Navien · Furnace troubleshooting

Installing the vent drain option

NDF

What is going on

Use when vent runs through an unconditioned space like an attic or crawl space to stop condensate building up in the inducer housing.

Likely causes

  • Vent passes through an unconditioned space
  • Condensate collects in the inducer housing during cycling

Check in this order

  1. Place a tee of the correct size (2 in or 3 in) in the horizontal run or vertical riser closest to the furnace.
  2. Fit a 5/8 in (15.9 mm) reducer bushing into the tee stem.
  3. Fit a piece of 5/8 in (15.9 mm) pipe at least 3 in (76 mm) long into the reducer as a nipple.
  4. Connect flexible drain tubing such as EPDM rubber or PVC to the nipple.
  5. Loop the drain tubing to form a trap.
  6. Connect the discharge end of the drain tube to the external condensate disposal system.

Applies to: NDF600 series furnaces with vent through unconditioned space

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NDF Forced Air Gas Furnace Installation and Operation Manual, p. 20. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.