Navien · Furnace troubleshooting

Rotating the inducer and mounting pressure switches

NDF

What is going on

Rotate the inducer to suit the chosen flue orientation, then reinstall the pressure switches and hoses so condensate cannot reach the sensing hose.

Likely causes

  • Condensate draining into the pressure switch sensing hose, causing erratic operation
  • Openings between the blower compartment and the combustion compartment, causing incomplete combustion

Check in this order

  1. Loosen the collar clamp and raise the exhaust pipe for clearance if needed.
  2. Disconnect the inducer wire connection.
  3. Remove the 4 inducer screws.
  4. Remove the pressure switch assembly and pressure sensing hoses.
  5. Remove the inducer.
  6. Reverse the bands on the rubber drain coupling so the screws are reachable. Do not reverse the coupling itself, and make sure the directional arrow points away from the inducer.
  7. Remove the plastic cap on the side panel for the vent opening in use, and install a cap on any unused vent opening.
  8. Reinstall the inducer and pressure switch assembly in the correct orientation. Do not use a power tool.
  9. Mount the pressure switches above the front manifold drain and keep the sensing hoses above it, cut to length with no sags or traps.
  10. Rotate the drain coupling so the drain holes point 15 degrees down, and tighten the coupling band to the inducer.
  11. Complete the venting, mount the exhaust pipe and secure it to the collar.
  12. Secure or support the vent and intake to floor joists or rafters to prevent sagging and fatigue.
  13. Make sure the blower compartment is fully sealed from the burner compartment, and check that the combustion door gasket is in good condition.

Applies to: Inducer orientation changes and pressure switch mounting

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NDF installation and operation manual, p. 38-39. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.