Navien · Furnace troubleshooting

Gas type and high altitude conversion procedure

NPF

What is going on

Converting the furnace to propane or to high altitude natural gas. Use only the Navien conversion kit for the job. Tools needed: Phillips and flathead screwdrivers, 5/32 in or 4 mm Allen wrench, combustion analyzer or dual port manometer, gas leak detector.

Check in this order

  1. Turn off power, gas and water supply (if a supply valve is used). Let the furnace cool if it was running.
  2. Loosen the knobs on the upper front cover counterclockwise, remove them, then remove the cover.
  3. With the internals exposed, find the gas inlet pipe and gas valve.
  4. Remove the two screws at location A, where the gas valve connects to the gas valve outlet adapter.
  5. Remove the two screws at location B, where the gas valve connecting pipe attaches to the single venturi, then pull the pipe away from the fan assembly.
  6. Remove the two screws holding the gas orifice in the fan assembly, then take out the orifice.
  7. Check the O-ring between the gas valve and its inlet adapter. It must be in good condition and installed; replace it if needed.
  8. Seat the gasket in the port, then install the new orifice from the correct conversion kit. Confirm the orifice sits properly on the gasket.
  9. Reinstall the gas valve outlet adapter and all screws. Do not overtighten.
  10. Set DIP switch 1 for the new gas type (ON for propane, OFF for natural gas).
  11. Turn the gas and water supply back on.
  12. Check the gas/air ratio with a combustion analyzer (recommended) at the analyzer port, or by the other method in the manual, against the CO2 values in Table 2. Keep CO2 within 1.0% of the listed value.
  13. Set the installation altitude on the front control panel.
  14. Reinstall the upper front cover and check that the furnace runs normally.

Applies to: NPF700 series furnaces (natural gas to propane or high altitude natural gas)

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NPF Condensing Hydro-furnace installation and operation manual, p. 131 to 136. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.