Vertical exhaust and combustion air termination layout

NDF

What is going on

Terminal layout for vertical venting through a roof.

Check in this order

  1. No termination fitting is needed when venting vertically through a roof.
  2. Set the exhaust pipe end 12 in (305 mm) higher than the combustion air intake terminal.
  3. Use a pair of medium or long sweep 90 degree elbows pointing downward on the combustion air intake.
  4. Locate the combustion air inlet at least 12 in (305 mm) above grade or expected snow level and 12 in (305 mm) below the exhaust outlet.
  5. Extend the exhaust pipe through the roof at least 18 in (457 mm) above any obstruction within an 18 in (457 mm) horizontal distance.
  6. Insulate all venting extending 24 in (610 mm) or more to the outside.

Applies to: NDF600 series furnaces, vertical venting

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NDF installation and operation manual, p. 31. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.