Navien · Furnace troubleshooting
Condensate drain setup and trap mounting
What is going on
The furnace can make up to about 4-1/2 lb of water per hour (about 2 imperial quarts, 2-1/2 US quarts or 2-1/4 liters). Provide a drain path, and protect drains and traps from freezing in spaces that can drop below freezing.
Check in this order
- Mount the condensate trap on the outside of the blower compartment side panel for upflow. For horizontal positions, mount it on the exterior side panels.
- Use the drain hose supplied. Cut it to length for the application so it does not kink, and make sure it can reach the side panel.
- Secure the large plastic clamps on the front manifold cover drain outlet and on the 5/8 in barbed fitting of the trap.
- Secure the small plastic clamp on the inducer drain collar and on the 1/2 in barbed fitting of the trap.
- Tighten the clamps firmly with pliers.
- Angle the inducer drain holes about 15 degrees downward.
- Slope the drain tubing toward the trap and make sure no hose sections form a trap before the condensate trap.
- Push barbed fittings fully into the trap and hoses until they seat on the barb flange.
- Prime the condensate trap with water before the first startup.
- Protect drains and traps from freezing where the space can reach freezing temperatures.
Applies to: Upflow and horizontal installations
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NDF installation and operation manual, p. 37-38. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.