Navien · Furnace troubleshooting

Support and drainage of horizontally installed furnace

NPF

What is going on

The furnace must drain correctly when installed on its side, so the full length must be supported.

Check in this order

  1. Support the entire length of the furnace when used in horizontal position.
  2. Install a drain pan and stands under the furnace to catch leaks, covering the full area under the unit.
  3. Add a center stand so the furnace does not deform under its weight.
  4. For suspended installs, use 3/8 in threaded rod (6 places) and 2 x 2 x 3/8 in angle iron (3 places), tilted outward for front cover and blower removal.
  5. Use a support deck or board to carry the furnace weight.

Applies to: NPF horizontal and suspended furnace installs

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NPF installation and operation manual, p. 75-76. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.