Installing the pressure relief valve

NPF

What is going on

Install a 30 psi maximum pressure relief valve on the 3/4 in adapter on the upper cover. The valve must be ASME certified and installed only by a licensed professional.

Check in this order

  1. Apply thread seal tape to the threads of the valve before installing.
  2. Install the valve at the furnace outlet in the vertical position.
  3. Point the drain outlet horizontally out the side of the valve, then elbow down.
  4. Do not install any valve between the relief valve and the furnace.
  5. Run an outlet line toward the drain pan and make sure it drains properly.
  6. Do not reduce the discharge line or fit anything that restricts flow.
  7. Do not plug the relief valve.
  8. Keep the discharge from splashing hot water on an operator or the furnace.

Applies to: NPF700 all models

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NPF installation and operation manual, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.