Navien · Furnace troubleshooting

Adjust gas/air ratio using a combustion analyzer

NPF

What is going on

Set the CO2 with a combustion analyzer, which the manual recommends. Confirm high altitude and gas type first.

Check in this order

  1. Turn on the gas and water supply (if a supply water valve is used).
  2. Remove the analyzer port cap and insert the analyzer probe into the port.
  3. Put the furnace in heating mode and set it to MIN (low fire).
  4. Read the CO2 and compare it with Table 2 for the model, altitude and gas type.
  5. If CO2 is off by more than 1.0%, turn the gas valve set screw using a 5/32 in or 4 mm Allen wrench. The screw is under a screw-on cover, so remove that first.
  6. Turn the screw no more than 1/4 turn clockwise raises CO2, counterclockwise lowers it.
  7. Put the furnace in heating mode and set it to MAX (high fire).
  8. Read CO2 at high fire. If it does not match Table 2, do not adjust the gas valve; check for the correct gas orifice instead.
  9. Once CO2 or offset values are confirmed, apply the conversion labels next to the rating plate.
  10. Reinstall the upper front cover, seat it fully against the furnace, and tighten the three knobs clockwise.

Applies to: NPF700 furnaces, gas conversion or altitude change

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NPF installation and operation manual, p. 136-137. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.