (A2E)

Furnace · Daikin DR96TN/DD96TN

If the furnace has no R-32 coil and sensor, A2E must be set to no; otherwise the furnace drops into fan-only mitigation.

  1. Press the left or right switch to scroll to the A2E menu item.
  2. Press the center switch to open it.
  3. Choose no and press the center switch to save.

Applies to: Daikin DR96TN and DD96TN two-stage 96% furnaces

Source: Daikin RSD6612304 (DR96TN/DD96TN service), menu table p.26; R-32 Information p.10; speed selection p.8-9. Written in our own words; check the manual for your exact model.

Adjust panel brightness

General · Humidifying Air Purifier

Each press of the BRIGHTNESS button cycles the panel between BRIGHT, DIM and OFF. Some lamps stay on even when set to OFF. Unplugging the unit resets the brightness to BRIGHT.

  1. Press BRIGHTNESS during operation to cycle through BRIGHT, DIM and OFF.

Applies to: Operating panel

Source: Daikin MCKB70YSAU installation & operation manual, p. 11. Written in our own words; check the manual for your exact model.

Adjusting setpoints

General · Daikin One+ S21

Setpoints can be changed with the arrow icons, by turning the dial, or by sliding the setpoint to the desired temperature.

  1. Tap the arrow icons, turn the dial, or slide the setpoint to the target temperature.

Applies to: Daikin One+ S21 thermostat

Source: Daikin One+ installation & commissioning (S21) manual, p. 41. Written in our own words; check the manual for your exact model.

Away mode

General · Daikin One+ S21

The away screen shows whether away is on or off and the away cooling and heating setpoints. On/off is chosen from the drop-down menu. Setpoints can be changed by dragging the numbers or the comfort range. Geo-fencing in the mobile app switches to away mode when the phone is outside the set radius. Geo-fencing must be configured in the app.

  1. Select on or off from the drop-down menu.
  2. Drag the away setpoint numbers or comfort range to change them.
  3. To use geo-fencing, configure it in the mobile app. Away mode switches on when outside the radius.

Applies to: Daikin One+ S21 thermostat with mobile app

Source: Daikin One+ installation & commissioning (S21) manual, p. 43. Written in our own words; check the manual for your exact model.

Change an advanced setting

General · Humidifying Air Purifier

Advanced settings are changed with a button hold, then a press to toggle ON/OFF. The lamps show the current state. Button icons did not come through in the extracted text.

  1. Stop the unit, or change the setting while it is running if the function allows it.
  2. Press and hold the setting button for about 5 seconds until a short beep sounds.
  3. While still holding, press the second button shown in the manual. Release both when a short beep sounds.
  4. Read the state from the lamps: the function lamp blinks, then lights up, and the FAN lamp shows ON (lit) or OFF (unlit).
  5. Press the toggle button to switch between ON and OFF. Each press cycles the setting.
  6. Wait for the short beep and blinking lamp, then finish the change with the power cycle tip.

Applies to: Advanced settings: humidifying filter drying, quiet airflow with water supply lamp, notification tone

Source: Daikin MCKB70YSAU installation & operation manual, p. 23-24. Written in our own words; check the manual for your exact model.

Changing the system mode

General · Daikin One+ S21

Tapping the system mode icon opens the mode choices. Available modes are Auto (cool and heat), Cool, Heat, Off and Emergency heat. Emergency heat only appears on heat pump systems.

  1. Tap the system mode icon.
  2. Select Auto, Cool, Heat, Off or Emergency heat.
  3. Emergency heat is only offered on heat pump systems.

Applies to: Daikin One+ S21 thermostat, heat pump and other systems

Source: Daikin One+ installation & commissioning (S21) manual, p. 41. Written in our own words; check the manual for your exact model.

Enter advanced settings mode

General · Air Purifier

Used for the dust sensor sensitivity, ECONO monitoring, and AUTO FAN range settings.

  1. Hold the button combination down for about 5 seconds until a short beep sounds.
  2. While holding, press the setting button.
  3. Release both buttons when a short beep sounds.
  4. Press the setting button to change the value and confirm with the lamps.
  5. Unplug, wait at least 5 seconds, and plug back in to finish.

Applies to: MCB50YSAU

Source: Daikin MCB50YSAU installation & operation manual, p. 15-16. Written in our own words; check the manual for your exact model.

How to change an advanced setting

General · Daikin Humidifying Air Purifier

Advanced settings use a hold-and-press sequence. Button names are missing from the extracted text, so confirm which buttons on the unit to use. After changing some settings the unit must be unplugged to return to normal operation.

  1. Press and hold the button for about 5 seconds until a short beep sounds.
  2. While still holding it, press the second button named in the manual.
  3. Release both when a short beep sounds. The lamps show the current setting.
  4. Press the setting button to change the value. A short beep sounds and the lamp blinks.
  5. For the dust sensor, airflow range, quiet and filter drying settings, unplug the unit, wait at least 5 seconds, then plug it back in.
  6. If the lamps do not change, unplug, wait 5 seconds, and repeat the procedure from the start.

Applies to: MCKB70YSAU

Source: Daikin MCKB70YSAU installation & operation manual, p. 21, 22, 23. Written in our own words; check the manual for your exact model.

Normal mode navigation

General · Daikin One+

In normal mode you can view messages and temperature and open the settings the installer has made available. Navigate by tapping icons or turning the analog dial. The dial adjusts temperature only, and pressing the dial returns to the home screen.

  1. Tap icons to move between screens.
  2. Turn the analog dial to adjust temperature.
  3. Press the dial to return to the home screen.

Applies to: Daikin One+ normal mode

Source: Daikin One+ Installation & Commissioning (S21), p. 40. Written in our own words; check the manual for your exact model.

Schedule editing

General · Daikin One+ S21

The schedule shows 7 days, one day at a time, with 24 hours on screen. Editing is enabled from the drop-down menu or by swiping. Copy and paste can be used to build the schedule. Unlike other screens, schedule changes must be saved before leaving the mode.

  1. Open the schedule and choose the day from the drop-down menu or swipe to it.
  2. Enable schedule editing.
  3. Use copy and paste to repeat settings across days if needed.
  4. Save the schedule before exiting, otherwise edits are not kept.

Applies to: Daikin One+ S21 thermostat, homeowner schedule

Source: Daikin One+ installation & commissioning (S21) manual, p. 42. Written in our own words; check the manual for your exact model.

Away mode

Heat pump · Daikin One Touch

The away screen shows whether away is on or off and the away cooling and heating setpoints. On/off is chosen from the drop-down menu, and setpoints are changed by dragging the numbers or the comfort range. Geo-fencing in the mobile app switches to away when the phone leaves the set radius. Away settings must be made in the mobile app.

  1. Select on or off from the drop-down menu.
  2. Drag the numbers or the comfort range to change the away setpoints.
  3. Set geo-fencing radius in the mobile application if automatic away is needed.

Applies to: Daikin One Touch smart thermostat, away mode

Source: Daikin One Touch smart thermostat training module TRC-10, p. 62. Written in our own words; check the manual for your exact model.

Change a Setting Mode 1 value (Screen 3)

Heat pump · FIT

Setting Mode 1 changes airflow trims, profiles, delays and zoning. Check the settings table before changing anything.

  1. Enter Screen 3 by holding RECALL from Screen 2.
  2. Press RECALL to select the setting and to increase its value.
  3. Press TEST to change the setting.
  4. Press TEST again to complete the setting and return to setting mode.

Applies to: FIT outdoor units

Source: Daikin FIT outdoor unit installation & service reference, p. 52. Written in our own words; check the manual for your exact model.

Change a Setting Mode 2 value (Screen 4)

Heat pump · FIT

Setting Mode 2 changes defrost, compressor speed limits, cooling boost, noise level and capacity priority. Check the settings table before changing anything.

  1. Enter Screen 4 by holding RECALL and TEST together for 5 seconds.
  2. Press RECALL to increase the number of the setting.
  3. Press TEST to change the setting.
  4. Press TEST again to complete the setting and return to setting mode.

Applies to: FIT outdoor units

Source: Daikin FIT outdoor unit installation & service reference, p. 53. Written in our own words; check the manual for your exact model.

Change a value in setting mode 1

Heat pump · DX6VS / DZ6VS

Setting mode 1 (screen 3) changes system settings. Some outdoor units have setting items numbered up to 3.12, depending on production date.

  1. Enter screen 3 from screen 2 by holding RECALL.
  2. Press RECALL to step to the setting number to change and increase the value.
  3. Press TEST to confirm the setting.
  4. Press TEST to complete the setting and return to setting mode.
  5. Press LEARN to return to screen 0 when finished.

Applies to: DX6VS / DZ6VS outdoor unit control board

Source: Daikin SiUS612209EB service instructions, p. 40. Written in our own words; check the manual for your exact model.

Change values in setting mode 1

Heat pump · DX6VS / DZ6VS outdoor unit mode display

Setting mode 1 changes system settings. Some models have setting items up to 3.12 depending on production date. The full item list is on page 43, which is not in this extract.

  1. From screen 3, press RECALL to move through the setting numbers.
  2. Press RECALL to increase the value.
  3. Press TEST to change or confirm the setting.
  4. Press TEST to complete the setting and return to setting mode.
  5. Press LEARN to return to screen 0.

Applies to: Outdoor unit control board mode display

Source: Daikin SiUS612209EA service instructions, p. 40. Written in our own words; check the manual for your exact model.

Changing system mode and setpoints

Heat pump · Daikin One Touch

The system mode icon opens the mode choices: Auto (cool and heat), Cool, Heat, Off, and Emergency heat, which is for heat pump systems only. Setpoints are changed with the arrow icons or by sliding them to the desired temperature.

  1. Tap the system mode icon.
  2. Select Auto, Cool, Heat, Off, or Emergency heat (heat pump only).
  3. Use the arrow icons, or slide the setpoints, to reach the desired temperature.

Applies to: Daikin One Touch smart thermostat, heat pump systems for emergency heat

Source: Daikin One Touch smart thermostat training module TRC-10, p. 60. Written in our own words; check the manual for your exact model.

Cool/heat airflow ON and OFF delay

Heat pump · DX6VS, DZ6VS

The thermostat has Cool/Heat Airflow ON Delay and Cool/Heat Airflow OFF Delay settings. They change the fan delay for a set time compared with normal operation. Check the indoor unit installation manual for the details of each setting.

  1. Select Cool/Heat Airflow ON Delay or Cool/Heat Airflow OFF Delay on the thermostat.
  2. Check the indoor unit installation manual before you change the duration.

Applies to: Communicating Daikin thermostat with this outdoor unit

Source: Installation instructions outdoor unit DX6VS/DZ6VS, p. 32. Written in our own words; check the manual for your exact model.

Dealer edit

Heat pump · Daikin One Touch

Dealer edit gives access to the installer set-up screen again. Advanced adjustments to the thermostat are made here.

  1. Navigate to dealer navigation.
  2. Select dealer edit to reopen the installer set-up screen.
  3. Make advanced adjustments there.

Applies to: Daikin One Touch thermostat, dealer navigation

Source: Daikin One Touch installation guide, p. 56. Written in our own words; check the manual for your exact model.

ECONO/QUIET button cycle (ARC466A70)

Heat pump · FTXM-W, FTXM-V

Each press of the ECONO/QUIET button steps through ECONO, a blank state, no setting, a combination, and QUIET OUTDOOR UNIT. QUIET OUTDOOR UNIT is not available in FAN or DRY mode. It cannot run with POWERFUL at the same time, and whichever was pressed last takes priority.

  1. Press the ECONO/QUIET button repeatedly to step through the settings.
  2. Do not expect QUIET OUTDOOR UNIT in FAN or DRY mode.
  3. If POWERFUL and QUIET OUTDOOR UNIT are both wanted, note that the function pressed last wins.

Applies to: FTXM-W/V with ARC466A70 remote

Source: SiUS042113EA service manual, p. 86. Written in our own words; check the manual for your exact model.

ECONO/QUIET button cycle (ARC466A71)

Heat pump · FTXM-W, FTXM-V

On the ARC466A71 the ECONO/QUIET button cycles through the same ECONO, blank, no setting, combination and QUIET OUTDOOR UNIT states. QUIET OUTDOOR UNIT is not available in FAN or DRY mode and conflicts with POWERFUL, with the last function pressed taking priority.

  1. Press the ECONO/QUIET button repeatedly to step through the settings.
  2. Do not expect QUIET OUTDOOR UNIT in FAN or DRY mode.
  3. If POWERFUL and QUIET OUTDOOR UNIT conflict, the last one pressed is kept.

Applies to: FTXM-W/V with ARC466A71 remote

Source: SiUS042113EA service manual, p. 88. Written in our own words; check the manual for your exact model.

Emergency heat mode

Heat pump · Daikin One+ Unitary Aux Heater

With a heat pump, Emergency Heat appears as a system mode. When enabled, it can turn on the aux heat source directly.

  1. Enable Emergency Heat in the system settings if direct aux operation is needed.
  2. Select Emergency Heat as the system mode to run the aux heat source directly.

Applies to: Heat pump systems with aux heat

Source: Unitary Aux Heater installation and setup, p. 4. Written in our own words; check the manual for your exact model.

FAN button for indoor unit quiet operation

Heat pump · FTXM-W, FTXM-V

Setting the airflow to the quiet icon starts indoor unit quiet operation, which lowers the noise and also the airflow rate. The airflow rate setting is not available in DRY mode.

  1. Press the FAN setting button until the quiet airflow setting is shown.
  2. Expect a lower airflow rate and quieter operation.
  3. Do not try to set airflow rate in DRY mode, as it is not available.

Applies to: FTXM-W/V with ARC466A70 or ARC466A71 remote

Source: SiUS042113EA service manual, p. 85. Written in our own words; check the manual for your exact model.

Homeowner Settings menu options

Heat pump · Daikin One Touch

The Settings screen gives access to extra features: System Mode, Schedule, Reminders and Set date & time. Use the down arrow to reach more options.

  1. Open Settings from the homeowner navigation.
  2. Choose System Mode, Schedule, Reminders or Set date & time.
  3. Select the down arrow to see the remaining options.

Applies to: Daikin One Touch smart thermostat

Source: Daikin One Touch Smart Thermostat training module TRC-10, p. 64. Written in our own words; check the manual for your exact model.

Schedule editing

Heat pump · Daikin One Touch

The schedule shows 7 days, one day at a time, with 24 hours on screen. Editing is turned on from the drop-down menu or by swiping. Copy and paste speeds up scheduling. Unlike other screens, schedule edits must be saved before leaving the mode.

  1. Select the day from the drop-down menu or swipe to enable schedule editing.
  2. Use copy and paste to duplicate schedule entries where needed.
  3. Save the edits before exiting the schedule.

Applies to: Daikin One Touch smart thermostat, homeowner schedule

Source: Daikin One Touch smart thermostat training module TRC-10, p. 61. Written in our own words; check the manual for your exact model.

Secondary heat settings

Heat pump · Daikin One Touch

The secondary heat settings screen sets lockouts and the secondary heat activation temperature. With a heat pump, Emergency Heat appears as a system mode and can directly turn on the aux heat source when enabled.

  1. Open Aux Heat Setup and go to Secondary Heat Settings.
  2. Set lockouts and the secondary heat activation temperature.
  3. Enable Emergency Heat if the aux heat must run directly from the thermostat.

Applies to: Heat pump with aux heat

Source: Daikin One Touch smart thermostat training module TRC-10, p. 42. Written in our own words; check the manual for your exact model.

Set the clock from the ARC466 remote controller

Heat pump · FTXM-W/V

The clock is set with the Clock and Select buttons on the ARC466 series remote. Point the remote at the indoor unit when confirming the final step.

  1. Press the Clock button. The day of the week starts blinking.
  2. Press Select to set the current day of the week.
  3. Press the Clock button again. The time digits begin to blink.
  4. Press Select to set the present time. Hold the button to change time faster.
  5. Press the Clock button to save. Point the remote at the indoor unit. The time stops blinking when setting is complete.

Applies to: ARC466 series remote controller

Source: Daikin SiUS042113EA service manual, p. 50. Written in our own words; check the manual for your exact model.

Start and cancel ECONO operation

Heat pump · FTXM-W/V

ECONO runs the unit at reduced power. Each press of the Econo/Quiet button steps through a different option shown on the LCD. Turning ECONO off is done by pressing the button until no icon shows. The ON/OFF button also cancels it and clears the ECONO icon. Expect less cooling or heating capacity. If the unit is already drawing low power, ECONO will not save more.

  1. Press the Econo/Quiet button and choose the wanted mode.
  2. To cancel, press Econo/Quiet until no icon is displayed, or press ON/OFF.

Applies to: FTXM-W/V series

Source: Daikin SiUS042113EA service manual, p. 48. Written in our own words; check the manual for your exact model.

Start and stop COMFORT AIRFLOW

Heat pump · FTXM-W/V

Press the Comfort button on the remote to start COMFORT AIRFLOW. The icon shows on the display. Press the button again to stop it. The flaps then return to the position they were in before COMFORT AIRFLOW started. POWERFUL and COMFORT AIRFLOW cannot run together. The last direction button pressed overrides COMFORT AIRFLOW.

  1. Press the Comfort button to start COMFORT AIRFLOW.
  2. Confirm the icon is on the display.
  3. Press the Comfort button again to stop it.
  4. If a manual up or down flap direction is selected, COMFORT AIRFLOW is cancelled.

Applies to: Wall mounted FTXM-W/V remote control operation

Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 40. Written in our own words; check the manual for your exact model.

WEEKLY TIMER program setup and limits

Heat pump · FTXM-W/V

Up to 4 reservations can be set per day, and 28 per week. Each reservation sets ON/OFF, temperature and time. Copy mode can be used to repeat one day's settings to other days. Using OFF-OFF-OFF-OFF settings only sets a shutdown time each day.

  1. Set programs 1 to 4 for the first day that needs them.
  2. Use copy mode to apply the same settings to Tuesday through Friday when they match Monday.
  3. Leave Saturday empty if it has no timer settings.
  4. Set programs 1 to 4 for Sunday separately.
  5. Use ON-ON-ON-ON settings for scheduled mode and temperature changes, or OFF-OFF-OFF-OFF settings for automatic shutdown only.

Applies to: FTXM-W/V series with WEEKLY TIMER

Source: Daikin SiUS042113EA service manual, p. 51. Written in our own words; check the manual for your exact model.

Adjust the fan airflow rate

Mini-split · FTXM WVJU9

Each press of the airflow button steps through AUTO, quiet mode and levels 1 to 5, from low to high. Quiet mode runs the indoor fan at a weak level and makes it quieter. In DRY mode the airflow rate cannot be changed. Lower airflow gives less cooling or heating effect. In AUTO airflow, the unit sets the rate from room conditions, and it can end up weaker than quiet mode.

  1. Press the airflow rate button on the remote controller.
  2. Keep pressing to step through AUTO, quiet, and levels 1 to 5.
  3. If the rate seems too weak for the room, raise the level or switch off quiet mode.
  4. In DRY mode, expect no change because the rate is fixed.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin Room Air Conditioner Operation Manual, p. 16. Written in our own words; check the manual for your exact model.

Change temperature display between °C and °F

Mini-split · FTXM-W/V

Changes the unit used for temperature display on the remote controller.

  1. Press the upper side of the Temp button and the On button together and hold for 5 seconds.

Applies to: FTXM-W/V wireless remote controller

Source: SiUS042113EA Inverter Pair service manual, p. 164. Written in our own words; check the manual for your exact model.

Copy WEEKLY TIMER reservations to other days

Mini-split · FTXM-W/V

A reservation set once can be copied to another day. The whole reservation of the source day is copied, so change any single day afterwards in setting mode.

  1. Open copy mode from the WEEKLY TIMER screen.
  2. Select the source day that has the reservation.
  3. Select COPY, then confirm the copy.
  4. Choose each destination day and confirm. Check for the receiving tone and two OPERATION lamp blinks.
  5. Repeat for other days, then press the final confirm to activate WEEKLY TIMER.

Applies to: WEEKLY TIMER copy mode

Source: Daikin FTXM-W/V service manual, p. 54. Written in our own words; check the manual for your exact model.

Open indoor unit menu items on the display

Mini-split · FTXM-W/V

The indoor unit display has numbered menu items for brightness and CLEAN setting. Menu buttons are used to select and confirm. The menu returns to the default screen after 60 seconds.

  1. Press and hold the Menu button for 2 seconds.
  2. Use Select up or down to pick the menu number (1 = brightness, 2 = CLEAN).
  3. Press Menu for 2 seconds to confirm the menu item.
  4. Use Select up or down to change the value, then press Menu for 2 seconds to save.
  5. Press Cancel to return to the default screen, or press Cancel twice to exit sooner.

Applies to: Wall mounted FTXM-W/V indoor unit display

Source: Daikin FTXM-W/V service manual, pp. 57-58. Written in our own words; check the manual for your exact model.

Set a WEEKLY TIMER reservation

Mini-split · FTXM-W/V

Enter setting mode, choose the day and reservation number, then set ON or OFF timer, time, and temperature for ON timers. Confirm each reservation and finish with the final confirm step.

  1. Make sure the day of the week and clock time are correct. Set them first if not.
  2. Open WEEKLY TIMER setting mode and select the day and reservation number (1 to 4 per day).
  3. Select ON TIMER, OFF TIMER, or blank (blank deletes an existing reservation).
  4. Confirm, then set the time in 10-minute steps from 0:00 to 23:50.
  5. For ON TIMER, confirm the time and set the temperature.
  6. Confirm the reservation. Check for the receiving tone and that the OPERATION lamp blinks twice, and that the TIMER lamp lights orange.
  7. Repeat for further reservations, then press the final confirm to activate WEEKLY TIMER. The timer icon shows on the LCD.

Applies to: Wall mounted FTXM-W/V indoor unit with WEEKLY TIMER

Source: Daikin FTXM-W/V service manual, pp. 52-53. Written in our own words; check the manual for your exact model.

Set up-down and left-right airflow swing

Mini-split · FTXM WVJU9

Use the remote to start auto swing on the flaps (up-down) or louvers (left-right), or both together for 3-D airflow. Flap movement depends on mode. When the airflow rate is low or 3-D airflow is on, the room may not reach set temperature if air hits a wall. Do not move flaps or louvers by hand while they swing, as this can damage the mechanism.

  1. Use the remote controller only to change flap and louver angles. Never force them by hand while they swing.
  2. Press the up-down button to start flap auto swing.
  3. Press the left-right button to start louver auto swing.
  4. Press both buttons together to start 3-D airflow, and press either button again to cancel it.
  5. To park a flap or louver, press its button when it reaches the wanted position.
  6. If the airflow rate drops low during operation, the flaps and louvers stop; the flaps then stop in the upward position when up-down direction is set.
  7. If the room does not reach set temperature, change the airflow direction or raise the airflow rate.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin Room Air Conditioner Operation Manual, p. 17. Written in our own words; check the manual for your exact model.

