Daikin · Mini-split troubleshooting

Check expansion valve

Daikin FTX-W

What is going on

Connector S20 test.

Check in this order

  1. Check the EV connector is seated on the PCB.
  2. Cycle power and listen for the EV clicking.
  3. If no click, unplug and check continuity from pin 5 to pins 1, 2, 3 and 4. No continuity: bad coil. Continuity good: outdoor PCB is bad.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin FTX-W service manual SiUS042228E, Electronic expansion valve check 5.4, p.113. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.