Daikin · Mini-split troubleshooting
Check outdoor fan motor
What is going on
Voltage test at connector S70.
Check in this order
- Power off. Unplug S70.
- Check about 320 VDC on pins 4-7, 15 VDC on 4-3, 0 to 6.5 VDC on 4-2.
- Reconnect with power off. Turn the fan by hand one turn and look for 4 pulses (0 to 15 VDC) on pins 4-1.
- Bad voltage at step 2 replace outdoor PCB. Pulses missing: replace the fan motor.
Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin FTX-W service manual SiUS042228E, Outdoor fan motor check 5.8, p.117. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.