Start and cancel 2-area INTELLIGENT EYE (FTXM09 / FTXM12)

Mini-split · FTXM WVJU9

The sensor tracks human movement and steers airflow left or right away from people, or toward them. If nobody is detected for 20 minutes, the unit enters energy saving operation. Do not place large objects, heaters or humidifiers in the sensing area, and do not hit the sensor.

  1. Press the INTELLIGENT EYE button on the remote and select the wanted mode.
  2. Choose no setting (blank), do not blow directly on people, or blow directly on people.
  3. When a mode is selected, the INTELLIGENT EYE lamp lights green.
  4. Selecting a mode stops any flap swing that is running.
  5. To cancel, press the button until no icon shows on the display.
  6. INTELLIGENT EYE can run together with COMFORT AIRFLOW; the last button pressed takes priority.

Applies to: FTXM09WVJU9, FTXM12WVJU9

Source: Daikin Room Air Conditioner Operation Manual, p. 19. Written in our own words; check the manual for your exact model.

Start and cancel COMFORT AIRFLOW

Mini-split · FTXM WVJU9

Sends air up in COOL and DRY and down in HEAT so air does not hit people directly.

  1. Press the COMFORT AIRFLOW button on the remote.
  2. Confirm COMFORT AIRFLOW appears on the display.
  3. Press the button again to cancel.
  4. After cancelling, the flaps return to their previous position.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin Room Air Conditioner Operation Manual, p. 23. Written in our own words; check the manual for your exact model.

Start and cancel INTELLIGENT EYE (FTXM18 / FTXM24)

Mini-split · FTXM WVJU9

Single-sensor mode that detects movement and runs energy saving after 20 minutes without presence.

  1. Press the INTELLIGENT EYE button on the remote and select the wanted mode.
  2. The INTELLIGENT EYE lamp lights green when active.
  3. To cancel, press the INTELLIGENT EYE button.
  4. The INTELLIGENT EYE lamp goes off when cancelled.

Applies to: FTXM18WVJU9, FTXM24WVJU9

Source: Daikin Room Air Conditioner Operation Manual, p. 21. Written in our own words; check the manual for your exact model.

Turn automatic CLEAN drying on or off

Mini-split · FTXM WVJU9

CLEAN is a menu setting, disabled by default. When enabled, the unit dries the indoor coil area after COOL or DRY stops, to reduce condensation. The display returns to the default screen after 60 seconds if no key is pressed.

  1. Press and hold the menu button for 2 seconds.
  2. Press the up or down button and select the CLEAN menu number.
  3. Press the confirm button to select the setting.
  4. Press the up or down button to choose enabled or disabled (default is disabled).
  5. Press the confirm button again to save.
  6. Press the return button to go back to the default screen, or wait 60 seconds.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin Room Air Conditioner Operation Manual, p. 17. Written in our own words; check the manual for your exact model.

Set the maintenance contact number

Water heater · Mega-Q

Enter the maintenance contact phone number in the remote controller service settings.

  1. Press and hold the Cancel button for 4 seconds or more to open the service settings menu.
  2. Select Maintenance Contact in the Service Settings menu and press Menu/OK.
  3. Select Maintenance Contact again and press Menu/OK.
  4. Use Up/Down to set each digit and the Left/Right buttons to move the highlight.
  5. Press Menu/OK, select Yes on the save confirmation and press Menu/OK.
  6. Press Cancel to return to the basic screen.

Applies to: Remote controller for the hot water generation system

Source: Daikin Mega-Q installation manual, p. 49. Written in our own words; check the manual for your exact model.

Commissioning

Start-up and set-up steps that are easy to miss.

Check adaptor power and communication LEDs after wiring

Air conditioner · Daikin One+ Translation Adaptor

After wiring, power the indoor unit and read the adaptor indicators. The Power LED shows power is connected. The S21 LED is on for S21 units; the P1P2 LED is on for P1P2 units. When power and communication are confirmed, cover the LEDs with the rubber grommet so light does not show through the indoor unit.

  1. Turn on power to the indoor unit.
  2. Confirm the Power LED is on.
  3. Confirm the S21 LED (S21 units) or P1P2 LED (P1P2 units) is on.
  4. Fit the rubber grommet over the LEDs once operation is verified.

Applies to: Daikin One+ Translation Adaptor with S21 or P1P2 indoor units

Source: Daikin One+ Translation Adaptor installation instructions, p. 8. Written in our own words; check the manual for your exact model.

Confirm adaptor wiring with the LED indicators

Air conditioner · Daikin One+ Translation Adaptor

After wiring and mounting, use the adaptor's LEDs to check that the thermostat link is working. The Power LED shows the adaptor is getting power. The S21 LED lights on S21 indoor units, and the P1P2 LED lights on P1P2 indoor units. Once power and communication are confirmed, cover the LEDs so their light does not show through the indoor unit.

  1. Turn on power to the indoor unit.
  2. Check that the Power LED on the adaptor is lit. This means the adaptor is powered.
  3. If the indoor unit uses S21 termination, check that the S21 LED is on.
  4. If the indoor unit uses P1P2 termination, check that the P1P2 LED is on.
  5. After power and communication are verified, fit the rubber grommet over the LEDs to stop light showing through the indoor unit.
  6. Put the front cover back on the translator box and press down until it snaps into place. On some wall-mounted units the front cover is removed to fit inside the piping chase.

Applies to: Daikin One+ Translation Adaptor (S21 and P1P2 indoor units)

Source: IOD-7134 Daikin One+ Translation Adaptor installation instructions, p. 8. Written in our own words; check the manual for your exact model.

Do not charge by suction pressure

Air conditioner · DX6VS, DZ6VS

The charge must be set by subcooling, not by suction pressure.

Applies to: Charge verification

Source: Daikin DX6VS/DZ6VS outdoor unit installation & service reference, p. 30. Written in our own words; check the manual for your exact model.

Equipment setup order for unitary systems

Air conditioner · One+ and Touch

Setup walks through communication, personalization and equipment before optimization and preferences.

  1. Choose English, Spanish or French, then choose unitary equipment type.
  2. Connect Wi-Fi from the list of networks; search again if needed.
  3. Set date, time and time zone (automatic when connected to Wi-Fi or the mobile app).
  4. Choose room name and degree units (Fahrenheit or Celsius).
  5. Add equipment: scan model and serial numbers, confirm control and inverter software versions, cool and heat stages, tonnage and airflow trims.
  6. Complete the optimization and system test steps, then set preferences.

Applies to: Unitary systems

Source: Daikin One+ and Touch Thermostat Commissioning Menu Outline, p. 1, p. 2 and p. 5. Written in our own words; check the manual for your exact model.

Limit on refrigerant added while adjusting subcooling

Air conditioner · DX6VS, DZ6VS

Do not add more than 8 oz to reach target subcooling. Add in small steps and let the system stabilise.

  1. Add about 1 oz at a time.
  2. Wait 10 minutes after each addition before reading subcooling again.
  3. Check the Schrader ports for leaks and tighten valve cores if needed. Install caps finger-tight.

Applies to: Subcooling adjustment

Source: Daikin DX6VS/DZ6VS outdoor unit installation & service reference, p. 30. Written in our own words; check the manual for your exact model.

Power-up flap reset

Air conditioner · FTXM WVJU9

After the circuit breaker is switched on, the indoor unit flaps open and close once to find their reference position. This is normal and not a fault.

Applies to: Indoor unit, all FTXM WVJU9 models

Source: Daikin Room Air Conditioner operation manual, p. 11. Written in our own words; check the manual for your exact model.

Set the clock on the remote controller

Air conditioner · FTXM WVJU9

The clock must be correct or the ON/OFF TIMER and WEEKLY TIMER will not start at the right times.

  1. Press the CLOCK button. The clock display starts blinking.
  2. Use the NEXT or BACK buttons to set the current day of the week (MON to SUN).
  3. Press SELECT. The minutes/hours field starts blinking.
  4. Use the NEXT or BACK buttons to set the present time. Hold the button to change the time faster.
  5. Press SELECT to finish.

Applies to: Remote controller, all FTXM WVJU9 models

Source: Daikin Room Air Conditioner operation manual, p. 11. Written in our own words; check the manual for your exact model.

Heater kit and aux alarm wiring changes

Air handler · DV**FEC, DFVE**

Two wiring changes are needed when adding optional accessories.

  1. When installing the optional heat kit, discard connector PL1.
  2. When installing an aux alarm switch, remove the short red circuiting wire and connect the aux alarm switch in its place.

Applies to: EEV air handler with optional heat kit or aux alarm

Source: Daikin SiUS612209EA service instructions, p. 79. Written in our own words; check the manual for your exact model.

Select the transformer supply voltage

Air handler · DFVE EEV air handler, DV**FEC EEV air handler, CAPE / CHPE EEV cased coil

The correct transformer tap depends on the power supply voltage to the gas furnace or blower unit.

  1. Measure the supply voltage to the gas furnace or blower unit.
  2. Select the matching transformer supply voltage (208, 230 or 120 VAC tap as wired).

Applies to: EEV indoor units with transformer TR1

Source: Daikin SiUS612209EB service instructions, p. 80. Written in our own words; check the manual for your exact model.

Set the transformer for 208 V operation

Air handler · DV**FEC, DFVE**

The factory wiring is for 230 V. Move the red transformer leads for 208 V supply.

  1. For 208 V operation, move the red wires to the 208 V terminal of the 2-transformer (TR1/TR2).
  2. On cased coils, select the transformer supply voltage to match the power supply to the gas furnace or blower unit.

Applies to: EEV air handler and EEV cased coil transformers

Source: Daikin SiUS612209EA service instructions, p. 79-80. Written in our own words; check the manual for your exact model.

Add equipment: auxiliary heat source

Furnace · Daikin One+

Use Add Equipment to set up an auxiliary heat source. Aux heat is the only option for an AC-only outdoor unit. Emergency heat appears as a system mode with heat pump units and can directly turn on aux heat when enabled.

  1. Select Add Equipment and choose auxiliary heat.
  2. Set secondary heat lockouts and activation temperature in the control section.
  3. Enable emergency heat if direct aux operation is needed.

Applies to: Daikin One+ with aux heat or AC-only outdoor unit

Source: Daikin One+ installation & commissioning, p. 28-29. Written in our own words; check the manual for your exact model.

Add the thermostat location and log in

Furnace · Daikin One+

Log in with the email and password for the mobile account. If the password is forgotten, use the forgot password link to recover it by email. Enter the address where the thermostat is installed so that accurate local information is gathered.

  1. Enter the email and password for the mobile account and tap login.
  2. If the password is forgotten, tap the forgot password link and recover it by email.
  3. Enter the address where the thermostat is located.

Applies to: Daikin One+ mobile app location setup

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 56. Written in our own words; check the manual for your exact model.

Add the thermostat location in the mobile app

Furnace · Daikin One+

Step 3 of app setup. Sign in with the email and password tied to your mobile account. If you cannot remember the password, use the forgot-password option to recover it by email. Then enter the address where the thermostat is installed so the app can gather accurate local information.

  1. Open the Daikin mobile app and sign in with the account email and password.
  2. If the password is forgotten, use the forgot-password link and recover it by email.
  3. Enter the address where the thermostat is located.
  4. Confirm the location to finish adding it to the account.

Applies to: Daikin One+ thermostat with mobile app

Source: Daikin One+ Installation & Commissioning, p. 56. Written in our own words; check the manual for your exact model.

Added equipment and accessories

Furnace · Daikin One+

The thermostat supports several accessories. Humidifiers and dehumidifiers can use aux 1 or aux 2. An isolation relay is recommended between an auxiliary device and the thermostat.

  1. Install humidifier or dehumidifier on aux 1 or aux 2.
  2. Use an isolation relay between each auxiliary device and the thermostat.

Applies to: Daikin One+ accessories including air quality sensor, humidifier, dehumidifier, UV bulb, electronic filter, HEPA filter and EWC zone board

Source: Daikin One+ installation & commissioning, p. 27. Written in our own words; check the manual for your exact model.

Calibration of the thermostat

Furnace · Daikin One+

Calibration must be done with the thermostat in OFF mode, and the thermostat needs time to equalize first.

  1. Set the thermostat to OFF mode.
  2. Wait 30 minutes so the thermostat can equalize.
  3. Run Calibration from System Optimization.

Applies to: Daikin One+ thermostat

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 33. Written in our own words; check the manual for your exact model.

Compatible systems for two-way communication

Furnace · Daikin One+

The Daikin One+ offers two-way communication with Daikin FIT systems, residential inverter air conditioners and heat pumps, and two-stage air conditioners and heat pumps. It also works with the Daikin One ecosystem, which covers temperature control and air quality. It acts as a cloud-connected hub and controller for communicating HVAC systems. Daikin recommends adding the Daikin One home air monitor and a MERV 15 filter.

Applies to: Daikin One+ Smart Thermostat with compatible Daikin systems

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 5. Written in our own words; check the manual for your exact model.

Confirm the app account

Furnace · Daikin One+

A welcome email with a six-digit code is sent to the email address used when the account was created. Entering that code in the app lets you continue.

  1. Open the email account used to create the app account.
  2. Find the welcome email and note the six-digit code.
  3. Enter the six-digit code in the app to continue.

Applies to: Daikin One+ mobile app account

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 55. Written in our own words; check the manual for your exact model.

Connect the mobile app to the thermostat with the six-digit code

Furnace · Daikin One+

Step 4 of app setup. Wi-Fi must be enabled on the thermostat first. The six-digit code shown on the thermostat is entered into the app to link the two devices.

  1. Make sure Wi-Fi is enabled on the thermostat.
  2. Open the account on the app to retrieve the six-digit code.
  3. Read the six-digit code shown on the thermostat screen.
  4. Type that code into the connection field in the app.
  5. Tap connect to finish and control the Daikin One+ from the mobile device.

Applies to: Daikin One+ thermostat with Wi-Fi and mobile app

Source: Daikin One+ Installation & Commissioning, p. 57. Written in our own words; check the manual for your exact model.

Create the app account

Furnace · Daikin One+

Tap create one in the bottom right of the login screen. Read the terms of service, privacy statement and other notices before agreeing. Enter your name, a valid email address and a password.

  1. On the login screen, tap create one at the bottom right.
  2. Read the terms, privacy statement and notices.
  3. Enter name, valid email address and password.
  4. Continue to account confirmation.

Applies to: Daikin One+ mobile app account

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 54. Written in our own words; check the manual for your exact model.

Dealer information entry

Furnace · Daikin One+

Dealer information can be entered and reviewed in this menu.

  1. Open Dealer information under Preferences.
  2. Enter the dealer details and review them.

Applies to: Daikin One+ thermostat

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 39. Written in our own words; check the manual for your exact model.

Finish full set-up

Furnace · Daikin One+

Selecting complete set-up ends full set-up and returns the thermostat to normal mode so settings can be checked. All steps should be reviewed before this final step.

  1. Review every full set-up step.
  2. Select complete set-up as the final step.
  3. Check the settings in normal mode.

Applies to: Daikin One+ thermostat, full set-up

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 41. Written in our own words; check the manual for your exact model.

Full set-up step 1: communication network

Furnace · Daikin One+

Connect the thermostat to Wi-Fi during set-up. Once connected, it can check and update its software automatically.

  1. Select the home Wi-Fi network from the search list.
  2. Confirm the wireless router is password protected.
  3. Use a router that supports 5 GHz and also supports 2.4 GHz.

Applies to: Daikin One+ full set-up

Source: Daikin One+ installation & commissioning, p. 24. Written in our own words; check the manual for your exact model.

Full set-up step 2: personalization

Furnace · Daikin One+

Personalization settings are reviewed in this step. A green check mark appears next to each item once it has been reviewed in the set-up menu.

  1. Set language and large font selection.
  2. Set date and time (sets automatically if Wi-Fi is connected).
  3. Set thermostat name and degree units.

Applies to: Daikin One+ full set-up

Source: Daikin One+ installation & commissioning, p. 25. Written in our own words; check the manual for your exact model.

Full set-up step 3: equipment set-up

Furnace · Daikin One+

The thermostat finds equipment on the communication network or lets you add or remove equipment from a preset list. The unit identified sets which configuration screens are shown.

  1. Review unit specifications.
  2. Configure cool settings, heat settings, heat pump settings, humidifier relay, aux alarm and heater kit as applicable.

Applies to: Daikin One+ full set-up

Source: Daikin One+ installation & commissioning, p. 26. Written in our own words; check the manual for your exact model.

Mobile app account setup overview

Furnace · Daikin One+

Account setup has four stages: download the app from the iOS or Android store, create the account, confirm the account, and add the thermostat location. Connecting the app to the thermostat follows. You need a mobile device, a Daikin One+ connected to Wi-Fi and wired to a communicating system, and a valid email address.

  1. Confirm you have a mobile device, a valid email address, and a Daikin One+ on Wi-Fi wired to a communicating system.
  2. Download the app from the iOS or Android app store.
  3. Create the account, confirm it, add the thermostat location, then connect the app to the thermostat.

Applies to: Daikin One+ mobile app with communicating system

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 53. Written in our own words; check the manual for your exact model.

Pairing thermostat with 9 pin or 7 pin connectors

Furnace · Daikin One+

Some communicating units use a single connector that must be moved to pair the thermostat terminals with the board inputs.

  1. On a communicating indoor unit with a 9 pin connector only, move the connector to the far left so R, C, G and W1 pair with 1, 2, R and C on the indoor board.
  2. On a communicating outdoor unit with a 7 pin connector only, move the connector to the far left so R and C pair with 1 and 2 on the outdoor board.
  3. Confirm the Daikin One+ terminals are labeled 1, 2, C and R before connecting.

Applies to: Communicating indoor units with 9 pin connector and outdoor units with 7 pin connector

Source: Daikin One+ installation & commissioning, p. 16. Written in our own words; check the manual for your exact model.

Service reminders during full set-up

Furnace · Daikin One+

Service reminders are chosen during full set-up. The number of reminders depends on the installed equipment and accessories. Once equipment is added, a reminder interval of 1 to 24 months can be picked to suit that equipment. The homeowner cannot edit service reminders afterward.

  1. Add the installed equipment and accessories.
  2. Select a service reminder interval from 1 to 24 months that fits the equipment.

Applies to: Daikin One+ thermostat, full set-up

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 40. Written in our own words; check the manual for your exact model.

Step 1 Communication: Wi-Fi setup

Furnace · Daikin One+ Smart Thermostat

Step 1 configures the network. With Wi-Fi set up, the thermostat can check the software version and update itself. The equipment type shown matches what was selected at start-up.

  1. Select the home Wi-Fi network from the search list.
  2. Confirm the wireless router is password protected.
  3. Confirm the router is 5 GHz and supports 2.4 GHz.
  4. Confirm the equipment type matches the start-up selection.

Applies to: Daikin One+ Step 1 Communication

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 24. Written in our own words; check the manual for your exact model.

Step 4 System Optimization menu overview

Furnace · Daikin One+

Full set-up System Optimization step includes the system test, charge mode, optional tests, error history, calibration and status screens.

  1. Open Full Set-up and go to Step 4 System Optimization.
  2. Choose the test or screen needed: System test, Charge mode, Optional test, Error history, Calibration or Status.
  3. Charge mode and System test apply to inverter systems only.

Applies to: Daikin One+ with heat pump or air conditioner

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 33. Written in our own words; check the manual for your exact model.

Step 5 Preferences menu

Furnace · Daikin One+

Four preference groups are available. Changing preferences is optional, but reminders and dealer contact information should be entered.

  1. Review Cool/Heat preferences.
  2. Set House settings if needed.
  3. Enter Dealer information.
  4. Set Reminders.

Applies to: Daikin One+ thermostat

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 38. Written in our own words; check the manual for your exact model.

Thermostat terminal labels do not match unit labels

Furnace · Daikin One+ Smart Thermostat

The thermostat is labeled 1, 2, C, R, while communicating equipment uses its own labels. Pair terminals by function as shown in the connector table. A wrong pairing gives a communication error or no equipment detected.

  1. Check the unit board labels (1, 2, R, C) before landing the wires.
  2. Match the thermostat 1, 2, C, R terminals to the unit labels using the connector pairing table.
  3. Confirm the thermostat communicates with the equipment after power-up.

Applies to: Communicating indoor and outdoor units

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 16-17. Written in our own words; check the manual for your exact model.

Add the thermostat location and connect the app to the thermostat

General · Daikin One+

Link the app to the thermostat using the six-digit code the thermostat shows. Wi-Fi must be enabled on the thermostat first.

  1. Log in with the account email and password. Use the forgot password link if needed.
  2. Enter the address where the thermostat is installed.
  3. Confirm Wi-Fi is enabled on the thermostat.
  4. Access the account to get the six-digit code.
  5. Type the six-digit code shown on the thermostat into the app.
  6. Tap connect to finish and operate the Daikin One+ from the mobile device.

Applies to: Daikin One+ thermostat with the Daikin mobile app

Source: Daikin One+ Smart Thermostat Installation & Commissioning (S21) manual, p. 50-51. Written in our own words; check the manual for your exact model.

Calibrate after the thermostat has run 30 minutes

General · Daikin One+ Smart Thermostat

Calibrate the system only after the thermostat has been powered for at least 30 minutes. This gives accurate temperature sensor readings. Commissioning steps are in the thermostat packaging documents, which are not on these pages.

  1. Power the thermostat for at least 30 minutes.
  2. Run the calibration step from the thermostat documentation.

Applies to: Daikin One+ Smart Thermostat

Source: Daikin flushmount installation card, p. 4. Written in our own words; check the manual for your exact model.

Commissioning wizard behaviour

General · Daikin One+, S21

The guided set-up walks the installer through the full commissioning process. Screens are filled in from the equipment model numbers, matched to a database of device configuration settings. Any setting can be reached directly, values are saved as they are entered, and the set-up can be paused and resumed.

  1. Start Begin set-up to run the guided commissioning.
  2. Enter equipment model numbers so the screens populate correctly.
  3. Stop and restart as needed. Entered settings are kept.

Applies to: Daikin One+ S21 commissioning

Source: Daikin One+ installation & commissioning (S21) manual, p. 21. Written in our own words; check the manual for your exact model.

Complete full set-up

General · Daikin One+

Completing full set-up ends the installer setup and returns the thermostat to normal mode so settings can be checked. All steps must be reviewed before completing.

  1. Review every Full Set-up step.
  2. Select Complete set-up to finish and show normal mode.
  3. Verify the settings in normal mode.

Applies to: Daikin One+ Full Set-up

Source: Daikin One+ Installation & Commissioning (S21), p. 35. Written in our own words; check the manual for your exact model.

Create and confirm the Daikin One+ mobile app account

General · Daikin One+

Set up the homeowner app account before connecting it to the thermostat. The email address you use must be able to receive the confirmation code.

  1. Tap the create option at the bottom right of the app login screen.
  2. Read the terms, service and privacy notices before agreeing.
  3. Enter a name, a valid email address and a password.
  4. Open the email inbox for the address you entered and find the welcome email.
  5. Enter the six-digit code from that email into the app to confirm the account.

Applies to: Daikin One+ thermostat with the Daikin mobile app

Source: Daikin One+ Smart Thermostat Installation & Commissioning (S21) manual, p. 48-49. Written in our own words; check the manual for your exact model.

