Daikin · Mini-split troubleshooting

Runs but does not cool or heat

Daikin FTX-W

What is going on

Compressor runs but the room does not change.

Likely causes

  • Wiring or piping crossed between indoor and outdoor
  • Loose thermistor
  • Expansion valve fault
  • Low refrigerant

Check in this order

  1. Check interconnect wiring and piping.
  2. Confirm thermistors are seated.
  3. In cooling, check liquid line temperature to see if the expansion valve is working.
  4. Check service port pressures and running current for refrigerant shortage.
  5. Read any code with the service check.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin FTX-W service manual SiUS042228E, General problem symptoms 1, p.63. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.