Navien · Furnace troubleshooting

Connecting the supplied drain hoses to the trap

NDF

What is going on

Two hoses connect the front manifold cover and the inducer to the trap assembly. The larger tube goes to the manifold, the smaller tube goes to the inducer. All tubing must slope toward the trap with no kinks or low points.

Likely causes

  • Hose low points or kinks ahead of the trap cause trapped water

Check in this order

  1. Connect the 5/8 in. tubing from the most direct drain outlet on the front manifold cover to the larger elbow on the trap.
  2. Cut excess tubing and secure it with the supplied plastic hose clamps.
  3. Connect the 1/2 in. tubing from the inducer drain outlet to the smaller elbow on the trap.
  4. Check that all tubing slopes down toward the trap with no traps or kinks.

Applies to: NDF drain hose connections

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NDF Installation and Operation Manual, p. 44. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.