Enter dealer information

General · Daikin One+

The dealer information screen stores the installer's details. The homeowner can view everything entered here.

  1. Open Full Set-up and select Dealer information.
  2. Enter the dealer details.

Applies to: Daikin One+ Full Set-up

Source: Daikin One+ Installation & Commissioning (S21), p. 34. Written in our own words; check the manual for your exact model.

Full set-up: five steps to complete

General · Daikin One+

Start-up full set-up runs through five steps: Communication, Personalization, Equipment Set-up, System Optimization and Preferences. All five must be completed and reviewed before set-up is finished so the system is configured correctly for the homeowner.

  1. Start the full set-up from the start-up menu.
  2. Complete Communication, Personalization, Equipment Set-up, System Optimization and Preferences in that order.
  3. Review every step before finishing set-up.

Applies to: Daikin One+ thermostat, full set-up

Source: Daikin One+ Installation & Commissioning (S21), p. 24. Written in our own words; check the manual for your exact model.

Install or reinstall the wire mesh insect screen

General · Daikin One Powered Ventilator

The insect screen sits inside the control compartment just inside the intake port, stamped side toward the controller.

  1. Remove the control compartment cover.
  2. Insert the screen behind the base tab with its wider side running side to side.
  3. Slide it toward the side with the larger top tab and seat it behind that tab.
  4. Slide it the other way and tuck it behind the smaller top tab.
  5. Confirm both top tabs hold the screen, then reinstall the cover.

Applies to: DQ-P-16-100

Source: IO-DPV installation manual, p. 6. Written in our own words; check the manual for your exact model.

Measure airflow at the intake test port

General · Daikin One Powered Ventilator

A test port sits at the base of the intake duct collar and is capped with a red plastic cover.

  1. Remove the red plastic port cover at the base of the intake duct collar.
  2. Insert a pitot tube into the port to read flowrate.
  3. Make sure ducting or insulation does not block the port.

Applies to: DQ-P-16-100

Source: IO-DPV installation manual, p. 4. Written in our own words; check the manual for your exact model.

Run the system fan continuously for best cleaning

General · Daikin One Premium Air Cleaner

The air cleaner only removes particles while the system fan is running.

  1. Set the heating/cooling fan to run continuously, on low speed if available.
  2. Keep furniture and carpets away from the return grilles so air flows freely.

Applies to: DV1-15 series

Source: Daikin One Premium Air Cleaner installation & operation manual, p. 3. Written in our own words; check the manual for your exact model.

Sensor probe LED: solid blue means online

General · Daikin One

After the sensor probe is powered or reinserted, a solid blue LED means the monitor is back online and operating. Wait for solid blue and do not assume it is working while the LED is flashing.

  1. Restore 24V power to the sensor probe.
  2. Wait for the LED to show solid blue (not flashing).

Applies to: DSEN-HAQA Daikin One Home Air Monitor

Source: Daikin One Home Air Monitor installation manual (IO-DSEN-HAQA), p. 4. Written in our own words; check the manual for your exact model.

Set odor sensor baseline at power-on

General · Humidifying Air Purifier

The odor sensor baseline is set from the odor level in the first minute after the power plug is inserted, so plug the unit in when the air is clean.

  1. Plug in the unit only when the room air is odor-free.
  2. Start operation after plugging in.

Applies to: Odor sensor

Source: Daikin MCKB70YSAU installation & operation manual, p. 11, p. 16. Written in our own words; check the manual for your exact model.

Set preferences in Full Set-up Step 5

General · Daikin One+

Step 5 Preferences sets the cool and heat set points, deadband, and changeover points with their guard timers. The screen lists the deadband and changeover fields with ranges, but the printed ranges on this page are hard to match to each field, so confirm them on the thermostat.

  1. Open Full Set-up and go to Step 5 Preferences.
  2. Set the cool set point and heat set point.
  3. Set the deadband and the cool and heat change-over points.
  4. Set the immediate changeover points and the guard timers for change to heating and change to cooling.
  5. Leave the defaults unless the application requires otherwise.

Applies to: Daikin One+ Full Set-up

Source: Daikin One+ Installation & Commissioning (S21), p. 33. Written in our own words; check the manual for your exact model.

Start-up screens and system selection

General · Daikin One+, S21

The start-up screen appears when the thermostat is powered. The welcome screen offers preference choices. Choose Single/Multi-split (S21) before going to the setup screen. The thermostat version is shown on the learn more screen.

  1. Power the thermostat and wait for the start-up screen.
  2. On the welcome screen, select Single/Multi-split (S21) before continuing to setup.
  3. Check the thermostat version on the learn more screen if needed.

Applies to: Daikin One+ S21 start-up

Source: Daikin One+ installation & commissioning (S21) manual, p. 22. Written in our own words; check the manual for your exact model.

Step 1 Communication: Wi-Fi setup

General · Daikin One+

Select the home Wi-Fi network so the thermostat can connect. Once Wi-Fi is set up, the thermostat can check the software version and update itself to the latest version. Equipment type shows the equipment chosen at start-up.

  1. Select the home Wi-Fi network from the search list.
  2. Confirm the router is password protected.
  3. Use a 5 GHz router only if it also supports 2.4 GHz.

Applies to: Daikin One+ thermostat, Communication step

Source: Daikin One+ Installation & Commissioning (S21), p. 25. Written in our own words; check the manual for your exact model.

Step 2 Personalization: fields to check

General · Daikin One+

Personalization covers language, large font, date and time, thermostat name and degree units. If Wi-Fi is connected, date and time set automatically. A green check mark appears next to each item once it has been reviewed.

  1. Check language, large font, date and time, thermostat name and degree units.
  2. Confirm date and time are correct if Wi-Fi is not connected.
  3. Review each item so it gets a green check mark.

Applies to: Daikin One+ thermostat, Personalization step

Source: Daikin One+ Installation & Commissioning (S21), p. 26. Written in our own words; check the manual for your exact model.

Step 3 Equipment Set-up: entering equipment

General · Daikin One+

Pick the equipment and accessories from the list. After selecting the model number, the outdoor and indoor unit serial numbers must be typed in by hand. If the indoor model number is entered manually, the indoor unit type must also be selected.

  1. Select the equipment and accessories to add or remove.
  2. Select the model number.
  3. Enter the serial number for the indoor unit and the outdoor unit.
  4. If the indoor model was entered manually, select the indoor unit type.

Applies to: Daikin One+ thermostat, Equipment Set-up step

Source: Daikin One+ Installation & Commissioning (S21), p. 27-28. Written in our own words; check the manual for your exact model.

Test damper after restoring power

General · Daikin One Powered Ventilator

Test operation after the damper is wired and powered so you can confirm it tracks the ventilator.

  1. Restore power.
  2. Run the ventilator and confirm the damper opens.
  3. Stop the ventilator and confirm the damper closes.

Applies to: DQ-P-MDV with DQ-P-16-100 Powered Ventilator

Source: Daikin IO-DPVMD motorized damper installation manual, p. 3. Written in our own words; check the manual for your exact model.

Add auxiliary heat source in full setup

Heat pump · Daikin One Touch

Use Add Equipment in full setup to configure an auxiliary heat source. Aux heat is the only option when the outdoor unit is air conditioning only.

  1. Open Full Set-up and select Add Equipment.
  2. Select Auxiliary Heat and configure the source.
  3. For an AC-only outdoor unit, select aux heat as the only heat option.

Applies to: Heat pump or AC outdoor unit with auxiliary heat

Source: Daikin One Touch smart thermostat training module TRC-10, p. 41. Written in our own words; check the manual for your exact model.

Add thermostat to job and configure zoning

Heat pump · Daikin One Touch

Add the thermostat to the job in the app. The 2D bar code is on the terminal subbase, and the DKN(S) number is found in the thermostat settings menus. Zone board configuration is viewed with the toggle. If the thermostat is on a zone board and not zone one, equipment info will not show.

  1. Tap + in the top right corner of the app.
  2. Scan the 2D bar code on the terminal subbase, or enter the DKN(S) number manually.
  3. Find the DKN number in the thermostat settings menus if needed.
  4. Slide the toggle to check the zone board configuration.
  5. Confirm the thermostat is on zone one, otherwise equipment info is unavailable.

Applies to: Daikin One Touch thermostat

Source: Daikin One Touch Smart Thermostat Training Module TRC-10, p. 24. Written in our own words; check the manual for your exact model.

Adding thermostat location in the app

Heat pump · Daikin One Touch

The app can set the thermostat location from GPS or by entering it manually.

  1. Press the Add Location button on the Add Location screen.
  2. For GPS: select Allow Once or Allow While Using App, then follow the prompts.
  3. For manual entry: select Don't Allow, enter the location information, select Next, drag the pin over the location on the map and save the location.

Applies to: Daikin One Touch smart thermostat with SkyportHome app

Source: Daikin One Touch Smart Thermostat training module TRC-10, p. 69-70. Written in our own words; check the manual for your exact model.

Anchor the unit with foundation bolts and set drain clearance

Heat pump · DX6VS, DZ6VS, DZ6VSA

Use four foundation bolts sized by unit size. Stop the bolt ends about 1 inch above the pad. If drain water could cause a problem, use the optional drain plug. Leave at least 4 inch under the bottom frame. In cold climates do not use the centralized drain method, because drain freeze-up and ice build-up on the bottom frame can occur.

  1. Prepare 4 foundation bolts with nuts and washers (not supplied): 3/8 in or 7/16 in for 1.5-3.0 ton FIT and 2.0 ton Enhanced Capacity FIT; 1/2 in for 3.5-5.0 ton FIT and 3.0-4.0 ton Enhanced Capacity FIT.
  2. Screw the bolts in until their ends are about 1 in above the foundation surface.
  3. Where drainage could splash people, fit the optional drain plug and pipe the drain.
  4. Keep at least 4 in clear under the bottom frame.
  5. In cold climates do not use centralized drainage.

Applies to: All DX6VS, DZ6VS and DZ6VSA outdoor units

Source: Daikin DX6VS/DZ6VS/DZ6VSA installation manual 3P731493-1, p. 3. Written in our own words; check the manual for your exact model.

Aux heat thermostat wiring

Heat pump · Daikin One+ Unitary Aux Heater

The thermostat aux outputs are dry contacts that close to switch on the auxiliary heat equipment. A 24V AC control signal must run through one of the thermostat aux contacts. Aux 1 and Aux 2 each have a common (c) terminal and a normally open contact. The ground terminal is chosen in the Daikin One+ installer wizard.

  1. Wire the aux heat field device to the thermostat Aux 1 or Aux 2 terminal and its common (c) terminal, using the normally open contact.
  2. Route the 24V AC control signal through one of the aux contacts.
  3. Use at least 18-gauge wire.
  4. Keep the wire run to 125 ft or less.
  5. Select the ground terminal in the Daikin One+ installer wizard.

Applies to: Daikin One+ thermostat aux heat wiring

Source: Unitary Aux Heater installation and setup, p. 2. Written in our own words; check the manual for your exact model.

Complete set-up

Heat pump · Daikin One Touch

Completing set-up ends the full set-up and returns the thermostat to normal mode so settings can be checked. Checkmarks beside each step show what is done. Every step must be reviewed before completing.

  1. Review every set-up step and confirm each has a checkmark.
  2. Select complete set-up to finish and enter normal mode.
  3. Check the settings in normal mode.

Applies to: Daikin One Touch thermostat, full set-up

Source: Daikin One Touch installation guide, p. 54. Written in our own words; check the manual for your exact model.

Complete setup and share commissioning report

Heat pump · Daikin One Touch

After all steps are complete, a commissioning report can be shared before the job is closed. One copy can go to the homeowner and one to the dealer.

  1. Finish all commissioning steps.
  2. Share the commissioning report with the homeowner.
  3. Share the commissioning report with the dealer.
  4. Complete the job.

Applies to: Daikin One Touch thermostat

Source: Daikin One Touch Smart Thermostat Training Module TRC-10, p. 32. Written in our own words; check the manual for your exact model.

Connect the D-Checker cable and verify the COM port

Heat pump · DX6VS, DZ6VS

The cable plugs into connector X41A on the outdoor board. The connector location differs between chassis sizes, so check the matching board. The COM port in Device Manager must match the one used in D-Checker.

  1. Large chassis (3.5-4.0 ton): plug the D-Checker cable into X41A on the outdoor PCB.
  2. Small chassis (1.5-3.0 ton): plug the D-Checker cable into X41A on the outdoor PCB.
  3. Plug the USB end of the cable into the laptop.
  4. Open Device Manager and go to hardware selection.
  5. Open COM Ports and note the port the USB connector uses.

Applies to: 1.5-3.0 ton and 3.5-4.0 ton outdoor units

Source: Daikin SiUS612209EB service instructions, p. 129. Written in our own words; check the manual for your exact model.

Connecting the app to the thermostat

Heat pump · Daikin One Touch

Pair the app to the thermostat using the six-digit code shown on the thermostat.

  1. In the app, select Add Device.
  2. Use the dropdown to select the thermostat model.
  3. Make sure Wi-Fi is enabled on the thermostat.
  4. On the thermostat, open the main screen dropdown and go to settings/account to show the six-digit code.
  5. Type the six-digit code into the app.
  6. Tap Add. The app will display the thermostat.

Applies to: Daikin One Touch smart thermostat with SkyportHome app

Source: Daikin One Touch Smart Thermostat training module TRC-10, p. 71. Written in our own words; check the manual for your exact model.

Create a job and add the thermostat

Heat pump · Daikin One Touch

Every job needs a location. The thermostat can be added by scanning its code or typing its DKN number.

  1. Tap the + sign to add location details. Use GPS or type the address.
  2. Tap + in the top right corner to add a thermostat.
  3. Scan the 2D bar code on the terminal subbase, or enter the DKN(S) number manually.
  4. Find the DKN number in the thermostat settings menus if needed.
  5. For zoning, slide the toggle to view zone board configuration.
  6. If the thermostat is on a zone board and not zone one, equipment info will not show.

Applies to: SkyportCare jobs and thermostat setup, including zoning

Source: Daikin One Touch Smart Thermostat training module TRC-10, p. 23-24. Written in our own words; check the manual for your exact model.

Create a recording and select the system

Heat pump · DX6VS, DZ6VS

Recording needs a customer record. D-Checker will not talk to a system that is in sleep or hibernate mode.

  1. Click Recording (F1).
  2. Select Add new (F3).
  3. Enter at least the customer ID, then select OK (F1).
  4. Click Select (F2) when the customer is chosen, then New.
  5. Click Auto select (F2).
  6. Select the correct COM port and press OK (F1).
  7. Wait for the detection to finish; the system name will fill in.
  8. Click OK (F1).
  9. If nothing is detected, check the COM port and make sure the system is awake, not in sleep mode.

Applies to: Daikin inverter outdoor units

Source: Daikin SiUS612209EB service instructions, pp. 130-131. Written in our own words; check the manual for your exact model.

Dealer information

Heat pump · Daikin One Touch

Enter and review the dealer's contact details. The homeowner sees this information on the thermostat home screen if a system error occurs.

  1. Open dealer information in full set-up.
  2. Enter or check the dealer details.

Applies to: Daikin One Touch thermostat, full set-up

Source: Daikin One Touch installation guide, p. 52. Written in our own words; check the manual for your exact model.

Invite a dealer team member in SkyportCare

Heat pump · Daikin One Touch

Admins can add team members. Technician role can only add new customers.

  1. Open the SkyportCare account and click Add Member in the Team Member widget.
  2. Enter first name, last name, email and access level (Admin or Technician).
  3. The invited person gets an email with a temporary password and logs in at the SkyportCare site.
  4. On first login, the new user is taken to the What's New page and can open the Dashboard, Customers or Map from the left menu.

Applies to: SkyportCare dealer accounts

Source: Daikin One Touch Smart Thermostat training module TRC-10, p. 18-21. Written in our own words; check the manual for your exact model.

Mobile app account setup

Heat pump · Daikin One Touch

Account setup takes five steps. You need a mobile device, a Daikin One Touch thermostat connected to Wi-Fi and wired to a communicating system, and a valid email address.

  1. Download the SkyportHome app from the iOS or Android app store.
  2. Tap Create Account at the bottom right of the login screen.
  3. Read the terms, privacy statement and notices, then fill in name, valid email and password.
  4. Select Next.
  5. Open the email account and enter the six-digit welcome code in the app to confirm the account.
  6. Add the thermostat location, either by GPS or manually.
  7. Connect the app to the thermostat.

Applies to: Daikin One Touch smart thermostat with SkyportHome app

Source: Daikin One Touch Smart Thermostat training module TRC-10, p. 66-68. Written in our own words; check the manual for your exact model.

Pre start-up checklist for unitary inverter

Heat pump · DX6VS, DZ6VS

Checklist to complete before start-up. Check each item as completed and keep the form in the job file.

  1. Remove all packaging material and shipping brackets per the installation instructions.
  2. Verify the job site voltage matches the unit serial plate.
  3. Verify the condensate connection is installed per the instructions.
  4. Verify proper clearances for safety, service, maintenance and operation.
  5. Verify weatherproofing of all ductwork, roof curbs and electrical connections.
  6. Check the line set for leaks.
  7. Verify gas pressure to the unit is within the range on the serial plate.
  8. Check that all fan blades and wheels are secure.
  9. Check refrigerant piping for rubbing and leaks, and repair if needed.
  10. Check that unit wiring does not touch refrigerant piping or sharp metal edges.
  11. Check all electrical connections and terminals and tighten as needed.
  12. Verify the outdoor unit has been energized for 2 hours.
  13. Verify all accessories are installed and operating correctly.
  14. Check filters and replace if necessary.
  15. Verify a Daikin approved communicating thermostat is installed. It is the only approved thermostat for the unitary inverter unit.

Applies to: Unitary inverter systems

Source: Daikin DX6VS/DZ6VS installation & service reference, p. 58. Written in our own words; check the manual for your exact model.

Pre-commissioning and charging precautions

Heat pump · Mega-Q

Key cautions from the commissioning and charging sections.

  1. Do not run test operation while working on connected units, because all connected units start.
  2. Keep fingers and objects out of fan inlets and outlets. Do not remove the fan guard.
  3. Do not use gauge manifolds, charge hoses or leak detectors made for conventional refrigerants on R410A.
  4. Tighten the charge hose by hand only. Replace a seal if it leaks when hand tightened.
  5. Do not charge until field wiring and leak test are complete.
  6. Do not charge more than the specified amount to avoid compressor damage.
  7. Use protective gloves and glasses when charging. The fan can keep spinning after shutdown.

Applies to: Mega-Q installation and commissioning

Source: Mega-Q installation manual, p. 29, 31, 33. Written in our own words; check the manual for your exact model.

Reassembly checks for outdoor unit components

Heat pump · DX6VS / DZ6VS

Points to check before closing the unit.

  1. Align the insulation tube slit opposite the suction pipe thermistor.
  2. Do not mix the refrigerant cooling pipe screws with the other screws.
  3. Replace the grease on the cooling pipe and check the coating limits.
  4. Install the OL so the retainer hooks sit in the fixture square holes (lower hooks first, then upper).
  5. Keep the compressor lead wires on the right U/V/W terminals for the model.

Applies to: Outdoor units 3.5 to 5.0 ton

Source: Daikin SiUS612209EB service instructions, p. 112, 116, 119, 120. Written in our own words; check the manual for your exact model.

Route the fan motor and compressor lead wires on reassembly

Heat pump · DX6VS / DZ6VS inverter outdoor units

Correct lead routing prevents malfunction and tension on the compressor leads.

  1. Clamp the compressor lead wires about 20 to 50 mm (13/16 to 2 inch) from the end of the fan motor lead protective tube on 1.5/2.0 ton models.
  2. Make sure the compressor lead wires are not under tension.
  3. Bend the fan motor stand claws and fix the fan motor lead wire in place.
  4. Pass the fan motor lead through the hole in the stand on 2.5/3.0 ton models.
  5. Keep the fan motor lead wire downward with no slack.

Applies to: 1.5 to 3.0 ton HP and AC outdoor units

Source: Daikin SiUS612209EB service instructions, p. 84, 87. Written in our own words; check the manual for your exact model.

Service reminders

Heat pump · Daikin One Touch

The number of reminders depends on the installed equipment and accessories. After equipment is added, a service reminder of 1 to 24 months can be chosen to suit that equipment.

  1. Confirm the equipment and accessories have been added.
  2. Select a service reminder interval from 1 to 24 months.

Applies to: Daikin One Touch thermostat, full set-up

Source: Daikin One Touch installation guide, p. 53. Written in our own words; check the manual for your exact model.

Set heat pump and auxiliary heat outdoor lockout temperatures

Heat pump · DX6VS, DZ6VS

Set the outdoor temperature lockouts during the first thermostat setup. Heat pump lockout turns the compressor off when it is cold outside and switches heating to auxiliary or secondary heat. Aux heat lockout turns the auxiliary heat off when outdoor temperature is above its setpoint.

  1. Set the heat pump lockout temperature during initial thermostat setup.
  2. Set the aux heat lockout temperature during initial thermostat setup.

Applies to: Heat pump systems with auxiliary or secondary heat

Source: Installation instructions outdoor unit DX6VS/DZ6VS, p. 32. Written in our own words; check the manual for your exact model.

Set-up screens follow the equipment model numbers

Heat pump · Daikin One Touch

The thermostat fills the set-up screens from a database of device configuration settings matched to the model numbers of the equipment. Random access to any setting is allowed, entered settings are remembered, and the installer can stop and restart the process at any time.

Applies to: Daikin One Touch smart thermostat, full set-up

Source: Daikin One Touch installation training TRC-10, p. 34. Written in our own words; check the manual for your exact model.

SkyportCare app Quality Install

Heat pump · Daikin One Touch

The app lets a technician edit profile settings, run commissioning tests and verify charge.

  1. Download the SkyportCare app from the app store.
  2. Create an account and tie it to the dealer account registered with SkyportCare.
  3. Use Quality Install in the app for profile changes, commissioning tests and charge verification.

Applies to: SkyportCare mobile app

Source: Daikin One Touch Smart Thermostat training module TRC-10, p. 22. Written in our own words; check the manual for your exact model.

Start-up readings to record

Heat pump · DX6VS, DZ6VS

Values to fill in during start-up and save in the job file. Blank fields on the form are for the technician to complete.

  1. Record supply voltage L1-L2.
  2. Record return air, supply air and total external static pressure in inches W.C., and airflow in CFM.
  3. Record outdoor air, return air and cooling supply air temperatures in DB and WB.
  4. Record suction line pressure in PSIG and temperature in °F.
  5. Record superheat / subcooling in °F.
  6. Record liquid line pressure in PSIG and temperature in °F.

Applies to: Unitary inverter start-up record

Source: Daikin DX6VS/DZ6VS installation & service reference, p. 59. Written in our own words; check the manual for your exact model.

Step 5 preferences

Heat pump · Daikin One Touch

Four preference groups are available to tune system performance: cool/heat, house settings, dealer information and reminders. Changing preferences is optional, but reminders and dealer contact information should be entered.

