Installing the condensate trap (upflow and downflow models)
What is going on
The trap mounts on the side of the furnace and can go on the right or left. The hose and overflow hose are marked right or left type. Water tank plugs must be removed from the overflow connection and the trap area cleared before the trap goes on.
Check in this order
- Turn each knob on the upper front cover counterclockwise, remove it, then pull the lower front cover back and off.
- Remove the rubber cap from the condensate drain hose. If water comes out, drain it onto a cloth.
- Install the condensate drain adapter on the furnace with the two screws.
- Connect the condensate drain hose to the adapter and fit the clip on the hose.
- Remove the plug from the overflow connection hole and the water tank, then remove the two screws from the trap installation area.
- Install the condensate hose and overflow hose, with their hose fasteners, on the condensate trap. Use the right type or left type to match the installation side.
- Mount the condensate trap on the furnace with the two screws from the Installation Parts Kit, then fit the fasteners on the drain adapter and overflow hose.
- Push the lower front cover on, line up the upper front cover in its original position, make sure it is fully seated, and turn the three knobs clockwise to tighten.
- Place the free end of the drain line into an appropriate drain.
- Prime the trap by pouring water into the exhaust vent until water flows out of the condensate drain.
Applies to: Upflow and downflow NPF700 models
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NPF installation and operation manual, p. 34-35. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.