Navien · Furnace troubleshooting

Vent termination clearances in the United States

NDF

What is going on

Minimum distances for the vent exhaust terminal in the United States.

Check in this order

  1. Keep the bottom of the terminal at least 12 in (305 mm) above grade.
  2. Do not terminate over public walkways or where condensate or vapor could create a nuisance or hazard.
  3. Keep the terminal 4 ft (1.2 m) below, 4 ft (1.2 m) horizontally from, or 1 ft (305 mm) above any door, window, soffit, under eave vent or gravity air inlet.
  4. Keep at least 4 ft (1.2 m) horizontal clearance from electric meters, gas meters, regulators and relief equipment.
  5. Locate the terminal 3 ft (0.91 m) above any mechanical air inlet within 10 ft (3 m); a dryer or furnace make-up air inlet counts as a forced air inlet.
  6. Keep the terminal at least 3 ft (0.91 m) from an inside corner formed by two exterior walls.
  7. For overhangs, keep at least 1 ft (0.3 m) vertical clearance for each foot horizontal, up to 6 ft (1.8 m).

Applies to: NDF600 series furnaces, installations in the United States

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NDF installation and operation manual, p. 29. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.