  1. Review cool/heat preferences and house settings as needed.
  2. Enter dealer information.
  3. Set up reminders.

Applies to: Daikin One Touch thermostat, full set-up step 5

Source: Daikin One Touch installation guide, p. 51. Written in our own words; check the manual for your exact model.

Wi-Fi is required for aux heat lockout logic

Heat pump · P1P2, S21

The heat pump lockout and aux heat lockout use ambient temperature data. That data reaches the Daikin One+ through the weather service, so the Wi-Fi connection must be working for aux heat logic to run.

  1. Confirm the Daikin One+ is connected to Wi-Fi before commissioning aux heat lockouts.

Applies to: Daikin One+ with heat pump primary setup

Source: Aux heater installation and setup instructions, p. 3. Written in our own words; check the manual for your exact model.

Wi-Fi requirements for set-up

Heat pump · Daikin One Touch

The wireless router must be password protected. The thermostat works with 5 GHz routers that also support 2.4 GHz. Once Wi-Fi is connected, the thermostat can check and update its software automatically.

  1. Confirm the router is password protected before starting Step 1.
  2. Confirm the router supports 2.4 GHz as well as 5 GHz.
  3. Select the home Wi-Fi network from the search list.

Applies to: Daikin One Touch smart thermostat, Step 1 Communication

Source: Daikin One Touch installation training TRC-10, p. 37. Written in our own words; check the manual for your exact model.

Connect wireless LAN adapter directly to smart device

Mini-split · FTXM-W/V

Direct mode makes the adapter act as an access point. The smart device joins the adapter's network, then the app moves the adapter onto the home network.

  1. With operation stopped, press and hold the menu button for 5 seconds.
  2. Press up or down and select the direct connection menu number.
  3. Press the select button. The adapter lamp blinks for 1 second.
  4. On the smart device, select the SSID printed on the unit or in the accessory set and enter the password.
  5. Confirm the adapter lamp lights, then press return to go to the default screen.
  6. Open the Daikin Comfort Control App and follow the app steps to connect to the home network.
  7. Connect the smart device to the home network.

Applies to: Wireless LAN connection adapter, FTXM-W/V

Source: Daikin FTXM-W/V service manual, p. 68. Written in our own words; check the manual for your exact model.

Connect wireless LAN adapter to home network using WPS

Mini-split · FTXM-W/V

Used when the home router has a WPS button. The router button must be pressed within about one minute of the adapter entering pairing mode.

  1. With operation stopped, press and hold the menu button for 5 seconds.
  2. Press up or down and select the WPS menu number.
  3. Press the select button. The adapter lamp blinks faster.
  4. Press the WPS button on the router within about 1 minute.
  5. Confirm the adapter lamp lights, then press return to go to the default screen.
  6. If the lamp does not light, repeat the steps. If it still fails, reset the connection to factory default.

Applies to: Wireless LAN connection adapter, FTXM-W/V

Source: Daikin FTXM-W/V service manual, p. 67. Written in our own words; check the manual for your exact model.

Dealer edit and commissioning screens

Mini-split · Daikin ONE+

Dealer edit leads into the commissioning screens and is reached through the dealer access menu after the 4-digit code.

  1. Enter the 4-digit code for the dealer access level.
  2. Select dealer edit to enter the commissioning screens.

Applies to: Daikin ONE+ commissioning

Source: Daikin ONE+ and ONE Touch homeowner settings menu outline, p. 3. Written in our own words; check the manual for your exact model.

Charge R410A as liquid only

Water heater · Mega-Q

R410A is a blended refrigerant. Charging it as a gas changes its composition and the system will not run correctly.

  1. Charge the additional R410A in its liquid state.
  2. Do not use a charging cylinder, as it can degrade the refrigerant.

Applies to: Mega-Q R410A circuit

Source: Daikin Mega-Q installation manual, p. 3, 6. Written in our own words; check the manual for your exact model.

Connect water temperature sensors to tank control board

Water heater · Mega-Q

Connect the three relay wire harnesses (accessory) to the tank control board. Match each harness to its board connector by color, and check the harness is at the correct sensor position.

  1. Connect relay harness for sensor 1 (R1T, white, X13A) to the board.
  2. Connect relay harness for sensor 2 (R2T, yellow, X17A) to the board.
  3. Connect relay harness for sensor 3 (R3T, red, X18A) to the board.
  4. Pass the relay harnesses through the wire clips on the board.
  5. Secure the harness clamp (accessory) so no external force reaches the connectors.
  6. When closing the tank control board cover, make sure no wiring is pinched.

Applies to: Mega-Q hot water generation system, tank control board

Source: Daikin Mega-Q installation manual, p. 64 of 68. Written in our own words; check the manual for your exact model.

Install sensors in hot water storage tank

Water heater · Mega-Q

Sensors are field-installed in the storage tank and their relay harnesses run back through conduit to the tank control board.

  1. Connect each relay harness to its water temperature sensor (3 places), matching the identification numbers.
  2. Put the harness connector part into the storage box.
  3. Run the wiring conduit from the tank control board to the sensor storage box.
  4. Keep the conduit layout as shown in the manual.

Applies to: Mega-Q hot water generation system, hot water storage tank

Source: Daikin Mega-Q installation manual, p. 65 of 68. Written in our own words; check the manual for your exact model.

Keep low voltage wiring apart from power wiring

Water heater · Mega-Q

Low voltage wiring (remote controller, between units) must not run close to power wiring or it can cause interference, malfunction or breakage.

  1. Keep low voltage and power wiring at least 2 in (50 mm) apart.
  2. Connect power wiring to the power terminal block and secure it per the power wiring section.
  3. Secure transmission wiring per the transmission wiring section.
  4. Clamp wiring so it does not touch piping and shape it so the control box cover can close firmly.

Applies to: Mega-Q

Source: Daikin Mega-Q installation manual, p. 24. Written in our own words; check the manual for your exact model.

Keep wiring and controllers clear of interference

Water heater · Mega-Q

Power and transmission wires for the unit and tank control board can cause picture or radio noise if run close to electronics. Wireless remote controllers may also have a shorter range near fluorescent lamps.

  1. Keep power and transmission wiring at least 10 ft (3 m) from televisions and radios.
  2. Keep the wireless remote at least 3.5 ft (1 m) from TVs, radios and stereos.
  3. Place the unit away from fluorescent lamps where possible.

Applies to: Mega-Q wiring and controls

Source: Daikin Mega-Q installation manual, p. 3, 4. Written in our own words; check the manual for your exact model.

Open the sliding plate in hot-climate regions

Water heater · Mega-Q

In hot regions the sliding plate on the heat source unit must be set to OPEN to reduce temperature rise in the main control box. Regions listed in the manual include CA, NV, AZ, NM, OK, TX, AR, LA, MS, AL, TN, GA, NC, SC, FL and Latin America. Failure to do this can cause early component failure.

  1. Remove the left screw and loosen the right screw.
  2. Slide the sliding plate to the right and set the arrow to OPEN.
  3. Reinstall the left screw and tighten both the left and right screws.

Applies to: Heat source unit in listed hot-climate regions

Source: Daikin Mega-Q installation manual, p. 10. Written in our own words; check the manual for your exact model.

Operate the stop valve

Water heater · Mega-Q

Do not open the stop valve until all checks in the checking equipment and installation status section are done. Leaving it open with power off can let refrigerant condense in the compressor. Use a dedicated tool. The 1/2 in. liquid valve is not back-seal type, so do not force it. The 1 in. gas valve is front and back seal type.

  1. Remove the stop valve cover.
  2. To open: insert a hexagon wrench and turn counterclockwise until the shaft stops (1/2 in.) or until the shaft stops and the designated torque is reached (1 in.).
  3. To close: turn clockwise until the shaft stops at the designated torque.
  4. Tighten the stop valve cover to the designated torque.
  5. Check for refrigerant leaks after tightening the cover.
  6. When working on the service port, use a charge hose with a valve depressor pin because it is a Schrader valve. Tighten the port cover and check for leaks.

Applies to: Heat source unit stop valves (RXHWQ120MQTJA)

Source: Daikin Mega-Q installation manual, p. 51. Written in our own words; check the manual for your exact model.

Plan for tank warm-up time

Water heater · Mega-Q

The storage tank takes time to reach its set temperature.

  1. Start the system in advance using schedule operation when hot water is needed at a set time.

Applies to: Mega-Q tank system

Source: Daikin Mega-Q installation manual, p. 4. Written in our own words; check the manual for your exact model.

Other

Everything else worth knowing at the appliance.

Add and remove equipment

Air conditioner · Daikin One+, Touch thermostat

The equipment list lets you add accessories and remove equipment. Most accessory types can be added only once. One+ thermostats can add up to 8 remote sensors.

  1. Open the equipment setup list and select Add Equipment.
  2. Choose the accessory type, such as humidifier, dehumidifier, aux heat source, UV bulb, HEPA filter, or electronic filter.
  3. To remove equipment, select it and confirm with Continue, or Cancel to keep it.

Applies to: All unitary equipment; one of each type except remote sensors

Source: Daikin One+ commissioning menu outline v3.9, p. 3. Written in our own words; check the manual for your exact model.

Air filter cleaning interval

Air conditioner · FTXM WVJU9

Clogged air filters reduce efficiency and waste energy. Clean the filters about every 2 weeks. The manual's care section is on page 42.

  1. Open the front cover.
  2. Clean the air filters (full cleaning steps are in the Care section, p. 42).

Applies to: Indoor unit, all FTXM WVJU9 models

Source: Daikin Room Air Conditioner operation manual, p. 14. Written in our own words; check the manual for your exact model.

Check firmware version and update

Air conditioner · Daikin One+, Touch thermostat

The setup options menu shows the installed firmware version and has a check for update option.

  1. Open setup options.
  2. Read the firmware version number.
  3. Select check for update if a newer version is needed.

Applies to: Daikin One+ and Touch thermostats

Source: Daikin One+ commissioning menu outline v3.9, p. 1. Written in our own words; check the manual for your exact model.

Choose coil transformer supply voltage

Air conditioner · CAPE / CHPE EEV cased coils

The correct supply voltage for the coil transformer depends on the power supply to the gas furnace or blower unit.

  1. Check the supply voltage to the gas furnace or blower unit.
  2. Select the matching transformer supply voltage on the cased coil.

Applies to: EEV cased coil transformer

Source: Daikin SiUS612209EB service instructions, p. 80. Written in our own words; check the manual for your exact model.

Choosing the mounting location by unit type

Air conditioner · Daikin One+ Translation Adaptor

Wall-mounted units: mount inside the piping chase if the refrigerant piping is on the right and the chase is free, otherwise mount outside the unit. Ducted and air handler, ceiling cassette and ceiling suspended units can use tape on the side or top, or be mounted in a nearby surface. Floor-mounted units use the side of the unit. In all cases, keep the adaptor close to the indoor unit electrical box.

  1. For wall units inside the chase, use the largest free space and face the high-voltage side toward the indoor unit electrical box.
  2. For wall units mounted inside the chase, the front cover is optional; if the adaptor is inside the unit, no cover is needed.
  3. For wall units with left-side piping occupying the chase, mount the adaptor outside the unit and minimize the view of the adaptor and cables.

Applies to: Wall-mounted, ducted, cassette, ceiling suspended and floor-mounted indoor units

Source: Daikin One+ Translation Adaptor installation instructions, p. 3. Written in our own words; check the manual for your exact model.

Combine ON and OFF timers

Air conditioner · FTXM

Example from the manual: unit running at 23:00, OFF TIMER at 0:00 stops it, ON TIMER at 14:00 restarts it. When OFF TIMER is set, NIGHT SET mode adjusts the temperature during sleep.

  1. Set the OFF TIMER and the ON TIMER using the 24 hour method.
  2. Confirm both timers appear on the LCD.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin room air conditioner operation manual, p. 27. Written in our own words; check the manual for your exact model.

COMFORT AIRFLOW and upward/downward flap conflict

Air conditioner · FTXM

If an upward or downward flap direction is selected by hand, COMFORT AIRFLOW is cancelled. The function that was pressed last takes priority. COMFORT AIRFLOW cannot be combined with POWERFUL.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin room air conditioner operation manual, p. 24. Written in our own words; check the manual for your exact model.

Cooling and heating airflow ON/OFF delay

Air conditioner · DX6VS, DZ6VS

Fan ON and OFF delays can be changed from normal operation through the thermostat for set durations. Refer to the indoor unit installation manual for details.

Applies to: Fan delay settings

Source: Daikin DX6VS/DZ6VS outdoor unit installation & service reference, p. 32. Written in our own words; check the manual for your exact model.

Do not use other remote controllers with the thermostat

Air conditioner · Daikin One+ Translation Adaptor

The Daikin One+ thermostat cannot work alongside any other wired or wireless remote controller. On retrofit jobs, remove all other remote controllers before installing.

  1. Remove any existing wired or wireless remote controllers from the indoor unit before installation.

Applies to: Daikin One+ Translation Adaptor with S21 or P1P2 indoor units

Source: Daikin One+ Translation Adaptor installation instructions, p. 2. Written in our own words; check the manual for your exact model.

ECONO and QUIET OUTDOOR UNIT limitations

Air conditioner · FTXM

Both modes use lower power, so cooling or heating may be less than full output. ECONO does not reduce power if the draw is already low. QUIET OUTDOOR UNIT does not reduce frequency or fan speed if they are already reduced. If the unit is stopped with the remote or indoor ON/OFF switch, the QUIET icon stays on the remote display.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin room air conditioner operation manual, p. 26. Written in our own words; check the manual for your exact model.

Energy saving temperature guidance

Air conditioner · FTXM WVJU9

Keeping the setpoint moderate saves energy. Recommended setpoints are 78-82°F (26.0-28.0°C) for cooling and 68-75°F (20.0-24.0°C) for heating. Blinds or curtains help by blocking outdoor sun and air.

Applies to: All FTXM WVJU9 models

Source: Daikin Room Air Conditioner operation manual, p. 14. Written in our own words; check the manual for your exact model.

Independent aux heater operation

Air conditioner · P1P2, S21

The aux heater runs independently of the master unit mode. It can heat automatically while the master unit is cooling, or it can be called directly with Emergency Heat.

  1. Use automatic aux heating when the master unit is cooling and aux heat is needed.
  2. Select Emergency Heat to run aux heat directly.

Applies to: P1P2 and S21 systems with aux heater

Source: Aux heater installation and setup instructions, p. 7. Written in our own words; check the manual for your exact model.

Indoor unit beep meanings

Air conditioner · FTXM

The indoor unit beeps to confirm remote signals and status changes. Use these to tell whether the unit received a command.

  1. Operation start: beep-beep.
  2. Setting change: single beep.
  3. Operation stop: long beep.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin FTXM operation manual, p. 5. Written in our own words; check the manual for your exact model.

Long non-use shutdown

Air conditioner · FTXM WVJU9

The unit draws a small amount of power even when off. For long periods out of use, such as spring or autumn, switch off the circuit breaker.

  1. Switch off the circuit breaker for the air conditioner.

Applies to: All FTXM WVJU9 models

Source: Daikin Room Air Conditioner operation manual, p. 14. Written in our own words; check the manual for your exact model.

Mixing clock and countdown timer modes

Air conditioner · FTXM

The ON and OFF timers can use different display modes at the same time, for example OFF at 3 hours from now and ON at a fixed 6:00. Changing display mode cancels the timer, so it must be set again.

  1. Set the timer in the new display mode.
  2. Confirm both timers appear on the LCD.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin room air conditioner operation manual, p. 28. Written in our own words; check the manual for your exact model.

Mounting with double-sided adhesive tape

Air conditioner · Daikin One+ Translation Adaptor

Adhesive mounting needs a clean surface and firm pressure to form a good bond. The mounting plate has a recess for the tape and is marked APPLY OPTIONAL ADHESIVE STRIP HERE on the back. On curved surfaces a thicker molding tape may be needed.

  1. Clean the mounting surface with a 50:50 mix of isopropyl alcohol and water to remove dust and oil.
  2. Apply the tape to the recess in the mounting plate.
  3. Press firmly for 30 seconds.
  4. On non-flat surfaces, use thicker molding tape such as 3M Super Strength Molding Tape 03609.

Applies to: Daikin One+ Translation Adaptor on ducted, cassette and ceiling suspended units

Source: Daikin One+ Translation Adaptor installation instructions, p. 4. Written in our own words; check the manual for your exact model.

Mounting with screws

Air conditioner · Daikin One+ Translation Adaptor

Mount the adaptor backplate to the wall with the two supplied screws. Do not screw the adaptor directly onto the indoor unit.

  1. Select a sound wall surface within reach of the indoor unit electrical box.
  2. Fix the backplate to the wall with the two screws provided.
  3. Attach the adaptor to the backplate.

Applies to: Daikin One+ Translation Adaptor

Source: Daikin One+ Translation Adaptor installation instructions, p. 4. Written in our own words; check the manual for your exact model.

Refrigerant type R32

Air conditioner · FTXM

This unit is charged with R32 refrigerant. Refrigerant leaks and repairs must go through the dealer or a qualified service person.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin FTXM operation manual, p. 3. Written in our own words; check the manual for your exact model.

Remote controller range and aiming

Air conditioner · FTXM WVJU9

Point the remote transmitter at the indoor unit. Curtains or other obstructions between the remote and the unit can stop it from working. Maximum transmission distance is about 23 ft (7 m).

Applies to: Remote controller, all FTXM WVJU9 models

Source: Daikin Room Air Conditioner operation manual, p. 8. Written in our own words; check the manual for your exact model.

Remote controller signal range and line of sight

Air conditioner · FTXM

The remote controller works up to about 23 ft (7 m) away. Anything between the remote and the indoor unit, such as a curtain, can stop the unit from responding.

  1. Aim the remote controller at the indoor unit.
  2. Clear any obstruction between the remote and the indoor unit.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin FTXM operation manual, p. 7. Written in our own words; check the manual for your exact model.

Remote display behaviour with QUIET OUTDOOR UNIT

Air conditioner · FTXM

If QUIET OUTDOOR UNIT was on, its icon stays on the remote after the unit is stopped from the remote or the indoor ON/OFF switch. This is normal.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin room air conditioner operation manual, p. 26. Written in our own words; check the manual for your exact model.

Remove compressor and sound blankets (air conditioner, 1.5 to 3.0 ton)

Air conditioner · DX6VS, DZ6VS

Teardown order for the sound blankets and compressor on cooling-only (AC) models. The steps match the heat pump procedure.

  1. Remove the 2 screws and take off the partition plate. The upper screw is a truss head tapping screw or a hex head screw (M4 x 12).
  2. On reassembly, hook the bottom frame into the slit of the partition plate.
  3. Remove the sound blanket (outer top).
  4. On reassembly, the full edge of the outer top blanket must sit inside the outer body blanket and must not rise above it.
  5. Remove the sound blanket (outer body).
  6. Remove the sound blanket (inner top).
  7. Remove the sound blanket (inner body).
  8. Remove the terminal cover.
  9. Disconnect the compressor lead wires (yellow V, red U, blue W) from the protection bushing.
  10. Remove the OL (overload) from the compressor.
  11. On reassembly, hook the retainer lower hooks into the square holes of the fixture first, then push the upper hooks until they latch. Pass the OL lead wire through the harness route.
  12. Before brazing, remove all putty, the terminal cover and any other plastic parts that could burn. Put a protective sheet or steel plate under the work so the flame cannot reach the surroundings.
  13. Heat the brazed compressor piping joints and disconnect the compressor piping.

Applies to: DX6VS/DZ6VS air conditioner outdoor units, 1.5 to 3.0 ton, AC only

Source: Daikin DX6VS/DZ6VS service instructions, p. 100-103. Written in our own words; check the manual for your exact model.

Replace remote controller batteries

Air conditioner · FTXM WVJU9

Use two AAA LR03 alkaline batteries. Replace both at the same time, usually about once a year. Batteries supplied with the remote are only for initial use and may last less than a year.

  1. Slide the remote's front cover off.
  2. Insert 2 new AAA LR03 (alkaline) batteries, matching + and - marks.
  3. Put the front cover back on.

Applies to: Remote controller ARC466A70 and ARC466A71

Source: Daikin Room Air Conditioner operation manual, p. 10. Written in our own words; check the manual for your exact model.

Screen cleaning mode

Air conditioner · ONE+, One Touch

Screen cleaning disables the touch screen for 30 seconds so the display can be wiped.

  1. Open the screen cleaning option.
  2. Wipe the screen during the 30 second window.

Applies to: Touch screen cleaning

Source: daikin-one-touch-unitary-homeowner-settings.pdf, p. 1. Written in our own words; check the manual for your exact model.

Start and stop operation

Air conditioner · FTXM WVJU9

Choose the operation mode first, then start the unit. The unit keeps the last mode for next time. The OPERATION lamp lights green when running.

  1. Press the MODE selector button until the wanted mode shows (AUTO, DRY, COOL, HEAT or FAN).
  2. Press the ON/OFF button to start. The OPERATION lamp lights green.
  3. Press the ON/OFF button again to stop. The OPERATION lamp goes off.

Applies to: Remote controller, all FTXM WVJU9 models

Source: Daikin Room Air Conditioner operation manual, p. 13. Written in our own words; check the manual for your exact model.

WEEKLY TIMER and ON/OFF TIMER conflict

Air conditioner · FTXM

WEEKLY TIMER and ON/OFF TIMER cannot run together. If an ON/OFF timer is set while WEEKLY TIMER is active, the ON/OFF timer takes priority and WEEKLY TIMER goes to standby. WEEKLY TIMER becomes active again when the ON/OFF timer expires.

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin room air conditioner operation manual, p. 32. Written in our own words; check the manual for your exact model.

WEEKLY TIMER capacity and use

Air conditioner · FTXM

Up to 4 reservations per day and 28 per week. Setting all ON entries keeps mode and temperature changing through the day. Setting only OFF entries acts as an auto shut-off if the unit is left running.

  1. Set the clock and day of the week before programming.
  2. Use copy mode to repeat a day's settings on other days (see p. 32).

Applies to: FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9, FTXM24WVJU9

Source: Daikin room air conditioner operation manual, p. 29. Written in our own words; check the manual for your exact model.

Wireless LAN adapter button

Air conditioner · FTXM WVJU9

Holding the Wireless LAN button on the remote for 5 seconds starts the wireless LAN connection. The orange adapter lamp on the unit lights when connected to a router. The adapter can be turned off if the unit is accessed illegally. Do not use near a microwave oven.

  1. Hold the Wireless LAN button for 5 seconds to start connection.
  2. Check the orange wireless LAN lamp lights when connected to the router.

Applies to: Models with wireless LAN connection adapter

Source: Daikin Room Air Conditioner operation manual, p. 8. Written in our own words; check the manual for your exact model.

Wiring rules for the adaptor

Air conditioner · Daikin One+ Translation Adaptor

Only one communication terminal may be used per indoor unit. Never run S21 and P1P2 at the same time. Do not splice wires, and make sure all connectors are secure, since loose connections can cause poor communication or malfunction.

