Vent termination clearances in the United States
What is going on
Minimum distances for the vent exhaust terminal in the United States.
Check in this order
- Keep the bottom of the terminal at least 12 in (305 mm) above grade.
- Do not terminate over public walkways or where condensate or vapor could create a nuisance or hazard.
- Keep the terminal 4 ft (1.2 m) below, 4 ft (1.2 m) horizontally from, or 1 ft (305 mm) above any door, window, soffit, under eave vent or gravity air inlet.
- Keep at least 4 ft (1.2 m) horizontal clearance from electric meters, gas meters, regulators and relief equipment.
- Locate the terminal 3 ft (0.91 m) above any mechanical air inlet within 10 ft (3 m); a dryer or furnace make-up air inlet counts as a forced air inlet.
- Keep the terminal at least 3 ft (0.91 m) from an inside corner formed by two exterior walls.
- For overhangs, keep at least 1 ft (0.3 m) vertical clearance for each foot horizontal, up to 6 ft (1.8 m).
Applies to: NDF600 series furnaces, installations in the United States
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NDF installation and operation manual, p. 29. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.