Daikin · Mini-split troubleshooting

Check power module and diode bridge for shorts

Daikin FTX-W

What is going on

Resistance checks on a de-energized unit.

Check in this order

  1. Wait until the bus voltage is near 0 V. FU2 to DC- must read 50 V or less before touching anything.
  2. Diode bridge (DB1) infinite or under 1 kohm between pins means a short.
  3. Power module unplug the compressor harness and measure U, V, W against the (+) and (-) terminals. Good is several kohm to several Mohm; 0 ohm or infinite is bad.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin FTX-W service manual SiUS042228E, Main circuit short check 5.12 to 5.14, p.119. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.