Navien · Furnace troubleshooting
Propane gas supply and piping
What is going on
Propane pressure and piping checks from the manual.
Likely causes
- Propane odorant can fade, so a leak may not be smelled.
- Rust and soil can reduce odorant.
- Pipe dope that is not approved for propane can attack the joints.
Check in this order
- In basements, excavated areas or confined spaces, install a gas detecting warning device.
- Confirm propane pressure is 8 in WC to 13 in WC at the furnace manifold with all gas appliances running.
- Use two-stage regulation and check pressure drop between regulators and the appliance.
- Use only pipe dope approved for propane; do not use white lead compounds.
- Follow the propane tank maker's installation manual and the supplier's regulator settings.
Applies to: NPF700 hydro-furnace propane installations
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NPF installation and operation manual, p. 51. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.