Navien · Furnace troubleshooting
Spacing vent terminations for multiple furnaces
What is going on
Each furnace needs its own dedicated combustion air intake and exhaust. Common venting is not allowed.
Likely causes
- Common venting of two or more furnaces
Check in this order
- Do not common-vent furnaces. Each furnace needs dedicated intake and exhaust.
- If more than two furnaces are installed close together, keep each additional intake and exhaust termination set at least 12 in (305 mm) apart.
- In Canada, a 105,000 Btu/hr unit requires 3 ft (915 mm) spacing.
- Use the standard horizontal or standard vertical multiple venting arrangements shown in the manual (Figures 12 and 13).
Applies to: Multiple furnace installations
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NDF installation and operation manual, p. 33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.