Daikin · Mini-split troubleshooting
Unit does not run at all
What is going on
Nothing starts from the remote or the unit switch.
Likely causes
- No power or wrong voltage
- Indoor and outdoor units not a matching pair
- Outdoor temperature outside the operating limit
- Wrong remote address
Check in this order
- Turn off power at the disconnect before opening the unit or touching connectors. Check rated voltage is present.
- Confirm the indoor type matches the outdoor.
- Check outdoor temperature against the operation limit page.
- Check remote and indoor address settings.
- Read any code with the service check.
Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin FTX-W service manual SiUS042228E, General problem symptoms 1, p.63. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.