Installing the combustion air inlet pipe drain
What is going on
Where moisture can enter the combustion air inlet pipe, condensation can form and drip inside the furnace. A short horizontal or vertical section of pipe with a condensate trap and drain prevents excess water entering the cabinet.
Likely causes
- Excessive moisture entering the combustion air inlet pipe
Check in this order
- Install a short horizontal or vertical pipe section with a condensate trap and drain.
- Build the trap using a tee of the same diameter as the air inlet pipe.
- Connect a condensate drain hose to the trap.
- Only connect this drain to the furnace and evaporator coil condensate drain if both drains empty into an open section of pipe above the drain.
Applies to: Combustion air inlet pipe condensate
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NPF installation and operation manual, p. 69. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.