Daikin · Mini-split troubleshooting
Read fault codes from the remote, method 2
What is going on
Full service check mode on the ARC466A37.
Check in this order
- Press Temp up, Temp down and Mode together. SC shows.
- Select SC and press Mode. The left digit blinks.
- Change it until you hear two beeps or a long beep. Two beeps: left digit is right, right digit is not. Long beep: both right.
- Press Mode, then step the right digit until a long beep. The displayed number is the code.
- Hold Mode 5 seconds to exit.
Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin FTX-W service manual SiUS042228E, Service diagnosis 3.2, p.66. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.