Navien · Furnace troubleshooting

Vent termination clearances in Canada

NDF

What is going on

Minimum distances for the vent exhaust terminal in Canada.

Check in this order

  1. Do not terminate directly above a paved sidewalk or driveway between two single-family dwellings that serves both.
  2. Keep at least 7 ft (2.1 m) above a paved sidewalk or driveway on public property.
  3. Keep at least 6 ft (1.8 m) from any mechanical air supply inlet to a building.
  4. Above a meter/regulator assembly, stay at least 3 ft (0.91 m) horizontally from the regulator centerline.
  5. Keep at least 3 ft (0.91 m) from any service regulator vent outlet.
  6. Keep at least 12 in (305 mm) above grade or anticipated snow level.
  7. Keep at least 12 in (305 mm) from any door, window or non-mechanical air supply inlet.
  8. Keep at least 12 in (305 mm) from the combustion air inlet of any other appliance.
  9. Do not terminate underneath a veranda, porch or deck unless it is fully open on at least two sides beneath the floor and the vent top is more than 12 in (305 mm) below its underside.

Applies to: NDF600 series furnaces, installations in Canada

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NDF installation and operation manual, p. 29. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.