Navien · Furnace troubleshooting
Horizontal exhaust and combustion air termination layout
What is going on
Terminal geometry for horizontal venting to keep flue gases from recirculating into the intake.
Check in this order
- Terminate the vent at least 8 in (203 mm) from the wall.
- Use a medium or long sweep 90 degree elbow pointing downward on the combustion air intake to keep out rain.
- Exhaust may end in a tee, 45 degree elbow, or medium or long sweep 90 degree elbow pointing within 45 degrees of downward, away from the intake.
- If clearance to grade cannot be met with straight-through piping, periscope the pipe up to 24 in (610 mm) using the same pipe size, counting the fittings and length in total vent length.
- If winter winds may blow flue gases back into the intake, raise the exhaust 18 to 24 in (457 to 610 mm) above the combustion air intake terminal.
- Insulate exterior vent pipe 24 in (610 mm) or longer with 1/2 in (13 mm) insulation.
Applies to: NDF600 series furnaces, horizontal direct and non-direct vent
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NDF installation and operation manual, p. 27, 31. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.