Navien · Furnace troubleshooting

Freeze protection for condensate drain

NDF

What is going on

The trap and drain line should stay inside conditioned space. Where temperatures can reach 32 F (0 C), protect the trap and drain line. A rated self-regulating heat tape can be used, and RV antifreeze can protect the trap during long cold shutdowns.

Likely causes

  • Condensate freezing in the drain line or trap in areas below 32 F (0 C)
  • Freezing that blocks drainage and disrupts furnace operation

Check in this order

  1. Route the furnace, trap, and drain line within conditioned space where possible.
  2. Wrap the trap and drain line with self-regulating, shielded, waterproof heat tape rated 3 to 6 W/ft (10 to 20 W/m) at 115 V, 40 F (4 C).
  3. Secure the heat tape with plastic ties and follow the heat tape maker's instructions.
  4. Use RV antifreeze in the trap if the furnace will be off for long cold periods.
  5. Prime the trap before starting the furnace.

Applies to: NDF condensate drain system

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NDF Installation and Operation Manual, p. 45. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.