Check compressor and inverter with the analyzer
What is going on
Tell a bad compressor from a bad board. Tool is analyzer RSUK0917C.
Check in this order
- Power off and wait for the DC bus capacitor to drop to 10 VDC or less.
- Unplug the compressor leads and connect them to the analyzer. Keep U, V, W from touching.
- Power on, set FAN mode, press Temp up, Temp down and Mode together, pick T, press Mode.
- All six LEDs even compressor is bad. Uneven: check the power module.
- Re-crimp the FASTON terminals afterward.
Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin FTX-W service manual SiUS042228E, Inverter analyzer check 5.7, p.116. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.