Alternate drain piping using PVC or CPVC

NDF

What is going on

The factory rubber hoses at the trap can be used with rigid PVC or CPVC drain piping. Match the hose to the pipe size and seal with a coupling or bushing.

Check in this order

  1. Install the condensate trap per this manual.
  2. For 1/2 in. PVC, use the 1/2 in. hose. For 3/4 in. CPVC, use the 5/8 in. hose.
  3. Slide the hose over the trap outlet and cut it flush with the outlet end.
  4. Fit a 1/2 in. PVC coupling or bushing over the 1/2 in. hose, or a 3/4 in. CPVC coupling or bushing over the 5/8 in. hose, for a watertight seal that still allows trap removal.
  5. Optionally secure a strip of strapping around the drain using the existing trap screws.

Applies to: NDF condensate drain system

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NDF Installation and Operation Manual, p. 46. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.