Navien · Furnace troubleshooting

Vent sizing and length checks

NDF

What is going on

Confirm the vent system is within length limits before installation.

Check in this order

  1. Size combustion air and exhaust piping per the vent length table.
  2. Keep total vent length at least 15 equivalent ft (4.6 m).
  3. Count all termination fittings and the concentric vent as straight pipe.
  4. Do not common vent with any other appliance.
  5. Do not connect the furnace to a chimney or flue serving other appliances or a solid fuel appliance.
  6. Do not vent up a chimney serving another appliance, or in a chase with other gas or fuel pipes, unless clearances to combustibles can be maintained.

Applies to: NDF600 series furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NDF installation and operation manual, p. 25, 26. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.