Daikin · Mini-split troubleshooting
Read fault codes from the remote, method 1
What is going on
Quick way to pull a stored code on the ARC466A37.
Check in this order
- Hold Timer Cancel for 5 seconds. 00 shows.
- Press Timer Cancel repeatedly. Short beep or two beeps means not the code. A long beep means that is the code.
- Hold Timer Cancel 5 seconds to exit, or wait 60 seconds.
- Not all codes show this way. Use method 2 if nothing matches.
Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin FTX-W service manual SiUS042228E, Service diagnosis 3.1, p.65. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.