Daikin · Mini-split troubleshooting

Check outdoor fan motor

Daikin FTX-W

What is going on

Voltage test at connector S70.

Check in this order

  1. Power off. Unplug S70.
  2. Check about 320 VDC on pins 4-7, 15 VDC on 4-3, 0 to 6.5 VDC on 4-2.
  3. Reconnect with power off. Turn the fan by hand one turn and look for 4 pulses (0 to 15 VDC) on pins 4-1.
  4. Bad voltage at step 2 replace outdoor PCB. Pulses missing: replace the fan motor.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin FTX-W service manual SiUS042228E, Outdoor fan motor check 5.8, p.117. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.