  1. Pick S21 or P1P2 based on the indoor unit model; use only one.
  2. Do not splice any wires.
  3. Push all connectors in fully and check they are secure.

Applies to: All Daikin One+ Translation Adaptor installations

Source: Daikin One+ Translation Adaptor installation instructions, p. 1, p. 6. Written in our own words; check the manual for your exact model.

Check selector switch DS1 to DS6 positions

Air handler · DFVE EEV air handler, DV**FEC EEV air handler, CAPE / CHPE EEV cased coil

The positions of selector switches DS1 through DS6 show the factory setting. Compare them with the factory setting before changing anything.

  1. Locate selector switches DS1 to DS6 on the integrated control.
  2. Record their positions before making any change.
  3. Compare the positions with the factory setting in the manual.

Applies to: EEV indoor units with integrated control

Source: Daikin SiUS612209EB service instructions, p. 80. Written in our own words; check the manual for your exact model.

Check selector switch DS1-DS6 positions

Air handler · DV / DFVE EEV air handlers

The positions of selector switches DS1 to DS6 show the factory setting for the board.

  1. Compare DS1 to DS6 on the control board with the factory settings in the manual before changing anything.

Applies to: EEV air handler integrated control

Source: Daikin SiUS612209EB service instructions, p. 79. Written in our own words; check the manual for your exact model.

Network status LEDs and LEARN button on the integrated control

Air handler · DV**FEC, DFVE**, CAPE(A)*, CHPE*

The red status LED shows network status and the green RX LED flashes with network traffic. The LEARN button resets the network.

  1. Check the red status LED for network status.
  2. Check the green RX LED for network traffic.
  3. Press the LEARN button to reset the network.

Applies to: Integrated control, EEV indoor units

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 80. Written in our own words; check the manual for your exact model.

Read the 2-digit display state and airflow

Air handler · DV**FEC / DFVE**, CAPE(A)* / CHPE*

On a normal indoor unit the display cycles through the current state, any error code, and the estimated airflow. Airflow is shown as an upper and lower 2-digit pair. Example: 1240 CFM shows "A", then "12", then "40". The EEV cased coil does not report airflow.

  1. Read the state code first (for example FC, FH or dF).
  2. If an error exists it is shown after the state in normal mode.
  3. Airflow is shown last as the CFM pair.

Applies to: EEV indoor units with 2-digit display

Source: SiUS612209EA service instructions, p. 26-27. Written in our own words; check the manual for your exact model.

Read the network LEDs and reset the network

Air handler · DV / DFVE EEV air handlers

The red status LED shows network status and the green RX LED shows network traffic. The learn button resets the network.

  1. Check the red STATUS LED for network status.
  2. Check that the green RX LED flashes to confirm network traffic.
  3. If the network needs a reset, press the LEARN button.

Applies to: EEV air handler and EEV cased coil control boards

Source: Daikin SiUS612209EB service instructions, p. 79-80. Written in our own words; check the manual for your exact model.

Replacement wire rating

Air handler · DV / DFVE EEV air handlers, CAPE / CHPE EEV cased coils

Any original wire that must be replaced needs the correct rating and material.

  1. Use copper conductors only.
  2. Use wire rated at least 105°C.
  3. Use only manufacturer-specified replacement parts.

Applies to: Field wiring repairs on EEV air handlers and cased coils

Source: Daikin SiUS612209EB service instructions, p. 79-80. Written in our own words; check the manual for your exact model.

Selector switches DS1 to DS6 on the integrated control

Air handler · DV**FEC, DFVE**, CAPE(A)*, CHPE*

The positions of selector switches DS1 through DS6 show the factory setting for the control. Compare the switch positions against the factory settings shown on the wiring diagram.

Applies to: Integrated control

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 80. Written in our own words; check the manual for your exact model.

Selector switches DS1-DS6 show factory settings

Air handler · DV**FEC, DFVE**

The positions of selector switches DS1 to DS6 show the factory setting. Record them before changing anything.

  1. Note the position of DS1 to DS6 before making any change.
  2. Do not assume a changed position is a fault; check the factory setting table in the manual.

Applies to: EEV air handler and EEV cased coil control boards

Source: Daikin SiUS612209EA service instructions, p. 79-80. Written in our own words; check the manual for your exact model.

Set transformer tap for 208 V operation

Air handler · DV / DFVE EEV air handlers

For 208 VAC supply, the red transformer wires go on the 208 V terminal of the 2-transformer set (TR1/TR2).

  1. For 208 VAC operation, move the red wires to the 208 V terminal on TR1 and TR2.
  2. Make sure the supply matches the terminal you used.

Applies to: EEV air handler with TR1/TR2 transformers

Source: Daikin SiUS612209EB service instructions, p. 79. Written in our own words; check the manual for your exact model.

T on/T off control method

Air handler · Daikin One+ Unitary Aux Heater

T on and T off is an alternative control method where the main AC or heat pump controls the aux heat source using its PI control algorithm. It is the only control option for AC-only outdoor units. If the indoor unit is a gas furnace or an air handler with a heater strip, those heat sources are controlled around the heat setpoint by the demand-based algorithm, and the aux heat source is controlled independently.

  1. Use T on/T off control when the main equipment should run the aux heat source.
  2. For AC-only outdoor units, T on/T off is the only available control option.
  3. With a gas furnace or heater-strip air handler, expect the aux source to run on its own control.

Applies to: Aux heat control with T on/T off

Source: Unitary Aux Heater installation and setup, p. 5. Written in our own words; check the manual for your exact model.

Where to look for faults on a two-piece cased coil

Air handler · DV**FEC / DFVE**, CAPE(A)* / CHPE*

On an EEV cased coil the displayed active errors apply only to the coil. Gas furnace and modular blower faults must be read on their own control boards, using their service manuals.

  1. Check the active codes on the control board of each unit when there is a problem.
  2. Use the gas furnace or modular blower service manual for its troubleshooting.

Applies to: EEV cased coil with gas furnace or modular blower

Source: SiUS612209EA service instructions, p. 25. Written in our own words; check the manual for your exact model.

Wire replacement and grounding requirements

Air handler · DV**FEC, DFVE**, CAPE(A)*, CHPE*

Replacement wiring must meet the stated temperature and material rules, and the unit must be grounded.

  1. Use copper conductors only when replacing any original wire.
  2. Use wire rated at least 105 °C.
  3. Permanently ground the unit per NEC and local codes.
  4. Use only manufacturer-specified replacement parts.

Applies to: EEV air handler and EEV cased coil

Source: Daikin SiUS612209EA service instructions, p. 79-80. Written in our own words; check the manual for your exact model.

Wiring requirements for field and replacement wire

Air handler · DV**FEC, DFVE**, CAPE(A)*, CHPE*

Follow these rules when replacing original wiring or making field connections on the EEV cased coil.

  1. Replace any original wire with wiring rated at least 105°C.
  2. Use copper conductors only.
  3. Ground the unit permanently per N.E.C. and local codes.
  4. Use N.E.C. Class 2 wire for low voltage.
  5. Select the transformer supply tap to match the power supply voltage to the gas furnace or blower unit.
  6. Use manufacturer-specified replacement parts when servicing.

Applies to: EEV cased coil and air handler wiring, including fuses F1U and F2U and coil transformer TR1

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 80. Written in our own words; check the manual for your exact model.

Adjust setpoints

Furnace · Daikin One+

Setpoints can be changed with the arrow icons, by turning the dial, or by sliding the setpoints to the desired temperature.

  1. Tap the arrow icons, turn the dial, or slide the setpoint to the wanted temperature.

Applies to: Daikin One+ thermostat, normal mode

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 47. Written in our own words; check the manual for your exact model.

Air quality screen and One Clean

Furnace · Daikin One+

The air quality screen shows indoor air quality, outdoor air quality and weather when the unit is online and paired with the app. If no air quality sensors are installed, indoor air quality is estimated from filter life and humidity. One Clean runs the fan at high speed for three hours to circulate and filter the indoor air.

  1. Open the air quality screen to view indoor and outdoor air quality.
  2. Without air quality sensors, check filter life and humidity values, which are used for the indoor estimate.
  3. Select indoor air quality to reach the clean and air quality history.
  4. Start One Clean to run the fan on high speed for three hours.

Applies to: Daikin One+ air quality feature

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 50. Written in our own words; check the manual for your exact model.

Edit the schedule

Furnace · Daikin One+

The schedule shows 7 days, one day at a time, with 24 hours on screen. Schedule editing is enabled from the drop-down menu or by swiping. Copy and paste can be used to speed up scheduling. Schedule edits must be saved before leaving the mode.

  1. Select the day from the drop-down menu or swipe to it.
  2. Enable schedule editing.
  3. Make changes, using copy and paste if needed.
  4. Save edits before exiting the schedule.

Applies to: Daikin One+ thermostat, schedule

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 48. Written in our own words; check the manual for your exact model.

Normal mode navigation and dial use

Furnace · Daikin One+

In normal mode, navigation is done by tapping icons or turning the analog dial. The dial adjusts temperature only. Pressing the dial returns to the home screen.

  1. Tap icons to navigate.
  2. Turn the analog dial to adjust temperature only.
  3. Press the dial to return to the home screen.

Applies to: Daikin One+ thermostat, normal mode

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 46. Written in our own words; check the manual for your exact model.

Physical dial and home button

Furnace · Daikin One+

The thermostat has a physical dial on the right for manual setpoint changes. Pressing the centre of the dial in normal mode returns to the primary screen from any other screen. The touch screen on the left is used for navigation by tapping icons.

Applies to: Daikin One+ Smart Thermostat

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 6. Written in our own words; check the manual for your exact model.

Quick reference cards

Furnace · Daikin One+

Quick reference cards packed with the thermostat answer common questions during installation and commissioning. Each card has a barcode that links to a web page on its topic.

  1. Check the quick reference cards in the thermostat box when a question comes up during install or commissioning.

Applies to: Daikin One+ Smart Thermostat

Source: Daikin One+ installation & commissioning, p. 9. Written in our own words; check the manual for your exact model.

T on / T off aux heat control method

Furnace · Daikin One+

T on / T off is an alternative control method where the main AC or heat pump controls the aux heat source using its PI control algorithm. It is the only control option for AC-only outdoor units. If the indoor unit is a gas furnace or an air handler with a heater strip, those heat sources are controlled around the heat setpoint by the demand-based algorithm, and the aux source is controlled independently.

  1. Use T on / T off control for AC-only outdoor units.
  2. Use demand-based control for gas furnace or heater-strip air handler indoor units.

Applies to: Daikin One+ aux heat control

Source: Daikin One+ installation & commissioning, p. 30. Written in our own words; check the manual for your exact model.

Thermostat message types and priority

Furnace · Daikin One+

The thermostat shows messages that confirm and inform about selections made during set-up and operation. There are four types: status, alerts, reminders and prompts, and learn more/tips. Alerts take priority over all other messages.

Applies to: Daikin One+ Smart Thermostat

Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 8. Written in our own words; check the manual for your exact model.

Air purifying only

General · Daikin Humidifying Air Purifier

Use this when you do not want humidifying. The unit remembers its last operation, so it may restart humidifying on its own after a power loss.

  1. Press the air purifying button to start; press again to turn off.
  2. If humidifying was running, press the humidifying button until the humidifier lamp turns off.
  3. Discard the water in the water tank and humidifying tray before running air purifying only.

Applies to: MCKB70YSAU

Source: Daikin MCKB70YSAU installation & operation manual, p. 18. Written in our own words; check the manual for your exact model.

Air quality screen and One Clean

General · Daikin One+ S21

The air quality screen shows indoor air quality, outdoor air quality and weather when the unit is online and paired with the app. Without air quality sensors, indoor air quality is estimated from filter life and humidity. One Clean runs the fan on high speed for three hours to circulate and filter the air. Its history is accessible from the indoor air quality selection.

  1. Open the air quality screen to view indoor and outdoor air quality.
  2. To run One Clean, select it from the indoor air quality options.
  3. One Clean runs the fan at high speed for three hours.

Applies to: Daikin One+ S21 thermostat, systems with or without air quality sensors

Source: Daikin One+ installation & commissioning (S21) manual, p. 44. Written in our own words; check the manual for your exact model.

Airflow clearance and blockage

General · MCB50

Do not block the air inlets or outlet, and do not aim outflow directly at a wall, furniture or curtains. Do not put fingers or objects into the inlets or outlet, and do not pour water on the unit.

  1. Keep the air inlets and outlet clear of laundry, cloth and curtains.
  2. Position the unit so outflow does not hit walls or furniture directly.
  3. Do not insert objects into the air inlets or outlet.

Applies to: MCB50YSAU

Source: Daikin air purifier installation & operation manual, p. 5-6. Written in our own words; check the manual for your exact model.

Carbon filter unit care

General · Air Purifier

The carbon filter cannot be washed with water.

  1. Vacuum the carbon filter unit to remove dust.
  2. If odor persists, air it out in a shady spot for about 1 day.
  3. Replace the carbon filter if odor or dirt remains after cleaning.
  4. Do not wash it with water or rub the surface.

Applies to: MCB50YSAU

Source: Daikin MCB50YSAU installation & operation manual, p. 18. Written in our own words; check the manual for your exact model.

Carbon monoxide risk: keep the cabinet door installed

General · Daikin One Premium Air Cleaner

Operating without the cabinet door can draw exhaust fumes into occupied spaces.

  1. Do not run the air cleaner without the cabinet door in place.
  2. Confirm the door is fully seated after every filter change.

Applies to: DV1-15 series

Source: Daikin One Premium Air Cleaner installation & operation manual, p. 2. Written in our own words; check the manual for your exact model.

Change the airflow rate

General · Daikin Humidifying Air Purifier

Each press during operation cycles through the airflow levels. Quiet is for sleep hours and gives less deodorizing. Turbo is for fast cleaning of a room.

  1. Press the FAN button during operation to cycle Quiet, Low, Standard and Turbo.
  2. Do not move the unit or attach or remove parts while it runs, or water leakage and malfunction can result.

Applies to: MCKB70YSAU

Source: Daikin MCKB70YSAU installation & operation manual, p. 17. Written in our own words; check the manual for your exact model.

Cleaning and chemicals

General · MCB50

Do not use chlorinated or acidic detergents, paint thinner or other chemicals on the unit. Clean only with the unit unplugged.

  1. Unplug the unit before cleaning.
  2. Do not use chlorinated or acidic detergents.
  3. Do not wipe the unit with paint thinner or other chemicals.

Applies to: MCB50YSAU

Source: Daikin air purifier installation & operation manual, p. 4-5. Written in our own words; check the manual for your exact model.

Do not operate with UV parts removed or the unit damaged

General · MCB50

The unit uses a deep UVC LED for sterilization. UVC can harm eyes and skin. Do not run the unit without the carbon filter unit and dust collection filter, or if the unit is damaged. Do not look inside while it runs and do not touch the UV unit.

  1. Keep the carbon filter unit and dust collection filter installed.
  2. Do not run the unit if it is damaged.
  3. Do not look into the unit while it is operating.
  4. Do not touch the UV unit.

Applies to: MCB50YSAU

Source: Daikin air purifier installation & operation manual, p. 5. Written in our own words; check the manual for your exact model.

Do not unplug to stop the unit

General · Daikin Humidifying Air Purifier

Removing the power plug during operation can cause overheating or electric shock. Stop with the operation button instead.

  1. Press the operation button to stop the unit.
  2. Unplug only after it has stopped.

Applies to: MCKB70YSAU

Source: Daikin MCKB70YSAU installation & operation manual, p. 16, 17. Written in our own words; check the manual for your exact model.

Dust sensor reads low at Turbo airflow

General · Humidifying Air Purifier

At high airflow such as Turbo, dust may pass the inlet before reaching the dust sensor. This is normal and is not a fault.

  1. Use a lower airflow setting if accurate dust readings are needed.

Applies to: Dust/particle sensor

Source: Daikin MCKB70YSAU installation & operation manual, p. 10. Written in our own words; check the manual for your exact model.

Fill the water tank

General · Daikin Humidifying Air Purifier

Only fill with tap water, and never above the full line in the spout. The full tank weighs about 3.3 kg (7.28 lb), so carry it with both hands. Keep the tank level, because a tilted tank spills through the top.

  1. Unplug the unit before filling or installing the tank.
  2. Pull the tank toward you while pressing the lever, holding the grip, and release the side lock to take it out.
  3. Clean the tank by swirling a small amount of water inside before filling.
  4. Pour tap water slowly into the spout, stopping at the full line.
  5. Do not touch the water tank lid or side lock when fitting the tank, and avoid the center valve.
  6. Insert the tank into the humidifying tray and press until it clicks.
  7. Plug the unit in only when the air is odor-free, because the odor sensor sets its basic sensitivity during the first minute.

Applies to: MCKB70YSAU

Source: Daikin MCKB70YSAU installation & operation manual, p. 16. Written in our own words; check the manual for your exact model.

Filter and RTC change interval

General · Daikin One Premium Air Cleaner

Change the MERV 15 filter once or twice a year and the RTC every six months, based on home conditions.

Applies to: DV1-15 series

Source: Daikin One Premium Air Cleaner installation & operation manual, p. 2. Written in our own words; check the manual for your exact model.

Handling and storage of replacement filters and RTC

General · Daikin One Premium Air Cleaner

Protect yourself and keep the filters in good condition.

  1. Wear clean, maintained PPE: safety glasses, chemical-resistant gloves, and a disposable half-mask dust filter.
  2. Avoid eye and skin contact and breathing dust. Do not eat, drink or smoke in the work area.
  3. Store filters and RTC away from chemicals, heat and dampness in a well-ventilated area.
  4. Dispose of used materials according to national, state and local rules.

Applies to: DV1-15 series

Source: Daikin One Premium Air Cleaner installation & operation manual, p. 2. Written in our own words; check the manual for your exact model.

Homeowner dismissing alerts

General · Daikin One+ (S21)

The homeowner can clear an alert message or restart the system, but some alerts stay active until a dealer fixes the underlying issue.

  1. Check whether the alert is still showing after the homeowner restarts the system.
  2. If it remains, the dealer must resolve the cause before it clears.

Applies to: Daikin One+ Smart Thermostat

Source: Daikin One+ installation & commissioning (S21), p. 8. Written in our own words; check the manual for your exact model.

Humidity target selection

General · Daikin Humidifying Air Purifier

Pressing the humidity button during humidifying cycles through Low, Standard, High and OFF. Targets are estimates and the room may not reach them.

  1. Press the humidity button during operation to change the setting.
  2. Pick Low, Standard or High, or OFF.
  3. Change the water in the tray and tank every day.

Applies to: MCKB70YSAU

Source: Daikin MCKB70YSAU installation & operation manual, p. 18. Written in our own words; check the manual for your exact model.

Inline MERV filter change

General · Daikin One Powered Ventilator

Standard MERV 16 inline filter, nominal 10 x 10 x 2 in. Flow drops as it loads, so it needs periodic changes.

  1. Check the filter monthly.
  2. Replace at least every 3 months, or sooner if airflow restriction is too high.
  3. If the MERV 16 filter restricts airflow too much, use the MERV 13 filter (DQ-P-F-13).
  4. Remove the control compartment cover, pull out the old filter, and seat the new one fully to the bottom of the slot.

Applies to: DQ-P-16-100

Source: IO-DPV installation manual, p. 6-8. Written in our own words; check the manual for your exact model.

Keep flammable and smoke sources away

General · MCB50

Keep burning cigarettes and incense away from the unit. Do not use hair spray, insecticide or other flammable products near it. Do not use the unit right after insecticide fumigation until the room is aired out. Do not use silicone-containing cosmetics or ultrasonic humidifiers close to it, as they can clog the dust collection filter.

  1. Keep cigarettes and incense away from the unit.
  2. Keep flammable sprays and insecticide away from it.
  3. Air the room out after insecticide use before operating.
  4. Keep silicone-based products and ultrasonic humidifiers away from it.

Applies to: MCB50YSAU

Source: Daikin air purifier installation & operation manual, p. 5-6. Written in our own words; check the manual for your exact model.

Keep the unit complete and do not service it internally

General · MCB50

Operate only with all parts installed. Do not take the unit apart or repair it yourself. Servicing beyond the operating instructions is for qualified personnel only.

  1. Keep the pre-filter, carbon filter unit and dust collection filter installed.
  2. Do not disassemble or repair the unit.
  3. Use only the service paths allowed by the manual or the place of purchase.

Applies to: MCB50YSAU

Source: Daikin air purifier installation & operation manual, p. 4-5, 8. Written in our own words; check the manual for your exact model.

Known limits of the air purifier

General · Humidifying Air Purifier

The unit does not remove every contaminant, so it does not replace ventilation or UV-only sterilization.

  1. Do not rely on the unit to remove all toxic substances from tobacco smoke, such as carbon monoxide.
  2. Do not expect odors to disappear if they are constantly generated, such as building material or pet odors.
  3. Do not expect UV to remove all bacteria.
  4. Ventilate the room when combustion heating is used with the unit.

Applies to: Daikin MCKB70YSAU

Source: Daikin MCKB70YSAU installation & operation manual, p. 8. Written in our own words; check the manual for your exact model.

Locations to avoid

General · MCB50

Do not place the unit where oil, flammable gas, corrosive gas, metal dust or high humidity/splash is present, such as a bathroom. Keep it out of reach of small children and pets. Do not place it near a smoke detector, where the outflow blows toward the detector. Do not place it in direct sunlight, near combustion heaters or high-temperature devices, or near strong electromagnetic sources.

  1. Pick a dry location away from oil, flammable gas, corrosive gas and metal dust.
  2. Keep it out of bathrooms and out of reach of children and pets.
  3. Keep it away from smoke detectors and from direct sunlight.
  4. Keep it away from combustion heaters and electromagnetic devices.

Applies to: MCB50YSAU

Source: Daikin air purifier installation & operation manual, p. 4-6. Written in our own words; check the manual for your exact model.

Magnet handling precautions

General · Daikin One Premium Air Cleaner

The door uses very strong magnets that can pinch fingers and affect pacemakers or ICDs.

  1. Hold the outer door panel with both hands when removing or replacing it.
  2. Keep pacemaker or ICD wearers away from the door magnets.
  3. Keep magnets away from children; swallowed magnets can cause serious intestinal injury.

Applies to: DV1-15 series

Source: Daikin One Premium Air Cleaner installation & operation manual, p. 2. Written in our own words; check the manual for your exact model.

Maintenance and cleaning

General · Daikin One Powered Ventilator

Keep the heater and ventilator clean. Never immerse electrical parts in water.

  1. Disconnect power at the main disconnect before cleaning.
  2. Wipe all parts with a dry cloth or gently vacuum the fan.
  3. Do not immerse electrical parts in water.

Applies to: Heater accessory and ventilator

Source: IO-DPVH installation and operation manual, p. 4. Written in our own words; check the manual for your exact model.

Message types and alert priority

General · Daikin One+

The system shows four message types: status, alerts, reminders and prompts, and learn more/tips. Alerts take priority over all other messages. The homeowner can temporarily dismiss a message or restart the system, but some alerts stay until a dealer resolves the issue.

