Vertical exhaust and combustion air termination layout
What is going on
Terminal layout for vertical venting through a roof.
Check in this order
- No termination fitting is needed when venting vertically through a roof.
- Set the exhaust pipe end 12 in (305 mm) higher than the combustion air intake terminal.
- Use a pair of medium or long sweep 90 degree elbows pointing downward on the combustion air intake.
- Locate the combustion air inlet at least 12 in (305 mm) above grade or expected snow level and 12 in (305 mm) below the exhaust outlet.
- Extend the exhaust pipe through the roof at least 18 in (457 mm) above any obstruction within an 18 in (457 mm) horizontal distance.
- Insulate all venting extending 24 in (610 mm) or more to the outside.
Applies to: NDF600 series furnaces, vertical venting
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NDF installation and operation manual, p. 31. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.