Navien · Furnace troubleshooting

Draining the condensate trap

NPF

What is going on

Drain and remove the condensate trap for service. Step 1 is on the previous page (143) and is not included here.

Check in this order

  1. Connect the 3/4" condensate hose from the parts kit to the drain adapter.
  2. Turn the drain valve on the drain adapter 90 degrees clockwise, then lift the lever on the pressure relief valve to open it.
  3. Remove the clip from the overflow hose and condensate drain hose, then remove the two screws holding the condensate trap and take the trap out of the furnace.
  4. Drain the condensate water from inside the trap.
  5. After the trap is fully drained, fit the two screws to fix the drain trap to the furnace, then reinstall the clip on the overflow hose and condensate hose.

Applies to: NPF700 series (all listed models)

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NPF installation and operation manual, p. 144. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.