  1. Check for alerts first, since they override other messages.
  2. If an alert remains after the homeowner dismisses it or restarts the system, the dealer must resolve the underlying issue.

Applies to: Daikin One+ S21 thermostat

Source: Daikin One+ Smart Thermostat Installation & Commissioning (S21) manual, p. 7-8. Written in our own words; check the manual for your exact model.

Moving the unit

General · MCB50

Turn the power off before moving the unit. Carry it by the two body grips. Do not lift it by the grip on the carbon filter unit.

  1. Turn the power off.
  2. Unplug the unit.
  3. Hold the two body grips to carry it.
  4. Do not lift by the carbon filter unit grip.

Applies to: MCB50YSAU

Source: Daikin air purifier installation & operation manual, p. 5-7. Written in our own words; check the manual for your exact model.

Normal splashing during humidifying

General · Daikin Humidifying Air Purifier

Splashing sounds during humidifying are normal and are not a malfunction. Room temperature may drop slightly during humidifying.

Applies to: MCKB70YSAU

Source: Daikin MCKB70YSAU installation & operation manual, p. 17, 18. Written in our own words; check the manual for your exact model.

Overcool setting and how it changes thermostat cycling

General · Daikin One+

Overcool 0 cycles the system at the displayed cooling set point. Overcool 2 makes the thermostat run past the displayed set point using an internal over-set point that the user does not see. The thermo on/off deadband is fixed at ±1°F for mini-split and multi-split indoor units.

Applies to: Daikin One+ thermostat, mini-split and multi-split indoor units

Source: Daikin One+ Installation & Commissioning (S21), p. 32. Written in our own words; check the manual for your exact model.

Power off and follow local electrical code

General · Daikin One Powered Ventilator

Switch power off at the service panel before installation. All wiring must follow local codes and the national electrical code; get a qualified electrician if unfamiliar with wiring.

  1. Turn off power at the service panel before starting.
  2. Follow local codes and the national electrical code for all connections.

Applies to: DQ-P-MDV motorized damper

Source: Daikin IO-DPVMD motorized damper installation manual, p. 2. Written in our own words; check the manual for your exact model.

Power supply and cord rules

General · MCB50

Use only a 120 V supply. Do not run the cord under carpet, under rugs or under furniture. Do not pull the cord to unplug it, and do not plug or unplug with wet hands. Do not use a damaged cord or plug, and do not operate the unit with a damaged cord or plug.

  1. Use a 120 V outlet only.
  2. Check the cord and plug for damage before use.
  3. Route the cord clear of traffic and away from heavy objects.
  4. Unplug at the plug, not the cord.

Applies to: MCB50YSAU

Source: Daikin air purifier installation & operation manual, p. 4. Written in our own words; check the manual for your exact model.

Pre-filter cleaning

General · Air Purifier

Remove, vacuum, and wash the pre-filter at the interval given in the manual.

  1. Unplug the unit before maintenance.
  2. Vacuum the pre-filter.
  3. Wash the filter with water, then dry it fully in the shade.
  4. Use a soft brush between the slats; do not use hard brushes or cotton swabs.

Applies to: MCB50YSAU

Source: Daikin MCB50YSAU installation & operation manual, p. 17. Written in our own words; check the manual for your exact model.

Pre-filter maintenance in high-traffic sites

General · Humidifying Air Purifier

Clogged pre-filters cause malfunction. High-traffic sites need more frequent service.

  1. Shorten the maintenance period in busy places such as hotels and public facilities.
  2. Replace or service the pre-filter sooner if it becomes clogged.

Applies to: Daikin MCKB70YSAU

Source: Daikin MCKB70YSAU installation & operation manual, p. 8. Written in our own words; check the manual for your exact model.

Set the louver before operation

General · Daikin Humidifying Air Purifier

The louver is hand-operated and does not close by itself at the end of a run. Open it by hand before starting. It sets airflow direction in 4 positions.

  1. Open the louver by hand before operation.
  2. Adjust it to the desired position to change airflow direction.

Applies to: MCKB70YSAU

Source: Daikin MCKB70YSAU installation & operation manual, p. 17. Written in our own words; check the manual for your exact model.

Settings menu contents

General · Daikin One+ S21

The Settings menu gives access to Display, Comfort (target humidity), Configuration (app account, dealer information, date and time, message and alert settings, system components, home Wi-Fi).

  1. Open Settings from the home screen.
  2. Choose Display, Comfort or Configuration as needed.

Applies to: Daikin One+ S21 thermostat, homeowner settings

Source: Daikin One+ installation & commissioning (S21) manual, p. 45. Written in our own words; check the manual for your exact model.

Storing the unit for a long time

General · Air Purifier

Preparation for long periods of non-use.

  1. Unplug the power supply.
  2. Clean the parts and let all water-washed parts dry completely.
  3. Cover the air outlet and openings with plastic to keep out dust.
  4. Store the unit upright in a dry place, never upside down or on its side.

Applies to: MCB50YSAU

Source: Daikin MCB50YSAU installation & operation manual, p. 19. Written in our own words; check the manual for your exact model.

Turn off the system fan before maintenance

General · Daikin One Premium Air Cleaner

The system blower can start unexpectedly and cause injury.

  1. Turn off the main electrical disconnect and tag it before working.
  2. Turn off the heating and cooling fan before servicing the air cleaner.

Applies to: DV1-15 series

Source: Daikin One Premium Air Cleaner installation & operation manual, p. 2. Written in our own words; check the manual for your exact model.

UV emission modes

General · Daikin Humidifying Air Purifier

In AUTO UV the unit emits UV for about 30 minutes, pauses, then repeats about 90 minutes later. Hand-operated UV emits for about 30 minutes and then returns to AUTO UV. UV is off during humidifying filter drying and when the unit is stopped.

  1. Use AUTO UV for automatic emission.
  2. Press the UV button to start hand-operated UV for about 30 minutes.
  3. Press the UV button during emission to stop it.
  4. Do not operate with the filter fixing unit, carbon filter or dust collection filter removed, because deep UV can harm eyes and skin.

Applies to: MCKB70YSAU

Source: Daikin MCKB70YSAU installation & operation manual, p. 19. Written in our own words; check the manual for your exact model.

Ventilate when fuel-burning equipment is in the room

General · MCB50

Oxygen deficiency from burner equipment in the same room can cause asphyxiation. The air purifier does not remove carbon monoxide and is not a substitute for ventilation.

  1. Ventilate the room well when a burner is in use in the same room.
  2. Ventilate often when using combustion heaters with the unit.

Applies to: MCB50YSAU

Source: Daikin air purifier installation & operation manual, p. 4-5. Written in our own words; check the manual for your exact model.

2-area INTELLIGENT EYE airflow direction rules

Heat pump · FTXM-W/V

Detected people are steered away from the airflow. The direction moves to the opposite zone. The Comfort or Focus option sets whether air is directed away from or toward people.

  1. Both zones occupied: airflow moves to the left side (zone B).
  2. Only zone A occupied: airflow moves to zone B (left).
  3. Only zone B occupied: airflow moves to zone A (right).
  4. Nobody in either zone: airflow direction does not change.
  5. Select Comfort (away from people) or Focus (toward people) in the settings as needed.

Applies to: FTXM09/12WVJU9, FTXM09/12VVJU

Source: Daikin SiUS042113EA service manual, p. 45. Written in our own words; check the manual for your exact model.

Accessories and auxiliary device wiring

Heat pump · Daikin One Touch

The thermostat supports air quality sensors, humidifiers, dehumidifiers, UV bulbs, electronic filters, HEPA filters and the EWC Zone Board. Humidifiers and dehumidifiers can be installed on aux 1 or aux 2. An isolation relay is recommended between an auxiliary device and the thermostat.

  1. Select aux 1 or aux 2 for the humidifier or dehumidifier.
  2. Install an isolation relay between each auxiliary device and the thermostat.

Applies to: Daikin One Touch smart thermostat, added equipment

Source: Daikin One Touch installation training TRC-10, p. 40. Written in our own words; check the manual for your exact model.

Air quality screen and one clean

Heat pump · Daikin One Touch

The air quality screen shows indoor and outdoor air quality and weather when the unit is online and paired with the app. Without air quality sensors, indoor air quality is estimated from filter life and humidity. One clean runs the fan at high speed for three hours to circulate and filter the indoor air, and it is started from the indoor air quality history screen.

  1. Open the air quality screen to view indoor and outdoor air quality.
  2. Select indoor air quality to reach one clean and the air quality history.
  3. Start one clean to run the fan at high speed for three hours.

Applies to: Daikin One Touch smart thermostat with or without air quality sensors

Source: Daikin One Touch smart thermostat training module TRC-10, p. 63. Written in our own words; check the manual for your exact model.

Airflow flap behaviour by function

Heat pump · FTXM-W/V

The large power-airflow flap sends air down to the floor in cooling, dry and heating. In cooling or dry mode the flap pulls back into the unit so cool air travels further across the room. In heating the large flap points down to spread warm air. Wide-angle louvers made of elastic resin give a broad air spread.

  1. Check the flap is retracting in cooling or dry mode if air does not reach the far side of the room.
  2. Check the flap is pointing down in heating mode.

Applies to: Indoor unit airflow, FTXM-W/V series

Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 38. Written in our own words; check the manual for your exact model.

Aux heater wiring requirements

Heat pump · P1P2, S21

Aux heat is supported on P1P2 (VRV, SkyAir) and S21 (single and multi-split) systems. The aux heat source must not need the indoor unit fan; it is only controlled from the thermostat. The thermostat aux outputs are dry contacts that close to switch on the aux equipment, and a 24V AC control signal must be routed through those aux contacts.

  1. Confirm the system is P1P2 or S21.
  2. Confirm the aux heat source does not need the indoor unit fan to run.
  3. Wire the thermostat aux output as a dry contact that closes to call for aux heat.
  4. Route a 24V AC control signal through the aux contacts.

Applies to: P1P2 and S21 systems with Daikin One+ thermostat

Source: Aux heater installation and setup instructions, p. 1. Written in our own words; check the manual for your exact model.

Brazing refrigerant lines and protecting components

Heat pump · DX6VS, DZ6VS, DZ6VSA

Protect the service valve, sensors and filter drier from heat with a wet rag or heat trap compound, and keep water out of the tubing. Use a brazing alloy with at least 2% silver and no flux. Purge with nitrogen at 2 to 3 PSIG during brazing to stop copper oxide forming. Quench joints with water or a wet cloth during and after brazing. Remove Schrader valves from the service valves before brazing. Cut line ends square, deburr and clean them, and avoid kinks or dents. The bi-flow filter drier is brazed on site before the expansion device at the indoor unit. Check the drier paint after brazing and repaint or treat with rust inhibitor if burned or chipped.

  1. Remove Schrader valves from service valves before brazing.
  2. Cut and deburr line ends square and clean them.
  3. Purge with nitrogen at 2 to 3 PSIG while brazing.
  4. Wet-wrap the service valve, sensors and filter drier, or use heat trap compound.
  5. Braze with at least 2% silver alloy, no flux.
  6. Quench joints with water or a wet cloth during and after brazing.
  7. Braze the bi-flow filter drier before the indoor expansion device.
  8. Check and repair the drier paint finish after brazing.

Applies to: DX6VS / DZ6VS / DZ6VSA outdoor units, field refrigerant line work

Source: Daikin DX6VS/DZ6VS installation manual (3P731493-1), p. 16. Written in our own words; check the manual for your exact model.

Checking EEV coil attachment

Heat pump · DX6VS, DZ6VS

An EEV coil that is not fully clicked onto its body can cause EEV-related errors such as E21 and E22.

  1. Check that the protrusion on the EEV coil is clicked into the dimple on the EEV body.
  2. Reseat the coil if it is not fully clicked in.

Applies to: DX6VS/DZ6VS EEV coils (indoor and outdoor)

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 51. Written in our own words; check the manual for your exact model.

Compatible accessories

Heat pump · Daikin One Touch

The One Touch thermostat works with air quality sensors, humidifiers, dehumidifiers, UV bulbs, electronic filters, HEPA filters and the EWC zone board. Humidifiers and dehumidifiers are wired to aux 1 or aux 2. Use an isolation relay between any auxiliary device and the thermostat.

  1. Wire humidifier or dehumidifier to aux 1 or aux 2.
  2. Install an isolation relay between each auxiliary device and the thermostat.

Applies to: Daikin One Touch thermostat accessories

Source: Daikin One Touch smart thermostat training module TRC-10, p. 40. Written in our own words; check the manual for your exact model.

Compressor terminal venting precautions

Heat pump · DX6VS, DZ6VS

Compressor terminal venting can spray hot vapor and liquid and ignite. Proper evacuation of the system is essential. Extinguish open flame and turn off power and heat sources before servicing.

  1. Make sure the compressor terminal protective cover and gasket are in place and secured.
  2. Turn off or extinguish all open flame, electrical power and other heat sources before servicing.
  3. Do not bypass safety devices.

Applies to: Compressors on DX6VS / DZ6VS outdoor units

Source: Daikin SiUS612209EA service instructions, p. 20. Written in our own words; check the manual for your exact model.

Connect and set up D-Checker for inverter data

Heat pump · DX6VS, DZ6VS

D-Checker software logs inverter sensor data and actuator status from the outdoor unit through a PCB connector and a dedicated cable. Only one outdoor unit can be monitored at a time, and sensor items vary by model. The values in the addendum are examples only, so check the IO manual for the operating range of the unit.

  1. Copy the latest D-Checker software to any folder on the PC and run it. Confirm it is the latest version with Daikin tech support.
  2. Open Options (F6).
  3. Select the COM port.
  4. Select the unit of measurement.
  5. Select the sampling rate (5 seconds is recommended).
  6. Enter the service office (name or department) and the responsible person's name.
  7. Press OK to save.

Applies to: Daikin inverter outdoor units supported by D-Checker

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 128. Written in our own words; check the manual for your exact model.

Cooling plate cover screw torque and grease (3.5 to 5.0 ton)

Heat pump · DX6VS, DZ6VS

On 3.5 to 5.0 ton units, the inverter cooling plate must be sealed well to avoid E32. Check the screws and the thermal grease when troubleshooting E32.

  1. Tighten all cooling plate cover screws to 1.59 ± 0.20 N·m (1.17 ± 0.15 lb·ft).
  2. Make sure the liquid tubing contacts the cooling plate fully.
  3. Make sure all four cooling plate nails are hooked into the square holes.
  4. Apply new thermal grease between the refrigerant tubing and the cooling plate on the control board if the old grease is not new.

Applies to: DX6VS/DZ6VS 3.5 to 5.0 ton outdoor units

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 54. Written in our own words; check the manual for your exact model.

D-Checker: playback and CSV export

Heat pump · DX6VS, DZ6VS

Recorded data can be played back and exported as a CSV file for the job record.

  1. Rename the recording in the editor tab (F5) if needed.
  2. Stop the recording with Stop Rec. (F8).
  3. Select the recording and press Play (F2).
  4. Select CSV output (F2), then click Open and Save.
  5. Create a folder named for the jobsite on the desktop and save the CSV there.

Applies to: DX6VS / DZ6VS outdoor units with D-Checker

Source: Daikin SiUS612209EA service instructions, p. 133. Written in our own words; check the manual for your exact model.

Discharge the outdoor unit capacitor before repair

Heat pump · FTXM-W/V

The step-up capacitor holds high-voltage charge that can shock the technician even after power is removed.

  1. Fully discharge the step-up capacitor before starting repair work on the outdoor unit.

Applies to: Outdoor unit

Source: SiUS042113EA service manual, p. 8. Written in our own words; check the manual for your exact model.

Disconnect power before repair work

Heat pump · FTXM-W/V

Switch off and unplug the unit before disassembly. Working on energized equipment can cause electric shock. If power must stay on for circuit checks, do not touch live parts.

  1. Disconnect the power cable from the socket before disassembling for repair.
  2. If power must stay on for testing, keep hands off all charged sections.

Applies to: All FTXM-W/V indoor and outdoor units

Source: SiUS042113EA service manual, p. 7. Written in our own words; check the manual for your exact model.

Do not cut outdoor PCB jumpers

Heat pump · FTXM-W/V

Some jumpers on the outdoor PCB are needed for the circuit. Cutting one can cause wrong operation. If a jumper was cut by mistake, replace the PCB.

  1. Check the outdoor PCB for any jumper that has been cut.
  2. If a jumper was cut by mistake, replace the PCB. Do not try to repair the jumper.

Applies to: Outdoor unit PCB, FTXM-W/V series

Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 32. Written in our own words; check the manual for your exact model.

Do not power-cycle the unit by plugging and unplugging

Heat pump · FTXM-W/V

Using the power plug to turn the unit on or off can cause electric shock or fire.

  1. Operate the unit with its controls, not by plugging or unplugging the power cable.

Applies to: All FTXM-W/V units

Source: SiUS042113EA service manual, p. 8. Written in our own words; check the manual for your exact model.

Drain pan heater setup (09/12 class)

Heat pump · FTXM-W/V

Fit a drain pan heater in high humidity or heavy snow areas to stop ice building up on the bottom frame. On the 09/12 class, the heater is enabled by cutting a jumper on the outdoor PCB.

  1. Install the drain pan heater following the instructions supplied with the heater.
  2. Remove the outdoor unit top plate (4 screws).
  3. Remove the electrical wiring box cover.
  4. Cut jumper J9 on the outdoor PCB.
  5. Jumper location is shown on the outdoor PCB page referenced in the manual (page 26).

Applies to: Outdoor unit, 09/12 class (RXM09/12)

Source: Daikin SiUS042113EA service manual, p. 168. Written in our own words; check the manual for your exact model.

Drain pan heater setup (18/24 class)

Heat pump · FTXM-W/V

On the 18/24 class, the drain pan heater is enabled with a DIP switch on the outdoor PCB instead of a cut jumper.

  1. Install the drain pan heater following the instructions supplied with the heater.
  2. Remove the service lid (2 screws).
  3. Remove the switch cover (1 screw).
  4. Turn on switch SW6-1 on the outdoor PCB.
  5. Jumper location is shown on the outdoor PCB page referenced in the manual (page 26).

Applies to: Outdoor unit, 18/24 class (RXM18/24)

Source: Daikin SiUS042113EA service manual, p. 168. Written in our own words; check the manual for your exact model.

Electrical noise and communication wiring separation

Heat pump · DX6VS / DZ6VS FIT

The inverter can create electrical noise that disturbs nearby equipment. Keep communication wiring clear of power cable.

  1. Ground the unit well.
  2. Keep radios, TVs, computers, stereos and fluorescent lamps about 40 in. to 60 in. away from the unit and wiring, as shown on page 9.
  3. Keep communication wiring at least 2 in. away from high voltage power cable to avoid communication errors.

Applies to: Inverter outdoor units with communicating thermostat

Source: Daikin DX6VS/DZ6VS outdoor unit installation & service reference, p. 9. Written in our own words; check the manual for your exact model.

Electrostatic discharge precautions for indoor control module

Heat pump · DX6VS / DZ6VS

Discharge static before touching the integrated control module or its wiring to avoid damage.

  1. Disconnect all power to the indoor unit.
  2. Touch a clean, unpainted metal surface of the blower near the control to ground yourself.
  3. Keep the body grounded while servicing; do not shuffle feet or touch ungrounded objects.
  4. If an ungrounded object is touched, ground again before touching the control.
  5. Ground yourself before removing a new control from its container.

Applies to: Indoor unit integrated control module

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 3. Written in our own words; check the manual for your exact model.

Equipment set-up menu items

Heat pump · Daikin One Touch

Step 3 lists the equipment found on the communication network or lets you add or remove equipment and accessories from the preset list. The equipment identified sets which configuration screens appear. The menu covers unit specifications, cool settings, heat settings, heat pump settings, humidifier relay, aux alarm and heater kit.

  1. Check the equipment found on the network or adjust the preset list.
  2. Open View unit Specifications to confirm the identified unit.
  3. Configure the cool, heat, heat pump, humidifier relay, aux alarm and heater kit screens as they apply.

Applies to: Daikin One Touch smart thermostat, Step 3 Equipment Set-up

Source: Daikin One Touch installation training TRC-10, p. 39. Written in our own words; check the manual for your exact model.

Fastener types on panels and covers

Heat pump · DX6VS, DZ6VS

Use the right fastener type when reassembling the outdoor unit.

  1. Use M5 × 12 hex flanged screws for the screws not otherwise specified on the panels.
  2. Use 3 class hex head tapping screws for the circled screws on the right side plate, the terminal board shield plate and the field wiring plate. Reuse the same screws.

Applies to: 3.5 to 5.0 ton HP & AC

Source: Daikin SiUS612209EA service instructions, pp. 105, 107, 108. Written in our own words; check the manual for your exact model.

Grounding and protection device rules

Heat pump · DX6VS / DZ6VS FIT

Incomplete grounding or altered protection devices create shock, gas and fire hazards.

  1. Do not ground the unit to water pipes, suction line, telephone wires or lightning rods.
  2. Do not ground to gas pipes.
  3. Use a separate power supply circuit for the unit.
  4. Secure all wiring and keep the side plate over the power terminal block secure.
  5. Never short or force a pressure switch, thermal switch or other protection device, and use only Daikin-specified parts.

Applies to: Outdoor units

Source: Daikin DX6VS/DZ6VS outdoor unit installation & service reference, p. 11. Written in our own words; check the manual for your exact model.

Hermetic compressor terminal protective cover

Heat pump · DX6VS / DZ6VS

A venting terminal can spray hot oil, refrigerant and possibly flammable mixture. Never energize or run the compressor without the terminal cover in place.

  1. Confirm the terminal protective cover is properly installed before any electrical energizing.
  2. Follow the Service Section S-17 procedure for proper servicing.

Applies to: Hermetic compressors

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 4. Written in our own words; check the manual for your exact model.

Homeowner routine maintenance and filter care

Heat pump · DX6VS, DZ6VS

Recommended maintenance to pass on to the customer. A bi-annual checkup by a qualified servicer is advised before the heating and cooling seasons. Never run the unit without a filter, since dust and lint cause efficiency loss, damage and possible fire. Check the filter at least monthly and replace disposable filters or clean reusable ones. The compressor and fan motors are sealed or permanently lubricated and need no oiling.

  1. Schedule a bi-annual checkup by a qualified servicer before each heating and cooling season.
  2. Check the air filter at least monthly and replace or clean it as needed.
  3. Do not operate the system without a filter installed.
  4. Keep the outdoor unit free of obstructions and do not build a fence, deck or patio near it.
  5. Do not cover the outdoor unit. The fan may start on its own for system reliability.

Applies to: Outdoor unit homeowner maintenance

Source: Daikin DX6VS/DZ6VS installation & service reference, p. 57. Written in our own words; check the manual for your exact model.

Install the D-Checker software on a laptop

Heat pump · DX6VS, DZ6VS

D-Checker is a PC tool for logging inverter data (temperatures, pressures, actuator status) from the outdoor unit. It works only on a single outdoor unit and needs its own connection cable.

