Daikin · Mini-split troubleshooting
Runs but does not cool or heat
What is going on
Compressor runs but the room does not change.
Likely causes
- Wiring or piping crossed between indoor and outdoor
- Loose thermistor
- Expansion valve fault
- Low refrigerant
Check in this order
- Check interconnect wiring and piping.
- Confirm thermistors are seated.
- In cooling, check liquid line temperature to see if the expansion valve is working.
- Check service port pressures and running current for refrigerant shortage.
- Read any code with the service check.
Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin FTX-W service manual SiUS042228E, General problem symptoms 1, p.63. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.