Installing the combustion air inlet pipe drain

NPF

What is going on

Where moisture can enter the combustion air inlet pipe, condensation can form and drip inside the furnace. A short horizontal or vertical section of pipe with a condensate trap and drain prevents excess water entering the cabinet.

Likely causes

  • Excessive moisture entering the combustion air inlet pipe

Check in this order

  1. Install a short horizontal or vertical pipe section with a condensate trap and drain.
  2. Build the trap using a tee of the same diameter as the air inlet pipe.
  3. Connect a condensate drain hose to the trap.
  4. Only connect this drain to the furnace and evaporator coil condensate drain if both drains empty into an open section of pipe above the drain.

Applies to: Combustion air inlet pipe condensate

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NPF installation and operation manual, p. 69. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.