Erratic operation from vapor lock in drain line
What is going on
The drain configuration needs a vent. Less than a one inch rise along the horizontal drain run can form a vapor lock, which stops condensate from draining freely and causes erratic furnace operation.
Likely causes
- Less than a one inch rise anywhere along the horizontal drain run creates a vapor lock
- Missing vent on the drain system
Check in this order
- Check the horizontal drain run for any rise and remove it.
- Confirm the drain vent branch is installed.
- Confirm the drain slopes continuously toward the outlet.
Applies to: NDF condensate drain system
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NDF Installation and Operation Manual, p. 45. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.