Navien · Furnace troubleshooting

Install the condensate neutralizer kit

NPF

What is going on

Use the Navien neutralizer kit when condensate goes to a drain through neutralizing media, which raises the pH and protects the drain system and public sewer.

Likely causes

  • Local codes or the site require neutralized condensate

Check in this order

  1. Do not let exhaust flue gases pass through the neutralizer, as this can cause carbon monoxide poisoning.
  2. Mount the neutralizer on a wall or floor with the brackets supplied.
  3. Keep the neutralizer inlet and discharge closer to the floor than the condensate drain.
  4. Install an overflow bypass between the appliance and the neutralizer to stop backflow into the appliance.
  5. If the neutralizer is horizontal, rotate it so the outlet is the highest point.
  6. If it is vertical, make sure the outlet is higher than the inlet.
  7. Use corrosion resistant piping and secure it so it does not move.
  8. If more than one appliance feeds the neutralizer, size it correctly for the total load.

Applies to: NPF700 series with neutralizer disposal

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NPF installation and operation manual, p. 41. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.