Adjust gas valve offset using a digital manometer
What is going on
Alternative to the analyzer method. Measure the offset pressure at the offset port at low fire.
Check in this order
- Loosen the offset pressure port screw two turns to open the port.
- Connect a digital manometer to the offset port. On dual port manometers, use the positive side.
- Put the furnace in heating mode and set it to MIN (low fire).
- Read the offset and compare it with Table 3 for the model, altitude and gas type.
- If the offset is out of range, remove the screw-on cover and turn the set screw no more than 1/4 turn: clockwise raises the offset, counterclockwise lowers it.
- At high fire, do not check the offset and never adjust the gas valve.
Applies to: NPF700 U and H models, gas conversion or altitude change
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NPF installation and operation manual, p. 137-138. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.