Navien · Furnace troubleshooting

Measure total external static pressure

NPF

What is going on

Total external static is the return reading (negative) plus the supply reading (positive), with clean filters in place.

Likely causes

  • Static above the rating plate maximum.
  • Closed dampers, registers, undersized or oversized duct.
  • Air conditioner coil or electronic air cleaner not included in the reading.

Check in this order

  1. Install clean filters in the furnace.
  2. Measure return duct static at the furnace inlet with a draft gauge (negative pressure).
  3. Measure supply duct static (positive pressure).
  4. Add the two readings to get total external static. Example: -0.1 in WC return and +0.3 in WC supply gives 0.4 in WC.
  5. Include the coil or air cleaner in the reading if used with the furnace.
  6. Compare the result to the maximum on the rating plate.
  7. Check the temperature rise is within the rating plate range.
  8. Correct the duct system before continuing if static is too high.

Applies to: NPF700 hydro-furnace airflow setup

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NPF installation and operation manual, p. 52. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.