Navien · Furnace troubleshooting

Measure inlet gas pressure

NPF

What is going on

Licensed professional only. Furnace must have enough inlet gas pressure to run. Steps 2 to 7 are not on these pages.

Check in this order

  1. Shut off the manual gas valve on the gas supply line.
  2. Loosen the screw shown in the figure and connect a manometer to the pressure port.
  3. Zero the manometer before use.
  4. Reopen the manual gas valve and check all joints for leaks.
  5. Restart the furnace so the MAX setting runs the burner and fan at full capacity.
  6. At maximum firing rate, read the inlet gas pressure and confirm it is within the range for the gas type.
  7. Reinstall the upper front cover, seat it fully against the furnace, and tighten the three knobs clockwise.

Applies to: NPF700 hydro-furnace inlet gas pressure check

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NPF installation and operation manual, p. 49-50. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.