Navien · Furnace troubleshooting

Vent pipe check if the furnace will not start after vent work

NPF

What is going on

Use this check when the furnace will not run after the vent is connected, or when the vent detector reports a fault.

Likely causes

  • Vent pipe not fully seated in the collar
  • Wrong vent pipe size
  • Damaged vent pipe
  • Vent joint leaking or disconnected
  • Vent blocked

Check in this order

  1. Look for E762 on the front control panel display.
  2. Re-seat the vent pipe to the full 2-3/4 in (70 mm) depth.
  3. Check the pipe size and condition.
  4. Recheck all joints with a bubble test.
  5. Check the intake and exhaust terminations for snow, ice or other blockage.
  6. Restart the furnace and confirm it runs.

Applies to: NPF furnace vent connection

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NPF installation and operation manual, p. 62. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.