Connecting the condensate drain

NPF

What is going on

Furnace condensate is acidic (pH about 3 to 5). Dispose of it according to local codes. Choose one of three disposal options and follow the drain rules.

Likely causes

  • Condensate line blocked or frozen, which can cause condensate to back up and damage the furnace
  • Drain line without enough slope
  • Trap not primed

Check in this order

  1. Choose one disposal option (a) direct from the furnace into an external drain; (b) through a neutralizing agent and then into an external drain; or (c) into a condensate pump and then into a suitable drain. Use a pump when the accessible drain is far away.
  2. If using a neutralizer, replace the neutralizing agent periodically, following the neutralizer manufacturer's guidance. Depletion depends on how much the furnace runs.
  3. Use only the drain trap supplied with the furnace, and prime it during installation.
  4. Give the drain line a downward slope of 1/4 in. per foot toward the drain.
  5. Do not add any trap onto the drain line coming from the furnace.
  6. Protect the line from freezing wherever it may see near or below freezing temperatures.
  7. Do not cap or plug the condensate line, and do not let it become obstructed.
  8. If an air conditioning coil shares the drain, install an open tee in the drain line near the cooling coil to relieve positive pressure from the coil plenum so the furnace trap keeps working.
  9. Connect to the furnace drain at the NPT 3/4 in. connection.

Applies to: All NPF700 models

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NPF installation and operation manual, p. 39-40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.