Daikin · Heat pump · Other
Four-way valve energising and OFF delay
What happens, in order
- Energise the four-way valve in heating; keep it off in cooling, dry and defrost.
- When heating stops, keep the valve energised for a delay so it does not click as it switches off.
- In heating with outdoor temperature below -9°C (15.8°F), the delay is shorter.
Timings and thresholds
| Item | Value |
|---|---|
| Four-way valve OFF delay after operation stops | 160 seconds |
| OFF delay in heating when outdoor temperature is below -9°C (15.8°F) | 10 seconds |
Applies to: FTXM-W/V wall mounted heat pump
More Daikin heat pump sequences
- 3-minute standby before restart · Startup
- Commissioning and test run · Startup
- Five-step commissioning set-up · Startup
- Preheating control before inverter start (open phase) · Startup
- System start-up procedure with evacuation and checks · Startup
- Triple evacuation method (recommended) · Pump/purge
- 3-D airflow auto-swing order · Other
- Commissioning sequence in the app · Other
Related
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Daikin FTXM-W/V service manual, p. 76. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.