Pump down before moving or scrapping the unit
What is going on
Recover refrigerant into the outdoor unit.
Check in this order
- Take the caps off the liquid and gas stop valves.
- Start forced cooling.
- After 5 to 10 minutes close the liquid valve with a hex wrench.
- After 2 to 3 minutes close the gas valve and stop forced cooling.
- Put the caps back.
Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin FTX-W service manual SiUS042228E, Pump down operation, p.123. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.