Set manifold gas pressure (two-stage gas valve)

NDF

What is going on

Set low-fire and high-fire manifold pressure with a manometer on the outlet pressure boss. Always follow the values on the rating plate.

Check in this order

  1. Complete start-up and setup first. Turn off gas and power.
  2. Back the outlet pressure test screw out counterclockwise one turn maximum with a 3/32 in. Allen wrench, and attach a manometer hose (overlap 3/8 in., range at least 0 to 15 in. w.c.).
  3. Turn on gas and power. Energize the main solenoid by connecting R to W1. Do not energize HI.
  4. Remove the low outlet regulator adjust cover screw. Turn the plastic adjust screw clockwise to raise manifold pressure, counterclockwise to lower it. Set to the rating plate value and replace the cover screw.
  5. Energize the main solenoid and HI by connecting R/W1 and W1/W2. Remove the high outlet regulator cover screw. Adjust the same way to the rating plate value, then secure the cover screw.
  6. Turn off gas and power. Remove the hose and tighten the outlet pressure screw clockwise to at least 7 in-lb.
  7. Turn gas and power back on, energize the valve, and leak test the pressure boss screw with soap suds or leak solution.

Applies to: Two-stage gas valve manifold pressure

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NDF installation and operation manual, p. 51 to 52. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.