Daikin · Mini-split troubleshooting

Check thermistors by resistance

Daikin FTX-W

What is going on

Resistance chart, 20 kohm at 25 C (77 F), B 3950 K.

Check in this order

  1. Unplug the thermistor and measure across the pins.
  2. Compare with chart 0 C (32 F) 65.93 kohm, 10 C (50 F) 39.99, 20 C (68 F) 25.02, 25 C (77 F) 20.00, 30 C (86 F) 16.10, 40 C (104 F) 10.62, 50 C (122 F) 7.176; -20 C (-4 F) 197.8.
  3. Replace the thermistor as an assembly if it does not match.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin FTX-W service manual SiUS042228E, Thermistor resistance check 5.1, p.111. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.