Daikin · Mini-split troubleshooting

Pump down before moving or scrapping the unit

Daikin FTX-W

What is going on

Recover refrigerant into the outdoor unit.

Check in this order

  1. Take the caps off the liquid and gas stop valves.
  2. Start forced cooling.
  3. After 5 to 10 minutes close the liquid valve with a hex wrench.
  4. After 2 to 3 minutes close the gas valve and stop forced cooling.
  5. Put the caps back.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin FTX-W service manual SiUS042228E, Pump down operation, p.123. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.