  1. Copy the latest D-Checker version to any folder on the PC.
  2. Run the software.
  3. Confirm you have the latest version (ask Daikin technical support for it).
  4. Press Options (F6).
  5. Select the COM port.
  6. Select the unit of measurement.
  7. Select the sampling rate (5 seconds recommended).
  8. Enter the service office (your name or department).
  9. Enter the responsible person's name.
  10. Press OK when finished.

Applies to: Daikin inverter outdoor units with D-Checker cable

Source: Daikin SiUS612209EB service instructions, p. 128. Written in our own words; check the manual for your exact model.

INTELLIGENT EYE motion sensor detection logic

Heat pump · FTXM-W/V

The indoor unit microcomputer samples the motion sensor every 20 ms. It counts the pulses in each second. If the sensor gives at least 10 outputs per second and the High signal lasts 2 seconds or more, the unit treats the room as occupied. The 2-area version splits the view into two zones and checks each zone separately.

  1. If a presence fault is suspected, confirm the sensor sees moving people and that the High signal holds for at least 2 seconds.
  2. Check the sensor is not blocked and is aimed at the room.

Applies to: FTXM09/12WVJU9, FTXM09/12VVJU (2-area); FTXM18/24WVJU9, FTXM18/24VVJU (single area)

Source: Daikin SiUS042113EA service manual, p. 44. Written in our own words; check the manual for your exact model.

Inverter compressor drive basics

Heat pump · FTXM-W/V

The inverter first converts the AC supply to DC, then converts that DC back to three-phase AC at a variable frequency. A higher frequency speeds the compressor up and moves more refrigerant, so the unit delivers more heat or cooling. A lower frequency reduces capacity. The compressor frequency is set by the load on the operating indoor unit and the gap between the room thermistor and the target temperature.

  1. Expect higher compressor speed during quick heating or cooling startup.
  2. Expect reduced capacity when the set temperature is reached and the unit runs in energy saving mode.

Applies to: Outdoor unit inverter, FTXM-W/V series

Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 36. Written in our own words; check the manual for your exact model.

Keep R-410A system clean, dry and tight

Heat pump · DX6VS / DZ6VS FIT

Moisture and contamination damage the PVE oil and compressor. R-410A is a blend and must be charged as liquid.

  1. Keep foreign material and moisture out of the system.
  2. Check the piping for leaks.
  3. Charge R-410A in liquid state only. Charging as gas changes the blend and the system will not work correctly.
  4. Do not use the conventional refrigerant or refrigerator oil in R-410A. This causes deterioration.
  5. Keep the compressor open to air for as short a time as possible.

Applies to: R-410A systems

Source: Daikin DX6VS/DZ6VS outdoor unit installation & service reference, p. 11. Written in our own words; check the manual for your exact model.

Keep the outdoor fan clear when the unit has power

Heat pump · DX6VS, DZ6VS

Even when not running, the outdoor fan can start to cool the inverter control board, including in winter. Keep it clear at all times while the unit is powered.

  1. Check that nothing blocks the outdoor fan before the unit is powered.
  2. Keep hands and tools away from the fan while the unit is connected to main power.

Applies to: Inverter outdoor units

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 4. Written in our own words; check the manual for your exact model.

Keep the refrigerant circuit free of air and other gases

Heat pump · FTXM-W/V

Air or any gas other than the specified refrigerant raises system pressure enough to damage equipment and cause injury.

  1. Charge only the specified refrigerant (R-32 / R-410A / R-22 as applicable).
  2. Do not let air enter the refrigerant system during service.

Applies to: All refrigerant circuits

Source: SiUS042113EA service manual, p. 8. Written in our own words; check the manual for your exact model.

Limit refrigerant cylinder filling and check the cylinder

Heat pump · DX6VS, DZ6VS

R-410A cylinders can fail if overfilled, heated with flame or steam, or rated too low. Check the cylinder before use.

  1. Use only returnable (not disposable) service cylinders to remove refrigerant.
  2. Check that the cylinder is free of damage and its hydrostatic test date is within 5 years.
  3. Check the cylinder pressure rating is at least 400 psig.
  4. Never fill a cylinder more than 80% full of liquid refrigerant.
  5. Never apply flame or steam to a cylinder. Partly immerse it in warm water if you must heat it.
  6. Never add anything other than R-410A to a returnable R-410A cylinder.
  7. Store cylinders in a cool, dry place and never use them as a platform or roller.

Applies to: R-410A refrigerant handling

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 3. Written in our own words; check the manual for your exact model.

Line set vibration and sound isolation

Heat pump · DX6VS / DZ6VS FIT

Refrigerant tubing carries noise and vibration into the structure.

  1. Keep refrigerant lines from touching plumbing, ductwork, joists, studs, floors and walls.
  2. Use sleeves with sound and vibration absorbing material where lines pass through a wall or foundation.
  3. Fill gaps around lines with pliable silicone caulk, RTV or vibration damping material.
  4. Hang lines with insulated or suspension-type hangers, not rigid wire or straps that touch the tubing.
  5. Keep the liquid and suction lines separate.

Applies to: Line set routing

Source: Daikin DX6VS/DZ6VS outdoor unit installation & service reference, p. 12. Written in our own words; check the manual for your exact model.

Mode display basics

Heat pump · DX6VS / DZ6VS

The 3-digit display blinks at 0.4 seconds on and 0.4 seconds off. Screen 0 is the default screen and shows the most recent fault.

  1. Read the first digit to see the current screen number.
  2. Press LEARN to return to screen 0 from any other screen.

Applies to: DX6VS / DZ6VS outdoor unit control board

Source: Daikin SiUS612209EB service instructions, p. 36-37. Written in our own words; check the manual for your exact model.

Monitoring mode navigation

Heat pump · DX6VS / DZ6VS outdoor unit mode display

Screen 2 lets the technician view system values as listed in the monitoring tables at the end of the section (not in this extract).

  1. From screen 2, press RECALL to move through the item numbers.
  2. Read the value shown on the 3-digit display.
  3. Press LEARN to return to screen 0.

Applies to: Outdoor unit control board mode display

Source: Daikin SiUS612209EA service instructions, p. 39. Written in our own words; check the manual for your exact model.

Never energize a hermetic compressor without the terminal cover

Heat pump · DX6VS, DZ6VS

A compressor terminal that vents can spray hot oil, refrigerant and possibly a flammable mix. The terminal cover must be in place before power is applied.

  1. Confirm the compressor terminal protective cover is fitted correctly.
  2. Do not run or energize the compressor with the cover off or loose.
  3. Refer to Service Section S-17 for proper compressor servicing.

Applies to: All compressors in these outdoor units and air handlers

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 4. Written in our own words; check the manual for your exact model.

No pump-down function. Recover all refrigerant from the two service ports

Heat pump · DX6VS, DZ6VS

There is no pump-down function on this unit. To remove or relocate the unit, recover refrigerant through the service ports on the stop valves. Both ports are needed to recover all refrigerant.

  1. Use the two service ports on the stop valves to recover all refrigerant.
  2. Recover all refrigerant before removing or relocating the unit.

Applies to: Outdoor unit refrigerant recovery

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 22. Written in our own words; check the manual for your exact model.

Normal mode (homeowner view)

Heat pump · Daikin One Touch

Normal mode shows messages and the temperature, and gives access to the settings the installer has placed for the homeowner. Icons are tapped to move between screens.

  1. Tap the icons to navigate between screens.
  2. Use the settings the installer has made available to change parameters.

Applies to: Daikin One Touch smart thermostat, homeowner navigation

Source: Daikin One Touch smart thermostat training module TRC-10, p. 59. Written in our own words; check the manual for your exact model.

Oil type for R-410A compressor

Heat pump · DX6VS / DZ6VS

Do not use mineral oil based lubricants such as 3GS. The compressor uses FVC50K, so add only FVC oil if more oil is needed.

  1. Confirm the oil type is FVC before adding oil.
  2. Do not add mineral oil based lubricant.

Applies to: Outdoor AC and heat pump models

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 7. Written in our own words; check the manual for your exact model.

Operating limits for inverter outdoor units

Heat pump · DX6VS, DZ6VS, DZ6VSA

Inverter outdoor units run in cooling down to 0°F outdoor temperature and in heating down to -10°F (RH 10%) without an added kit. Only use a Daikin approved communicating thermostat. Match inverter units only with an EEV indoor unit, and use manufacturer approved, AHRI matched components when replacing any part. Damage from unmatched combinations is not covered by warranty.

Applies to: DX6VS, DZ6VS and DZ6VSA inverter outdoor units

Source: Daikin DX6VS/DZ6VS/DZ6VSA installation manual 3P731493-1, p. 2. Written in our own words; check the manual for your exact model.

Outdoor fan may run when unit is powered but not running

Heat pump · DX6VS / DZ6VS

The inverter control board stays energized and is cooled by the outdoor fan, which can start at any time, including winter. Keep the outdoor fan clear of obstructions when powered.

  1. Keep the outdoor fan clear of obstructions whenever the unit has power.

Applies to: Outdoor inverter units

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 4. Written in our own words; check the manual for your exact model.

Outdoor unit LED A check

Heat pump · FTXM-W/V

The outdoor unit has one green LED (LED A) on the PCB. It blinks when the microcomputer is working normally. Locations are shown on pages 26 and 28.

  1. Check that LED A on the outdoor PCB is blinking.
  2. If it is not blinking, check the PCB and the power supply.
  3. Use pages 26 and 28 to locate the LED on the PCB.

Applies to: FTXM-W/V outdoor unit

Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 92. Written in our own words; check the manual for your exact model.

PI frequency control behaviour

Heat pump · FTXM-W/V

The D value is sampled every 20 seconds and the frequency changes based on the difference from the previous value. If the frequency stays unchanged for a fixed time, the controller adjusts it by the D value: lower D brings the frequency down, higher D brings it up. While another limit is active, frequency control only drops the frequency (when dropping) or only raises it (when limiting the lower limit).

Applies to: FTXM-W/V wall mounted heat pump

Source: Daikin FTXM-W/V service manual, p. 75. Written in our own words; check the manual for your exact model.

Plugging pipe openings against foreign objects

Heat pump · DX6VS, DZ6VS, DZ6VSA

Seal all pipe through-holes with the accessory set or field-supplied putty to stop insects and small animals getting into the unit and damaging electrics. Do not make the final refrigerant connection until the tubing plugs are removed.

  1. Plug all pipe through-holes with accessory set or putty.
  2. Keep the plugs in place until the final refrigerant connection is made.
  3. Remove the tubing plugs before the final connection.

Applies to: Outdoor unit refrigerant line connections

Source: Daikin DX6VS/DZ6VS installation manual (3P731493-1), p. 16. Written in our own words; check the manual for your exact model.

Position the insulation tube slit when reassembling

Heat pump · DX6VS, DZ6VS

The slit in the insulation tube must be placed correctly around the suction pipe thermistor.

  1. Position the slit of the insulation tube opposite the suction pipe thermistor when reassembling.

Applies to: 3.5 to 5.0 ton HP only

Source: Daikin SiUS612209EA service instructions, p. 112. Written in our own words; check the manual for your exact model.

Protect R-410A POE/PVE oil from moisture

Heat pump · DX6VS, DZ6VS

The compressor oil for R-410A units absorbs moisture very easily, which can cause compressor failure. Keep the system sealed as much as possible.

  1. Do not leave the system open to the atmosphere longer than needed for installation or service.
  2. Use only FVC-type oil (FVC50K) when topping up. Do not use mineral oil based lubricants such as 3GS.

Applies to: Outdoor AC and heat pump R-410A models with Daikin rotary compressor

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 3, 7. Written in our own words; check the manual for your exact model.

PVE oil moisture risk on R-410A systems

Heat pump · DX6VS / DZ6VS

PVE oil for R-410A absorbs moisture very easily, which can cause compressor failure.

  1. Do not leave the system open to the atmosphere longer than needed for installation.

Applies to: R-410A systems

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 3. Written in our own words; check the manual for your exact model.

Re-crimp FASTON terminals after inverter analyzer diagnosis

Heat pump · FTXM-W/V

Loose FASTON terminals can overheat and burn. Re-crimp them after finishing the inverter analyzer diagnosis.

  1. After the inverter analyzer diagnosis, re-crimp all FASTON terminals that were disturbed.

Applies to: Inverter outdoor unit diagnosis with inverter analyzer

Source: Daikin Inverter Pair FTXM-W/V service manual, p. 152. Written in our own words; check the manual for your exact model.

Read the error code history

Heat pump · DX6VS / DZ6VS outdoor unit mode display

Screen 1 stores the six most recent faults. Screen 0 shows the present fault only.

  1. From screen 1, press RECALL to show the most recent error code.
  2. Press RECALL again to step to the 2nd most recent code, and so on up to the 6th.
  3. Press LEARN to return to screen 0.

Applies to: Outdoor unit control board mode display

Source: Daikin SiUS612209EA service instructions, p. 38. Written in our own words; check the manual for your exact model.

Read the fault history (Screen 1)

Heat pump · FIT

Screen 1 holds the six most recent faults. The first one shown is the newest and the sixth is the oldest. The fault code list is in the troubleshooting tables, which are not on these pages.

  1. Enter Screen 1 from Screen 0 by holding RECALL for 5 seconds.
  2. Press RECALL to step to the next fault, up to the 6th most recent.
  3. Look up each code in the troubleshooting tables.

Applies to: FIT outdoor units

Source: Daikin FIT outdoor unit installation & service reference, p. 50. Written in our own words; check the manual for your exact model.

Reassembly order for panels and covers

Heat pump · DX6VS, DZ6VS

Reassemble the 3.5 to 5.0 ton unit by doing the removal steps in reverse order.

  1. Reverse the removal sequence when reinstalling panels and covers.
  2. Use the same screw type in each location, as listed on the removal pages.

Applies to: 3.5 to 5.0 ton HP & AC

Source: Daikin SiUS612209EA service instructions, p. 105. Written in our own words; check the manual for your exact model.

Record operating data and view graphs

Heat pump · DX6VS, DZ6VS

Choose which data points to log, start the recording, then view the trends on the graph. The graph has three analog scales.

  1. Click OK (F1) and check that the recorded time fills in.
  2. Start the recording with Start Rec. (F6) if needed.
  3. Select Graph View (F2).
  4. Select all data with Op. All Data (F3), or only chosen points with Op. Selected Data (F4).
  5. Use the analog scale 100, 1000 or 10000 for each channel as needed.
  6. Left-click then right-click on the graph to select the desired data.

Applies to: Daikin inverter outdoor units

Source: Daikin SiUS612209EB service instructions, p. 132. Written in our own words; check the manual for your exact model.

Refrigerant handling and fire risk (R-32)

Heat pump · FTXM-W/V

This appliance is filled with R-32. Keep it away from fire sources. Refrigerant that contacts flame can form toxic gas. Refrigerant released during work can cause frostbite.

  1. Do not store the unit in a room with naked flames, gas appliances or electric heaters.
  2. Ventilate the area if refrigerant leaks during work.
  3. Do not touch refrigerant that is escaping from the system.
  4. Evacuate refrigerant fully in a ventilated place before cutting the compressor suction or discharge pipe at a welded joint.

Applies to: R-32 units

Source: SiUS042113EA service manual, p. 7. Written in our own words; check the manual for your exact model.

Refrigerant handling safety

Heat pump · DX6VS / DZ6VS FIT

R-410A can push oxygen out of a confined space. Recover refrigerant and keep cylinders in limits.

  1. Never vent refrigerant into an enclosed room. Refrigerant must be reclaimed by law.
  2. If an indoor leak is suspected, ventilate the area well before working.
  3. Never burn refrigerant. This produces toxic gas.
  4. Use only returnable (not disposable) service cylinders.
  5. Check that the cylinder is undamaged, its hydrostatic test date is no more than 5 years old, and its pressure rating is at least 400 psig.
  6. Never fill a cylinder more than 80% full of liquid.
  7. Never add anything other than R-410A to an R-410A cylinder. Store cylinders in a cool, dry place and never use one as a platform or roller.
  8. Never apply flame or steam to a cylinder. Partly immerse it in warm water if it must be heated for faster charging.

Applies to: R-410A systems

Source: Daikin DX6VS/DZ6VS outdoor unit installation & service reference, p. 10. Written in our own words; check the manual for your exact model.

Refrigerant tubing and insulation requirements

Heat pump · DX6VS / DZ6VS FIT

Use clean dehydrated copper tubing and insulate the suction line. Field piping must handle the 450 psig design pressure.

  1. Use refrigerant-grade (dehydrated and sealed) copper tubing only.
  2. Cap tubing ends until connection. Cut square, deburr and keep the ends round.
  3. Insulate the suction line to prevent condensation.
  4. Use at least 3/8 in. minimum wall insulation. In severe conditions (likely above 86°F and 80% RH) 1/2 in. may be needed.
  5. Insulate the liquid line if more than 50 ft. of it runs through an area that may be 30°F or more above outdoor ambient in cooling, or where the conditioned space may be colder than outdoor ambient in heating.
  6. Never attach a liquid line to an uninsulated part of the suction line.
  7. Choose field-installed pipe wall thickness for the 450 psig design pressure per local, state and national codes.
  8. Flush the line set with an HVAC flushing solvent if the existing system had oil or debris.

Applies to: Refrigerant line sets

Source: Daikin DX6VS/DZ6VS outdoor unit installation & service reference, p. 12. Written in our own words; check the manual for your exact model.

Remote controller signal range and aim

Heat pump · FTXM-W, FTXM-V

The remote must be aimed at the indoor unit receiver. Anything between them, such as a curtain, can stop the unit responding. Maximum transmission distance is about 23 ft (7 m).

  1. Aim the remote transmitter at the indoor unit.
  2. Clear any curtain or object blocking the signal.
  3. Stay within about 23 ft (7 m) of the unit.

Applies to: FTXM-W/V with ARC466A70 or ARC466A71 remote

Source: SiUS042113EA service manual, p. 85. Written in our own words; check the manual for your exact model.

Remove compressor and sound blankets (heat pump, 1.5 to 3.0 ton)

Heat pump · DX6VS, DZ6VS

Teardown order for the sound blankets and compressor on heat pump models. Heat and putty work is involved, so protect the area and keep plastics clear.

  1. Remove the 2 screws and take off the partition plate. The upper screw is a truss head tapping screw or a hex head screw (M4 x 12).
  2. On reassembly, hook the bottom frame into the slit of the partition plate.
  3. Remove the sound blanket (outer top).
  4. On reassembly, the full edge of the outer top blanket must sit inside the outer body blanket and must not rise above it.
  5. Remove the sound blanket (outer body).
  6. Remove the sound blanket (inner top).
  7. Remove the sound blanket (inner body).
  8. Remove the terminal cover.
  9. Disconnect the compressor lead wires (yellow V, red U, blue W) from the protection bushing.
  10. Remove the OL (overload) from the compressor.
  11. On reassembly, hook the retainer lower hooks into the square holes of the fixture first, then push the upper hooks until they latch. Pass the OL lead wire through the harness route.
  12. Before brazing, remove all putty, the terminal cover and any other plastic parts that could burn. Put a protective sheet or steel plate under the work so the flame cannot reach the surroundings.
  13. Heat the brazed compressor piping joints and disconnect the compressor piping.

Applies to: DX6VS/DZ6VS heat pump outdoor units, 1.5 to 3.0 ton, HP only

Source: Daikin DX6VS/DZ6VS service instructions, p. 96-99. Written in our own words; check the manual for your exact model.

Remove corner guard packaging before setting the unit (3.5-5.0 ton FIT and 3.0-4.0 ton Enhanced Capacity FIT)

Heat pump · DX6VS, DZ6VS, DZ6VSA

The corner guard protects the unit during carrying. It is on the right front part of these larger units and must come off before installation.

  1. Remove the front plate screw.
  2. Pull off the corner guard packaging from the right front part.
  3. Reinstall the front plate screw so the front and top plates are fixed together.

Applies to: DX6VS / DZ6VS 3.5-5.0 ton FIT; DZ6VSA 3.0-4.0 ton Enhanced Capacity FIT

Source: Daikin DX6VS/DZ6VS/DZ6VSA installation manual 3P731493-1, p. 3. Written in our own words; check the manual for your exact model.

Remove heat exchanger (1.5 to 3.0 ton, HP and AC)

Heat pump · DX6VS, DZ6VS

Removal of the outdoor heat exchanger. Brazed joints are involved, so the same fire protection precautions apply.

  1. Remove the suction grille by taking out 1 screw.
  2. Remove 4 screws and take off the left side plate.
  3. Remove putty that may burn from the area.
  4. Put a protective sheet or steel plate under the work so the brazing flame cannot reach the surroundings.
  5. Heat the brazed joints and remove the heat exchanger.

Applies to: DX6VS/DZ6VS outdoor units, 1.5 to 3.0 ton, HP and AC

Source: Daikin DX6VS/DZ6VS service instructions, p. 104. Written in our own words; check the manual for your exact model.

Returnable R-410A cylinder requirements

Heat pump · DX6VS / DZ6VS

Use only returnable service cylinders when removing refrigerant. Cylinder limits apply.

  1. Fill liquid refrigerant to no more than 80% of cylinder capacity.
  2. Use only returnable (not disposable) cylinders.
  3. Check that the cylinder is undamaged.
  4. Confirm the hydrostatic test date is no more than 5 years old.
  5. Confirm the pressure rating is at least 400 psig.
  6. Do not use the cylinder if in doubt.
  7. Never apply flame or steam. To speed charging, partly immerse the cylinder in warm water.
  8. Store cylinders in a cool, dry place and never use them as a platform or roller.

Applies to: R-410A refrigerant handling

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 3. Written in our own words; check the manual for your exact model.

Reuse the correct screws on reassembly

Heat pump · DX6VS, DZ6VS

Some screws are 3 class hex head tapping screws and must be replaced with the same type. Hex flanged M5 x 12 screws are used for any screw not otherwise listed.

  1. Use the same 3 class hex head tapping screws at the marked locations (shield plate, field wiring plate, right side plate circled screws).
  2. Use hex flanged M5 x 12 screws for any unlisted screw on 3.5 to 5.0 ton panels.
  3. Use M5 x 25 tapping screws for the fan motor.

Applies to: 3.5 to 5.0 ton HP & AC outdoor units

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, pp. 105-109. Written in our own words; check the manual for your exact model.

Revision history of this service manual

Heat pump · FTXM-W/V

First edition 04/2021. Revision 09/2022 added the FTXM09WVJU9, FTXM12WVJU9, FTXM18WVJU9 and FTXM24WVJU9 indoor units and the RXM09WVJU9, RXM12WVJU9, RXM18WVJU9 and RXM24WVJU9 outdoor units. Revision 01/2023 updated specifications and corrected errors.

Applies to: FTXM-W/V wall mounted models

Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 17. Written in our own words; check the manual for your exact model.

Rooftop mounting and vibration

Heat pump · DX6VS / DZ6VS FIT

Roof mounts must carry the unit weight and be weather-tight. The unit vibrates when running.

