Navien · Furnace troubleshooting
Freeze protection for condensate drain
What is going on
The trap and drain line should stay inside conditioned space. Where temperatures can reach 32 F (0 C), protect the trap and drain line. A rated self-regulating heat tape can be used, and RV antifreeze can protect the trap during long cold shutdowns.
Likely causes
- Condensate freezing in the drain line or trap in areas below 32 F (0 C)
- Freezing that blocks drainage and disrupts furnace operation
Check in this order
- Route the furnace, trap, and drain line within conditioned space where possible.
- Wrap the trap and drain line with self-regulating, shielded, waterproof heat tape rated 3 to 6 W/ft (10 to 20 W/m) at 115 V, 40 F (4 C).
- Secure the heat tape with plastic ties and follow the heat tape maker's instructions.
- Use RV antifreeze in the trap if the furnace will be off for long cold periods.
- Prime the trap before starting the furnace.
Applies to: NDF condensate drain system
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NDF Installation and Operation Manual, p. 45. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.