Navien · Furnace troubleshooting
Preparing the vent and drain option
What is going on
Choose the vent and drain option first, then prepare the inducer, vent and intake connections and the trap location.
Check in this order
- Choose the vent and drain option using the inducer rotation section and Table 5.
- Remove the 3-1/2 in plastic exhaust vent cap if needed and cover any unused vent hole. Install the rubber grommet from the parts bag for the 2 in vent pipe, then connect the field-supplied vent pipe.
- If using 1-1/2 in or 3 in vent, make the transition as close to the unit as possible and on a vertical section.
- Support the exhaust vent before fitting it to the inducer. The inducer must not carry any weight of the venting system.
- Remove the air inlet cap if applicable, attach the intake fitting with gasket to the furnace panel and connect the 2 in intake pipe.
- Remove the two plastic caps on the blower division and the one on the side panel if applicable.
- Mount the condensate trap on the side panel inside or outside the blower compartment for upflow and downflow, using the two screws from the parts bag. For horizontal positions, mount it on the exterior side panels.
Applies to: Upflow, downflow and horizontal orientations
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NDF installation and operation manual, p. 38. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.