Navien · Furnace troubleshooting
Convert the drain trap assembly for right-side installation
What is going on
Changes the condensate drain trap, overflow and grommet layout from the left-side arrangement to the right-side arrangement.
Check in this order
- Disconnect the condensate drain hose, junction box, supply water assembly and drain trap assembly.
- Loosen each hose fastener with pliers and disconnect the hoses.
- Move the grommets from the right side of the cabinet into the openings that were cleared on the left side.
- Replace the drain trap with the included right-type condensate drain hose and overflow hose. Assemble the adapter and fasteners as shown in the manual, using pliers on the hose fasteners.
- Move the overflow plug from the right overflow outlet of the tank to the left overflow outlet.
- Reinstall the right-type drain trap assembly, junction box and supply water assembly.
- After commissioning, run the furnace and check every hose connection for leaks.
Applies to: NPF700 series (all listed models), right-side drain configuration
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NPF installation and operation manual, p. 88-89. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.