Daikin · Mini-split troubleshooting
Check expansion valve
What is going on
Connector S20 test.
Check in this order
- Check the EV connector is seated on the PCB.
- Cycle power and listen for the EV clicking.
- If no click, unplug and check continuity from pin 5 to pins 1, 2, 3 and 4. No continuity: bad coil. Continuity good: outdoor PCB is bad.
Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin FTX-W service manual SiUS042228E, Electronic expansion valve check 5.4, p.113. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.