  1. Confirm the roof structure can carry the unit weight and keep the roof weather-tight.
  2. Fit vibration-absorbing pads or springs between the unit legs or frame and the roof mounting assembly.

Applies to: Rooftop installs

Source: Daikin DX6VS/DZ6VS outdoor unit installation & service reference, p. 9. Written in our own words; check the manual for your exact model.

Room and liquid pipe thermistor roles

Heat pump · FTXM-W/V

The room temperature thermistor measures room air and drives room temperature control. The liquid pipe thermistor is used in hybrid cooling: the controller sets a target liquid pipe temperature and adjusts the electronic expansion valve opening to reach it.

Applies to: Indoor unit thermistors, FTXM-W/V wall mounted heat pump

Source: Daikin FTXM-W/V service manual, p. 72. Written in our own words; check the manual for your exact model.

Room temperature control basis

Heat pump · FTXM-W/V

The room thermistor measures the temperature at the unit, which can differ from the temperature at the lower part of the room depending on the indoor unit type and installation. The control uses a target temperature that is adjusted for the indoor unit and the room thermistor reading, not the raw set temperature alone.

  1. Do not judge comfort only by the room thermistor reading.
  2. Remember the set temperature from the remote controller is not the same as the controller target temperature.

Applies to: Indoor units, FTXM-W/V series

Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 36. Written in our own words; check the manual for your exact model.

Route the fan motor lead wire on reassembly

Heat pump · DX6VS, DZ6VS

Route the fan motor lead so it does not catch on the outdoor fan. The routing differs between the 3.5/4.0 ton and 5.0 ton units.

  1. Lower the partition plate hook to pass the fan motor lead wire through, then return the hook.
  2. Clamp the fan motor lead no more than 10 mm (0.4 in) from the partition plate.
  3. On 3.5/4.0 ton units, route the lead behind the fan motor stand.
  4. On 5.0 ton units, route the lead in front of the fan motor stand.
  5. Secure the lead to the motor stand with a weather resistant tie.

Applies to: 3.5 to 5.0 ton HP & AC

Source: Daikin SiUS612209EA service instructions, p. 109. Written in our own words; check the manual for your exact model.

Set heat pump outdoor temperature lockouts at thermostat setup

Heat pump · DX6VS, DZ6VS, Daikin One+

Set the heat pump lockout temperature during initial thermostat setup. Below this outdoor temperature the compressor turns off and heat comes from the auxiliary source. The aux heat lockout temperature turns the auxiliary heat off when outdoor temperature is above that setting.

  1. Set the heat pump lockout temperature in the thermostat setup.
  2. Set the aux heat lockout temperature in the thermostat setup.

Applies to: Heat pump lockouts

Source: Daikin DX6VS/DZ6VS outdoor unit installation & service reference, p. 32. Written in our own words; check the manual for your exact model.

Set up D-Checker for monitoring inverter data

Heat pump · DX6VS, DZ6VS

D-Checker is Daikin's PC software for logging inverter sensor data (temperature, pressure) and actuator status such as compressor and solenoids. It connects through a cable to a PCB connector on the outdoor unit. It does not support monitoring several outdoor units at once. Supported items vary by model, and the manual's values are examples only, so check the product IO manual for real operating ranges.

  1. Copy the latest D-Checker version to any folder on the PC and run it.
  2. Confirm you have the latest version (ask Daikin technical support for it).
  3. Open Options (F6).
  4. Select the COM port.
  5. Select the unit of measurement.
  6. Set the sampling rate (5 seconds is recommended).
  7. Enter the service office (your name or department).
  8. Enter the responsible person's name.
  9. Press OK to finish.

Applies to: DX6VS / DZ6VS inverter outdoor units

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 128. Written in our own words; check the manual for your exact model.

Settings menu contents

Heat pump · Daikin One Touch

The settings screen gives access to system mode, schedule, reminders, and date and time. More options are reached with the down arrow.

  1. Open Settings from the homeowner navigation.
  2. Select the down arrow to show more options.

Applies to: Daikin One Touch smart thermostat, homeowner navigation

Source: Daikin One Touch smart thermostat training module TRC-10, p. 64. Written in our own words; check the manual for your exact model.

Silicone grease on outdoor PCB power transistor or diode bridge

Heat pump · FTXM-W/V

Apply the specified silicone grease to the heat generating part of the power transistor or diode bridge when replacing the outdoor PCB. Poor application can cause smoke from poor heat transfer.

  1. Wipe off all old silicone grease.
  2. Apply the grease evenly to the heat generating surface.
  3. Tighten the power transistor or diode bridge screws.
  4. Check that the heat generating parts sit firmly against the radiation fin.
  5. Check the surface is free of foreign matter before fitting.

Applies to: Outdoor unit PCB replacement

Source: Daikin SiUS042113EA service manual, p. 172. Written in our own words; check the manual for your exact model.

Standby electricity saving (suspend function)

Heat pump · FTXM-W/V

When the system is idle, the indoor and outdoor units can be partly cut from the power supply. The service monitor LED A turns off in this state. The function can be turned on or off from the remote controller service mode (page 164 of the manual). The outdoor unit stays energised for protection even when the indoor unit is off, so the system may not suspend. Starting the fan or any operation wakes the indoor unit and restores communication.

  1. Use the remote controller service mode to enable or disable standby saving.
  2. Expect LED A to be off when the system is in suspend state.
  3. To wake the system, start fan or another operation on the indoor unit.

Applies to: FTXM-W/V wall mounted heat pump

Source: Daikin FTXM-W/V service manual, p. 75. Written in our own words; check the manual for your exact model.

Stop, play back and export a recording to CSV

Heat pump · DX6VS, DZ6VS

Name the recording first, then stop it and export the data for the job file.

  1. Click OK (F1).
  2. Change the label name in the editor tab (F5).
  3. Stop the recording with Stop Rec. (F8).
  4. Select the desired recording and press Play (F2) to review it.
  5. Select CSV output (F2).
  6. Click Open, then Save.
  7. Create a new folder on the desktop named with the job site name and save the CSV there.

Applies to: Daikin inverter outdoor units

Source: Daikin SiUS612209EB service instructions, p. 133. Written in our own words; check the manual for your exact model.

Thermostat message types and priority

Heat pump · Daikin One Touch

The One Touch thermostat shows four kinds of on-screen messages: status, alerts, reminders/prompts, and learn-more tips. Alerts take priority over all other messages, so check for an alert first when a unit seems to be misbehaving. Example alert shown on the page: a fan failure.

  1. Check the screen for an alert before reading status or reminder messages.
  2. Use the status message to see the current mode, such as heating to a set temperature.
  3. Answer reminders or prompts during setup or operation when they appear.
  4. Tap the learn-more icon for an explanation of a message.

Applies to: Daikin One Touch smart thermostat

Source: Daikin One Touch Smart Thermostat Training Module TRC-10, p. 7. Written in our own words; check the manual for your exact model.

Use electrostatic discharge precautions on the integrated control module

Heat pump · DX6VS, DZ6VS

Static can damage the indoor control module. Ground yourself to the unit before touching the control or its wiring.

  1. Disconnect all power to the indoor unit.
  2. Do not touch the control or wires until your body is grounded.
  3. Touch a clean, unpainted metal surface of the blower near the control.
  4. Keep moving around to a minimum after grounding, and touch the blower again if you touch anything ungrounded.
  5. Ground yourself before removing a new control from its packaging. Return old or new controls to their packaging before touching anything ungrounded.

Applies to: Indoor units with integrated control module (EEV air handlers)

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 3. Written in our own words; check the manual for your exact model.

Use only R-32 / R-410A rated pipes, flare nuts and tools

Heat pump · FTXM-W/V

Materials made for R-22 can fail under R-32 or R-410A pressure and cause a refrigerant cycle failure.

  1. Use pipes, flare nuts and tools intended only for R-32 / R-410A.
  2. Do not use R-22 materials on these models.

Applies to: R-32 / R-410A models

Source: SiUS042113EA service manual, p. 8. Written in our own words; check the manual for your exact model.

Using conduit and entry ports

Heat pump · DX6VS, DZ6VS, DZ6VSA

Power and control cables use conduit. Elbow conduit uses a field-supplied elbow with a conduit plate. The caution label on the insulation sheet must be replaced if damaged. Route conduit along the unit so it is not stepped on.

  1. Use conduit for power supply cables.
  2. Route conduit along the unit with an elbow socket or similar so it cannot be stepped on.
  3. Make sure wiring is not pinched by the front panel, then close the panel firmly.
  4. Replace the caution label on the insulation sheet if damaged or peeled off.

Applies to: Outdoor unit power and control wiring entry

Source: Daikin DX6VS/DZ6VS installation manual (3P731493-1), p. 20-21. Written in our own words; check the manual for your exact model.

Warning, caution, note and reference icons

Heat pump · FTXM-W/V

The manual marks text with four icons. Warning means danger of personal injury. Caution means the work may damage equipment, lose data, give an unexpected result or force a restart of a procedure. Note is useful but not essential, such as tips. Reference points to other pages with more detail.

Applies to: FTXM-W/V wall mounted indoor and RXM outdoor units

Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 16. Written in our own words; check the manual for your exact model.

Wet-hand, cleaning and grounding precautions

Heat pump · FTXM-W/V

Water near live electrical parts can cause shock. Humid or wet sites need proper earthing.

  1. Do not repair electrical components with wet hands.
  2. Do not wash the unit with water.
  3. Provide earth/grounding when working in a humid or wet location.
  4. Turn off the power switch and unplug the unit before cleaning.
  5. Use proper tools to avoid injury from the fast-spinning internal fan.

Applies to: Indoor and outdoor units

Source: SiUS042113EA service manual, p. 8. Written in our own words; check the manual for your exact model.

Work at height safety

Heat pump · FTXM-W/V

Work above about 2 m (6.5 ft) can lead to falls without proper protection.

  1. Wear a safety helmet, gloves and a safety belt when working more than 2 m (6.5 ft) high.

Applies to: Installation and service at height

Source: SiUS042113EA service manual, p. 8. Written in our own words; check the manual for your exact model.

Auto-restart after power failure

Mini-split · FTXM-W/V

If power is lost during operation, even briefly, the unit restarts in the same mode after power returns. The 3-minute standby function delays the restart by about 3 minutes.

Applies to: FTXM-W/V indoor and outdoor units

Source: Daikin FTXM-W/V service manual, p. 70. Written in our own words; check the manual for your exact model.

Check for software update

Mini-split · Daikin ONE+

The thermostat shows either that a software update is found or that no update is available.

  1. Open check for update.
  2. If an update is found, follow the prompts to install it.
  3. If none is found, select dismiss.

Applies to: Daikin ONE+ thermostat software

Source: Daikin ONE+ and ONE Touch homeowner settings menu outline, p. 2. Written in our own words; check the manual for your exact model.

CLEAN operation behavior and stop

Mini-split · FTXM-W/V

CLEAN dries the indoor unit after COOL or DRY to reduce condensation. It uses FAN and HEAT operation, so indoor temperature and humidity may not feel as set. A short COOL or DRY run may not trigger CLEAN. CLEAN does not run when the unit is turned off by OFF TIMER or by smartphone.

  1. To stop CLEAN midway, press the ON/OFF button twice.
  2. If CLEAN is not wanted, set automatic CLEAN to OFF in menu 2.

Applies to: Wall mounted FTXM-W/V CLEAN operation

Source: Daikin FTXM-W/V service manual, pp. 58. Written in our own words; check the manual for your exact model.

Connector map for indoor control PCB (A1P) and outdoor main PCB (A1P)

Mini-split · FTXM-W/V

Indoor control PCB A1P connects the DC fan motor (S200), swing motors (S400), indoor heat exchanger thermistor (S501), humidity sensor PCB (S600), INTELLIGENT EYE sensor PCB (S602), display/signal receiver PCB (S800) and wireless LAN PCB (S801). Outdoor main PCB A1P connects the electronic expansion valve coil (S20), overload protector and high pressure switch (S40), outdoor DC fan motor (S70), four way valve (S80), outdoor thermistors (S90), liquid pipe thermistor (S97) and compressor leads (U, V, W).

  1. Use the connector labels on the board to identify the correct plug before disconnecting any harness.
  2. Check the thermistor and high pressure switch connectors (S90, S97, S40) when diagnosing sensor or pressure faults.

Applies to: FTXM-W and FTXM-V indoor units; 09/12 class and 18/24 class outdoor units

Source: Daikin FTXM-W/V service manual, p. 27, p. 31. Written in our own words; check the manual for your exact model.

Do not cut outdoor PCB jumpers; replace the board instead

Mini-split · FTXM-W/V

Outdoor main PCB jumpers J4, J5 and J9 are needed for the electronic circuit. Cutting one by accident can cause improper operation. If a jumper has been cut unintentionally, replace the PCB.

  1. Check the jumper pattern on the outdoor main PCB (J4, J5, J9) before handling the board.
  2. If a jumper was cut by mistake, replace the PCB rather than trying to repair the trace.
  3. Use the facility setting, warmer airflow and drain pan heater jumper pages in the manual before changing any jumper.

Applies to: Outdoor main PCB A1P, 09/12 class and 18/24 class

Source: Daikin FTXM-W/V service manual, p. 31-32. Written in our own words; check the manual for your exact model.

Fuse ratings on the indoor and outdoor control boards

Mini-split · FTXM-W/V

Use these fuse ratings when a board shows no power. Indoor power supply PCB (A2P) has F1U at 3.15 A, 250 V. Outdoor main PCB (A1P) has FU1 and FU2 at 3.15 A, 250 V, and FU3 at 30 A, 250 V.

  1. Check the fuse on the indoor power supply PCB (F1U) and the outdoor main PCB (FU1, FU2, FU3) with a meter before replacing the board.
  2. Replace each fuse only with the same rating and voltage listed above.

Applies to: Indoor power supply PCB A2P and outdoor main PCB A1P

Source: Daikin FTXM-W/V service manual, p. 28, p. 31-32. Written in our own words; check the manual for your exact model.

Hot-start function delays cold blow on heating start

Mini-split · FTXM-W/V

On heating start, defrost start, or thermostat ON, the indoor heat exchanger temperature is checked. Airflow is stopped or greatly reduced until the coil is warm enough. Do not treat the delay as a fault.

Applies to: FTXM-W/V indoor unit in heating mode

Source: Daikin FTXM-W/V service manual, p. 70. Written in our own words; check the manual for your exact model.

Indoor and outdoor board status LEDs

Mini-split · FTXM-W/V

Indoor display board LEDs: H1P operation (green), H2P timer (yellow), H3P CLEAN operation (green), H4P INTELLIGENT EYE (green), H5P wireless LAN connection (yellow). Outdoor main PCB has LEDA, a service monitor LED (green).

  1. Compare the indoor LED pattern on the display/signal receiver PCB (A3P) with the operating state of the unit.
  2. Use the outdoor service monitor LED (LEDA) to check the outdoor board status during diagnosis.

Applies to: Indoor display/signal receiver PCB A3P and outdoor main PCB A1P

Source: Daikin FTXM-W/V service manual, p. 29, p. 31. Written in our own words; check the manual for your exact model.

Indoor unit ON/OFF switch operation

Mini-split · FTXM-W/V

The ON/OFF switch on the indoor unit display toggles operation. It is used when the remote controller is missing or has no battery.

  1. Press the ON/OFF switch once to start operation. Press it again to stop.
  2. To force cooling, press and hold the ON/OFF switch for 5 to 9 seconds while the unit is not operating.
  3. Holding the switch 10 seconds or more does not start forced cooling.

Applies to: FTXM-W/V indoor unit

Source: Daikin FTXM-W/V service manual, p. 70. Written in our own words; check the manual for your exact model.

Indoor unit signal receiving sound

Mini-split · FTXM-W/V

The indoor unit beeps when it receives a command from the remote controller. This confirms the signal, not a fault.

Applies to: FTXM-W/V indoor unit

Source: Daikin FTXM-W/V service manual, p. 70. Written in our own words; check the manual for your exact model.

Leak handling and refrigerant gas hazard

Mini-split · FTXM-W/V

If a leak cannot be found and work must stop, prevent refrigerant from entering the room. Refrigerant can form toxic gas when it touches flames.

  1. Find and repair the leak before charging.
  2. If the leak cannot be found, pump down and close the service valve.
  3. Keep flames and heaters away from refrigerant gas.

Applies to: Refrigerant leaks

Source: Daikin FTXM-W/V service manual, p. 14. Written in our own words; check the manual for your exact model.

Read the communicating equipment list

Mini-split · Daikin ONE+

The equipment list shows the indoor and outdoor units with model number, serial number and unit type.

  1. Open the equipment menu.
  2. Check the indoor unit and outdoor unit model # and serial # entries.

Applies to: Daikin ONE+ equipment list

Source: Daikin ONE+ and ONE Touch homeowner settings menu outline, p. 2. Written in our own words; check the manual for your exact model.

Remote sensors

Mini-split · Daikin ONE+

Up to 8 remote sensors can be added, each showing temperature and humidity values.

  1. Open the remote sensors menu.
  2. Select a sensor and enter its name.
  3. Select save.

Applies to: Daikin ONE+ remote sensors

Source: Daikin ONE+ and ONE Touch homeowner settings menu outline, p. 2-3. Written in our own words; check the manual for your exact model.

Set a second indoor unit address in the same room

Mini-split · FTXM-W/V

Used when two indoor units share one room. One unit and its remote controller are given a different address. The remote controller address jumper (J4) must be cut first. If a jumper is cut by mistake, replace the remote controller.

  1. Remove the remote controller battery cover and cut the address jumper (J4).
  2. Press the center of Temp and Mode on the remote controller together.
  3. Select A with Temp, then press Mode to enter address setting. The indoor operation lamp blinks for 1 minute.
  4. While the lamp blinks, press the indoor unit ON/OFF switch.
  5. If not completed while the lamp blinks, start again from the beginning.
  6. Press Mode on the remote controller for 5 seconds to return to normal mode.

Applies to: Two FTXM-W/V indoor units in one room

Source: SiUS042113EA Inverter Pair service manual, p. 164. Written in our own words; check the manual for your exact model.

Use only R-32 / R-410A tools and parts

Mini-split · FTXM-W/V

Pipes, flare nuts and tools must be made for R-32 or R-410A. R-22 tools and materials must not be used on these models.

  1. Use pipes, flare nuts and tools intended only for R-32 or R-410A.
  2. Do not add air or any gas other than the specified refrigerant to the system.
  3. Replace electrical components only with parts specified by Daikin.

Applies to: R-32 / R-410A models

Source: Daikin FTXM-W/V service manual, pp. 8-9, 14. Written in our own words; check the manual for your exact model.

WEEKLY TIMER overview

Mini-split · FTXM-W/V

Up to 4 timer reservations can be stored per day, 28 per week. Each reservation can set ON/OFF, time and temperature. Using ON-ON-ON-ON style entries lets the unit change mode and temperature on a schedule. Using OFF-only entries gives an automatic turn-off time each day.

Applies to: WEEKLY TIMER on wall mounted FTXM-W/V indoor unit

Source: Daikin FTXM-W/V service manual, p. 51. Written in our own words; check the manual for your exact model.

WEEKLY TIMER priority and clock notes

Mini-split · FTXM-W/V

WEEKLY TIMER and ON/OFF TIMER cannot run together. If an ON/OFF TIMER is set while WEEKLY TIMER is active, the ON/OFF TIMER takes priority and WEEKLY TIMER goes to standby. When the ON/OFF TIMER expires, WEEKLY TIMER becomes active again. A breaker trip or power failure makes the indoor clock inaccurate, so reset the clock.

Applies to: Indoor unit clock and timer priority

Source: Daikin FTXM-W/V service manual, p. 53. Written in our own words; check the manual for your exact model.

Cascade pump may run with no hot water demand

Water heater · Mega-Q

The cascade pump can start even when hot water is not being supplied. This is anti-freeze protection and is normal.

Applies to: Cascade unit

Source: Mega-Q installation manual, p. 43. Written in our own words; check the manual for your exact model.

Cold-weather shutdown: drain the cascade unit

Water heater · Mega-Q

If the breaker is turned off while outdoor air is below freezing, water left in the cascade unit can freeze and damage the unit and piping.

  1. Drain the water from inside the cascade unit before shutting off the power circuit breaker in freezing conditions.

Applies to: Mega-Q cascade unit

Source: Daikin Mega-Q installation manual, p. 3. Written in our own words; check the manual for your exact model.

Do not use conventional refrigerant tools

Water heater · Mega-Q

Do not use gauge manifolds, charge hoses, gas leak detectors, reverse flow check valves, refrigerant charge bases, vacuum gauges or recovery equipment made for conventional refrigerants. Mixing conventional refrigerant or oil into R410A will degrade it.

  1. Use tools rated for R410A only.
  2. Keep the R410A circuit free of mineral oil, moisture and air.

Applies to: Mega-Q R410A circuit

Source: Daikin Mega-Q installation manual, p. 3. Written in our own words; check the manual for your exact model.

Install the cascade unit on the left

Water heater · Mega-Q

Placing the cascade unit on the left of the heat source unit is recommended. Other layouts make refrigerant piping, water piping and wiring harder.

  1. Place the cascade unit on the left side of the heat source unit where possible.

Applies to: Mega-Q layout

Source: Daikin Mega-Q installation manual, p. 3. Written in our own words; check the manual for your exact model.

Reading the subdivision code on the cascade unit

Water heater · Mega-Q

The subdivision code is not shown on the remote controller. Read it on the 7-segment display through the inspection port of the cascade unit electrical box cover.

  1. Remove the cascade unit electrical box cover inspection port cover.
  2. Read the subdivision code on the 7-segment display.

Applies to: Cascade unit

Source: Daikin Mega-Q installation manual, p. 50. Written in our own words; check the manual for your exact model.

Sensor connection mismatch stops hot water supply

Water heater · Mega-Q

Sensor harness labels must match at both ends. A mismatch between the tank control board and the storage tank sensor connectors prevents hot water supply operation.

  1. Check the identification label on each relay harness connector.
  2. Check the matching identification label on each sensor device-side connector.
  3. Correct any mismatched connection before starting the unit.

Applies to: Mega-Q hot water generation system, water temperature sensors

Source: Daikin Mega-Q installation manual, p. 65 of 68. Written in our own words; check the manual for your exact model.

Water is non-potable

Water heater · Mega-Q

Hot water made by Mega-Q is not drinking water. Scale build-up in the tank and piping wear can change water quality over time.

  1. Do not use the generated hot water for drinking.
  2. Use tap water that meets local water quality rules to protect condensers and piping.
  3. Install a strainer (60 mesh or finer) in the water piping.

Applies to: Mega-Q water circuit

Source: Daikin Mega-Q installation manual, p. 2, 3, 6. Written in our own words; check the manual for your exact model.

Same tips in your pocket

The HVACopedia app has these tips, every error code and the settings tables offline.

Open the app

For licensed technicians. Installer menus, test modes and access codes change settings that affect safety; only use them if you are trained on the appliance and understand the result. Gas, electrical and refrigerant work must be done by a qualified, licensed person, and the manufacturer’s manual for the exact model and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.