Installation checklist: airflow and temperature records

NPF

What is going on

Readings to record at commissioning. Record duct static pressure and air temperature rise or drop at each operating point.

Check in this order

  1. Record duct static pressure at maximum heating operation.
  2. Record air temperature rise at maximum heating operation.
  3. Record air temperature rise at minimum heating operation.
  4. Record duct static pressure at maximum cooling operation.
  5. Record air temperature drop at maximum cooling operation.

Applies to: NPF700 series (all listed models)

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NPF installation and operation manual, p. 93. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.