Navien · Furnace troubleshooting

Installation checklist: power supply and condensate drain

NPF

What is going on

Electrical and drain checks to complete before startup.

Check in this order

  1. Confirm the supply voltage is 120V.
  2. Confirm the furnace is hard wired to line voltage and properly grounded.
  3. If a direct power connection is used, install a power switch for end-user maintenance.
  4. Check the polarity of the electrical connection.
  5. Run a condensate drain line from the furnace to a drain or condensate pump.
  6. On upflow and downflow models, confirm the drain trap is filled with water.
  7. Slope the drain line toward the drain port.
  8. Check that all condensate drain hoses are connected and secured.
  9. Install an anti-freeze device if required.

Applies to: NPF700 series (all listed models)

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NPF installation and operation manual, p. 92-93. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.