Condensate drain piping to floor drain, sump or pump
What is going on
Condensate from the trap outlet must go to a floor drain, sump pit, or a condensate pump if neither is available. Any pump used must be rated for furnace condensate. A 1/2 in. CPVC tee on the trap outlet gives a vent branch and a drain branch.
Likely causes
- Vapor lock if the tee vent branch is missing or the line has a low point
- Drain blockage if the overflow vent is omitted
Check in this order
- Route condensate from the trap outlet to a floor drain, sump pit, or approved condensate pump.
- Fit a 1/2 in. CPVC tee to the trap outlet with the branches vertical.
- Add a 1 in. (25 mm) piece of 1/2 in. CPVC to the upper branch as a vent and overflow.
- Connect the lower branch to the drain using 5/8 in. ID / 7/8 in. OD flexible tubing, or run CPVC to the drain.
- Do not cement the drain assembly to the trap outlet if the trap may need removal later; use a piece of the supplied 1/2 in. hose instead.
Applies to: NDF condensate drain system
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NDF Installation and Operation Manual, p. 44. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.